ioLogik 2500 Series Quick Installation Guide Smart Remote I/O Edition 5.0, December 2016 Technical Support Contact Information www.moxa.
Package Checklist • • • • • • ioLogik 2500 series device 3-pin screw terminal block (for power input) 2 12-pin screw terminal blocks (for I/O) 2 8-pin RJ45-to-DB9 cables (CBL-RJ45M9-150) 1 antenna (only for wireless modules) Quick installation guide (printed) Appearance Top View Front View -2-
Physical Dimensions (unit = mm/inch) Specifications LAN Ethernet • 4 switched 10/100 Mbps RJ45 ports • 1 optimized port for faster downstream communications with daisy-chained ioLogik E1200 units Note: The optimized daisy-chain port is not supported on wind industry devices (ioLogik E1261W-T, E1261H-T, or E1263H-T) Protection 1.5 kV magnetic isolation Protocols Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP WLAN (ioLogik 25xx-WL1) Standards • IEEE 802.
TX Transmit Power • 802.11b: Typ. 18±1.5 dBm @ 1 to 11 Mbps • 802.11g: Typ. 18±1.5 dBm @ 6 to 24 Mbps, Typ. 17±1.5 dBm @ 36 Mbps, Typ. 16±1.5 dBm @ 48 Mbps, Typ. 16±1.5 dBm @ 54 Mbps • 802.11a: Typ. 18±1.5 dBm @ 6 to 24 Mbps, Typ. 16±1.5 dBm @ 36 Mbps, Typ. 15±1.5 dBm @ 48 Mbps, Typ. 14±1.5 dBm @ 54 Mbps RX Sensitivity • 802.11b: -97 dBm @ 1 Mbps, -94 dBm @ 2 Mbps, -92 dBm @ 5.5 Mbps, -90 dBm @ 11 Mbps • 802.11g: -88 dBm @ 6 to 24 Mbps, -85 dBm @ 36 Mbps, -75 dBm @ 48 Mbps, -70 dBm @ 54 Mbps • 802.
Digital Output (Sink) I/O Mode DO or Pulse Output Pulse Output Frequency 5 kHz Over-voltage Protection 45 VDC Over-temperature 175°C (min.) Shutdown Over-current Protection 1.5 A per channel @ 25°C Current Rating 500 mA per channel @ 25°C Isolation 3k VDC or 2k Vrms Analog Input (ioLogik 2542) Type Differential input Resolution 16 bits I/O Mode Voltage / Current (software selectable) Input Range ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA (with burn-out detection) Accuracy ±0.1% FSR @ 25°C ±0.
Connecting the Power Connect a 9 to 48 VDC power line to the ioLogik 2500’s terminal block V+ terminal; connect the ground from the power supply to the V- terminal. For most applications, it is desirable to ground the system by connecting the system’s power supply common wire to the chassis or panel ground. The negative (–V) side of the DC power input terminal as well as all I/O point terminals labeled GND should be connected to chassis ground.
Type Serial Port (P1/P2) SD Color Green Amber Flashing Off Green Description Tx Rx Data transmitting Disconnected SD card inserted Flashing SD card being accessed Green Channel ON Off Channel OFF or No Counter/Pulse Signal Green Cellular connection established W.
Step 2: Type the model name in the search box or select a product from the drop down box and then click Search. Step 3: Click the Software Packages link to download the latest software for the product. ATEX Information 1. 2. 3. 4. 5.