CONTROLLER CITY MULTI® CONTROLLER 1. MITSUBISHI ELECTRIC’S AIR-CONDITIONER NETWORK SYSTEM (MELANS)..............................................CNTR-2 1-1. Function table of controllers.........................................................................................................................CNTR-3 2. LOCAL REMOTE CONTROLLER..........................................................................................................................CNTR-4 2-1.
CONTROLLER 1. MITSUBISHI ELECTRIC’S AIR-CONDITIONER NETWORK SYSTEM (MELANS) MELANS has a large line-up, including local remote controllers, timers, group controllers, central controllers, integrated system software, PLC and its software, as well as BMS interface hardware and software. The combination of the MELANS products can fulfill the requirements of small-scaled control system, middlescaled control system up to 2,000 indoor units, and/or large-scaled open systems affiliated with a BMS system.
Local remote controller Model Controlable Groups/ Indoors (Groups/Indoors) Operating PAR21MAA PAR-F27MEA PACY151CRB PAR-FL32MAA 1 / 16 1 / 16 AG-150 50 / 50 GB-50ADA 50 / 50 GB-24 24 / 24 TC-24 AG-150 Browser GB-50 Browser *4 GB-24 Browser *7 TG-2000 *4*5 2000 / 2000 1 / 16 1 / 16 ON/OFF Mode(cool/heat/ dry/fan) N Temperature Local Permit/ Prohibit N N N N Fan speed Air-Flow N ON/OFF Mod
DATA U3 2-1. Deluxe MA remote controller [PAR-21MAA] Functions Item TIME SUN MON TUE WED THU FRI SAT TIMER Hr ON AFTER ERROR CODE FUNCTION FILTER WEEKLY SIMPLE AUTO OFF TEMP. MENU PAR-21MAA MONITOR/SET ON/OFF FILTER CLOCK Operation mode switching Temperature setting CHECK TEST OPERATION High-quality white color body and light-green display. Dot LCD is applied. Choose from Japanese, Chinese, English, German, Spanish, Russian, Italian, French displays.
2.LOCAL Local remote controller 2. REMOTE CONTROLLER DATA U3 2-2. ME remote controller [PAR-27MEA-US] Functions Item SET TEMP. TIMER PAR-F27MEA-US FAN SPEED AIR DIRECTION LOUVER VENTILATION Operations Display Description Switches between Cool / Dry / Auto / Fan / Heat. Operation modes vary depending on the air conditioner unit. Auto mode is only for the CITY MULTI® R2- and WR2-Series. FILTER Three timer modes are available with enhanced function.
CONTROLLER 2. LOCAL REMOTE CONTROLLER 2-3. Simple MA remote controller [PAC-YT51CRB] :Each unit :Each group :Each block :Each floor :Collective :Not available Description Item ON/OFF Run and stop operation for a single group Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat. Operation modes vary depending on the air conditioner unit. Auto mode is the CITY MULTI® R2- and WR2-Series only.
2-4. Wireless remote controller [PAR-FL32MA / PAR-FA32MA] CONTROLLER 2. LOCAL REMOTE CONTROLLER Functions HEAT PAR-FL32MA It can operate in a group system without requiring address settings. When operating, it displays LED lamps. When errors occur, the error code can be shown by the LED flash count. If an indoor unit with different functionality is operating inside the same group, please note there may be cases when functionality is partially disabled for batch control.
DATA U3 2-5. PWFY Hydronic Heat Exchanger Remote Controller [PAR-21WMAA] Functions Item TIME SUN MON TUE WED THU FRI SAT TIMER Hr ON AFTER ERROR CODE WEEKLY SIMPLE AUTO OFF ONLY1Hr. TEMP. MENU FUNCTION PAR-21MAA MONITOR/SET ON/OFF FILTER CLOCK Operation mode switching Sets the temperature for a single group Range of temperature setting Cool/Dry : : Heat Auto : ( ) For PDFY/PEFY/PFFY/PVFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.
CONTROLLER 2. LOCAL REMOTE CONTROLLER 2-6. LOSSNAY M-NET remote controller [PZ-52SF] Functions CENTRAL INTERLOCKED Operation mode switching ON/OFF Stand-alone LOSSNAY operation is possible by commands from a centralized controller or LOSSNAY remote controller. (AG-150/GB-50ADA/GB-24/TC-24 are centralized controllers that support LOSSNAY operation.) The LOSSNAY remote controller is capable of changing the air flow and vent modes.
CONTROLLER 3. SYSTEM CONTROLLER 3-1. System group controller [PAC-SF44SRA] Auto only supported for the CITY MULTI® R2- and WR2-Series. ( ) For PDFY/PEFY/PFFY/PVFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only. CNTR-10 CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER System example System remote controller PAC-SC51KUA Power supply MA remote controller LOSSNAY MA remote controller LOSSNAY LOSSNAY LOSSNAY remote controller LOSSNAY remote controller External dimension Unit:mm[in.] 18.5 2[3/32 ] [23/32 ] (Rear view) 120[ 4-23/32 ] 130[5-1/8 ] (Side view) 83.5[ 3-9/32 ] (Front view) 19 [ 3/4 ] 46[1-13/16] CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER 3-2. Schedule timer [PAC-YT34STA] Functions MONITOR PATTERN Sun Mon Tue Wed Thu Fri Sat WEEKLY SET COLLECTIVE GROUP OPERATION ON ON CHECK OFF TIMER OFF SET TEMP. PROH. : Group or collective Unit control 50 units/50 groups (Maximum 16 units connected in one group) Schedule control One week PERMIT ON/OFF MODE TEMP. Operation ON/OFF ON/OFF operations can be carried out collectively or for each group.
CONTROLLER 3. SYSTEM CONTROLLER System example System group controller LOSSNAY PAC-SC51KUA Power supply PAR-F27MEA-US Schedule timer PAR-21MAA PAC-YT51CRA External dimension Unit:mm[in.] 18.5 2[3/32 ] [23/32 ] (Rear view) 120[ 4-23/32 ] 130[5-1/8 ] (Side view) 83.5[ 3-9/32 ] (Front view) 19 [ 3/4 ] 46[1-13/16] CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER 3-3. ON/OFF controller [PAC-YT40ANRA] Functions CENTRALIZED ON/OFF Operation mode switching 16 groups/50 units can be controlled. Up to 16 groups/50 units can be operated with one ON/OFF remote controller. A general-purpose interface is available for control, so general devices can also be turned ON and OFF. Just press a switch to start.
CONTROLLER 3. SYSTEM CONTROLLER System example ON/OFF remote controller LOSSNAY PAC-SC51KUA Power supply PZ-52SF PAR-F27MEA-US PAC-YT51CRB PAR-21MAA External dimension (Front view) 18.1 [ 23/32 ] 130[ 5-1/8 ] (Rear view) ON/OFF 83.5 [3-9/32 ] 120[4-23/32] CENTRALIZED Unit:mm[in.] (Side view) 19 [ 3/4 ] 46[1-13/16 ] CONTROLLER (Sept.
3-4. Touch controller [TC-24] Functions :Each unit :Each floor ● TC-24 features a 5 inch wide color LCD touch panel. The settings for air conditioning units can be changed by touching the corresponding icons on the display. On the panel of TC-24 are 3 buttons; ON/OFF, SET BACK and HOLD enabling simple and quick operation. ● One TC-24 can control up to 24 groups/units of air conditioners. ● Operation status displayed on easy-to-read LCD.
CONTROLLER 3. SYSTEM CONTROLLER System example (1) Connection with CITY MULTI units HOLD COLLECTIVE ON OFF M-NET M-NET SET BACK TOUCH CONTROLLER TC-24A Touch controller TC-24 CITY MULTI Power supply unit PAC-SC51KUA Indoor unit MA remote controller LOSSNAY unit Simple MA remote controller MA remote controller (2) Connection with CITY MULTI and Mr.
CONTROLLER 3. SYSTEM CONTROLLER 1. Power supply to TC-24 TC-24 needs DC power supply of M-NET (24~32VDC) for centralized control transmission use, operation. (1). Power supply of M-NET from power supply unit PAC-SC51KUA. Power supply unit PAC-SC51KUA is recommended for TC-24.
(3) Power supply of M-NET from outdoor unit connector TB3. TC-24 can also receive power supply from R410A/R407C/R22 outdoor unit connector TB3. However, if the outdoor unit shuts down, TC-24 will also automatically shut down. Therefore, this scheme is not recommended for air conditioning system consisting of multiple outdoor units.
CONTROLLER 3. SYSTEM CONTROLLER 2. External input/output usage External input connector External output connector (1). External signal input function External signal input requires the external I/O adapter (Model: PAC-YT41HAA) sold separately. 1). External input External no-voltage contact signal can be used to send signals indicating the following status of all air conditioning units that are controlled : Emergency stop/Normal, ON/OFF, and local remote controller operation Prohibit/Permit.
CONTROLLER 3. SYSTEM CONTROLLER 4). Recommended circuit example (A) For level signal CN2 1 2 Green Yellow X1 X1 ON/OFF or Emergency stop 3 4 5 This unit Max. 10 m (32ft) (B) For pulse signal CN2 1 2 3 4 5 This unit Green Yellow X1 Orange X2 Red Y1 Brown Y2 Max. 10 m X1 X2 Y1 Y2 Run Prohibit Stop Enable (32ft) The relays and extension cables, etc. must be prepared separately at the site. Use a no-voltage contact and minute load relay (minimum application load 5VDC-1mA).
CONTROLLER 3. SYSTEM CONTROLLER 3. Screens of TC-24 CNTR-22 GRID (S) GRID (L) LIST GROUP Status List System-Changeover CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER Operation Lock Prohibit Remote Controller Set Temperature Range Limit Set Schedule Display Format CONTROLLER (Sept.
3-5. Central controller [AG-150] Functions :Each unit :Each group :Each block :Each floor :Collective :Not available Operations Description Item ON/OFF Run and stop operation for the air conditioner units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) Operation modes vary depending on the air conditioner unit. Auto mode is the City Multi R2 and WR2 series only.
3-5-1. Power supply to AG-150 AG-150 needs DC power supply of 24~30V (M-NET) and 24V; the former is for centralized control transmission use and the latter is for AG-150's operating and LAN function use. AG-150 can have power-supply at following 1,2 methods. 3-5-1-1. Power supply unit PAC-SC51KUA is the recommended power supply for AG-150A. The basic scheme is as follows. For details, please refer to Power supply unit PAC-SC51KUA.
CONTROLLER 3. SYSTEM CONTROLLER 3-5-2. External input/output usage 3-5-2-1. External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately. (1) External input Emergency stop/normal, run/stop and prohibit/permit of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source. (Select with the function select setting.
CONTROLLER 3. SYSTEM CONTROLLER 3-5-2-1. External signal input function (4) Recommended circuit example (A) For level signal CN5 Red X1 Run/stop or Emergency stop Orange X1 Power supply(*1) (12VDC or 24VDC) Max.10m (32 ft) This unit (B) For pulse signal CN5 Power supply(*1) (12VDC or 24VDC) Red Gray Blue Yellow Orange This unit Y2 Y1 X2 X1 X1 X2 Y1 Use relays X1, X2, Y1, and Y2 that meet the following specifications. Contact rating Rated voltage >= 12VDC Rated current >= 0.
CONTROLLER 3. SYSTEM CONTROLLER 3-5-3. LAN connection function When using the LAN connection function, connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use 100 BASE-TX Straight cable. For a description of the IP address setting method, refer to Instruction Book. LAN is 100 BASE-TX Specification. LAN NOTE Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-NET transmission line.
CONTROLLER 3. SYSTEM CONTROLLER Browser screens of AG-150 Condition List (Overview) Condition List (Block) °F Condition List (Overview/Floor Layout) Operation Malfunction List Malfunction Log CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER Operation (DIDO Controller) Trend Graph (temperature/humidity) CNTR-30 CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER Liquid crystal displays of AG-150 Floor screen Floor screen (Zoom-out display) Floor layout screen Floor layout screen (Zoom-out display) Weekly schedule setting screen Annual schedule setting screen Block display screen Operation screen CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER Error status screen CNTR-32 CONTROLLER (Sept.
3-6. Central controller [GB-50ADA] Functions :Each unit :Each floor Item A. The central controller of GB-50ADA combines Web function, which enable the air conditioner system management on a PC browser screen. *1. The management can even be carried out remotely. *1 Microsoft® Internet Explorer Ver. 6 or later by Microsoft Corporation is recommended. (Note: You must have operating system which complies with "Sun Microsystems® Java Plug-in". When using Internet Explorer (64 bit), use Java Plug-in (64bit).
CONTROLLER 3. SYSTEM CONTROLLER 1. M-NET power supply GB-50ADA has a built-in function to supply power to the M-NET transmission line. (power supply coefficient: 6) When power is supplied from GB-50ADA, the types of system controllers listed in the table below are connectable. System controller Power consumption coefficient Connectable units System remote controller ON/OFF remote controller Schedule timer Group remote controller 1 0.
3. External input/output usage (1). External signal input function * To use the external signal input, a separately-sold external input/output adapter (PAC-YG10HA) and external power supply are required. External input/output terminal (CN5) MODEL : Serial number : 1).
CONTROLLER 3. SYSTEM CONTROLLER (B) Pulse signals If pulse signals to operate the units are received while the units are in operation, the units will continue their operation (same with the Stop, Prohibit, and Permit signals). When operation from the local remote controllers is prohibited, Run/Stop mode, operation mode, temperature setting, and filter reset settings cannot be changed from the local remote controller. The pulse width (contact ON) should be between 0.5 and 1 second. 4).
CONTROLLER 3. SYSTEM CONTROLLER 4. LAN connection function Connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use an enhanced category 5 UTP cable. For a description of the IP address setting method, refer to Installation Manual. LAN is 100 BASE-TX Specification. The maximum wiring length from HUB to GB-50ADA is 100m [328ft]. GB-50ADA is connected to the monitoring PC via HUB.
CONTROLLER 3. SYSTEM CONTROLLER 5. Browser screens of GB-50ADA Condition List (Overview) Condition List (Block) Operation Malfunction List Malfunction Log Weekly 1 Schedule °F CNTR-38 CONTROLLER (Sept.
Operation (DIDO Controller) Trend Graph (temperature/humidity) CONTROLLER 3. SYSTEM CONTROLLER Measurement status monitor (temperature sensor/humidity sensor /measurement meter) Trend Graph (Peak cut control) CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER 3-7. Central controller [GB-24] Functions 130 (5 /8) :Each group :Each block :Each floor :Collective :Not available Operations Description Item 1 :Each unit ON/OFF Run and stop operation for the air conditioning units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat / Setback. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) *Operation modes vary depending on the air conditioner unit.
3-7-1. Power supply to GB-24 GB-24 needs DC power supply of M-NET (24~32VDC) for centralized control transmission use, operation and LAN function use. (1). Power supply of M-NET from power supply unit PAC-SC51KUA. Power supply unit PAC-SC51KUA is recommended for GB-24.
CONTROLLER 3. SYSTEM CONTROLLER (3) Power supply of M-NET from outdoor unit connector TB3. GB-24 can also receive power supply from R410A/R407C/R22 outdoor unit connector TB3. However, if the outdoor unit shuts down, GB-24 will also automatically shut down. Therefore, this scheme is not recommended for air conditioning system consisting of multiple outdoor units. Indoor/outdoor transmission line TB3 CN41 ME remote cotroller Centralized controller GB-24 CNTR-42 Fig. 3 GB-24, TB3 scheme.
CONTROLLER 3. SYSTEM CONTROLLER 3-7-2. External input/output usage CN2 (1). External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately. 1). External input Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
CONTROLLER 3. SYSTEM CONTROLLER 4). Recommended circuit example (A) For level signal CN2 Red 9 X1 Run/stop or Emergency stop 8 7 6 5 Orange 1 X1 Power supply (12VDC or 24VDC) Max.10m (32 ft) This unit (B) For pulse signal CN2 9 Power supply (12VDC or 24VDC) Red Gray Blue Yellow Orange 8 7 6 5 1 Y2 Y1 X2 X1 X1 Y1 Y2 Run Stop Prohibit Enable Max.10m (32 ft) This unit X2 Use relays X1, X2, Y1, and Y2 that meet the following specifications.
CONTROLLER 3. SYSTEM CONTROLLER 3-7-3. LAN connection function Connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use an enhanced category 5 UTP cable. For a description of the IP address setting method, refer to Installation Manual. LAN is 10 BASE-T Specification. The maximum wiring length from HUB to GB-24 is 100m [328ft]. GB-24 is connected to the monitoring PC via HUB.
CONTROLLER 3. SYSTEM CONTROLLER 3-7-4. Browser screens of GB-24 Condition List (Overview) Operation (with Setback) Malfunction Log CNTR-46 CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER Operation (DIDO Controller) Measurement status monitor (temperature sensor/humidity sensor /measurement meter) Trend Graph (temperature/humidity) Weekly Schedule CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER 3-8. Power supply unit [PAC-SC51KUA] PAC-SC51KUA supplies DC power of M-NET (22-30V) and 24V at TB2 and TB3 respectively; the former is for centralized transmission use and the latter is for AG-150 operation and LAN function use. 3-8-1. When using PAC-SC51KUA as the power supplier for system controller, the capacity for system controller is considered as follows.
3-2. When supply power to 1 AG-150, the PAC-SC51KUA can supply power to other system controllers as follows. Table 3 Connectable number of system controller when 1 AG-150 is used. V : Connectable Total number of ON/OFF remote controller(AN) Total number of System remote controller(SR) Schedule timer(ST) 0 1 2 3 4 5 0 V V V V V 1 V V V V V 2 V V V V 3 V V V V 4 V V V 5 V V V 6 V V 7 V V 8 V 9 V 10 CAUTION 3-3.
External dimension Unit:mm[in.] 72(2-7/ 8) T TB2,TB3 CNTR-50 CONTROLLER (Sept. 2010) TB1 155(6-1/ 8) This device complies with Part15 of the FCCRules.Operation is subject to the following two conditions:(1)this device may not cause harmful interference,and(2)this device must accept any interference received,including interference that may cause undesired operation. UP 169(6-11/ 16) 271(10-11/16) 90(3-9/16) 130(5-1/ 8) CONTROLLER 3.
CONTROLLER 3. SYSTEM CONTROLLER 3-9. Integrated centralized control software [TG-2000] 3-9-1. Example of Basic System Configuration.
CONTROLLER 3. SYSTEM CONTROLLER 3-9-2. List of TG-2000 functions The data for each GB-50 can be grouped and used to control the operation of up to 2000 units in floor or block units, etc., from the personal computer screen. By using a watt-hour meter or DIDO (PAC-YG66DCA), the power r ate can be appor tioned, and other general equipment can be controlled. List of integral software functions GB-50 license The units can be turned ON and OFF for all floors or in block, floor or group units.
(2). The data for each AG-150 can be grouped and used to control the operation of up to 2000 units in floor or block units,etc., from the personal computer screen. By using a watt-hour meter or DIDO (PAC-YG66DCA), the power rate can be apportioned, and other general equipment can be controlled. List of integral software functions AG-150 license ON/OFF The units can be turned ON and OFF for all floors or in block, floor or group units.
CONTROLLER 3. SYSTEM CONTROLLER 3-9-3. Browser screens of TG-2000 Weekly schedule screen Floor screen Annual schedule screen Block screen All floor screen Operation setting screen Air-conditioning charge screen CNTR-54 CONTROLLER (Sept.
3-9-4. Requirements (system recommendations) We recommend the following software and hardware when using this application (TG-2000). TG-2000 version When AG-150/GB-50ADA-compatible TG-2000 is used TG-2000 Ver.5.50 or later *1 System Requirements OS : Windows Vista/XP Refer to the table below for details. *1 : TG-2000 Ver.5.20 is upgraded to Ver.5.50 or later. Item PC CPU Memory HDD Requirement Recommended PC/AT interchangeable machine (Recommended: IBM, HP,DELL) CoreTM 2 Duo 1.
CONTROLLER 3. SYSTEM CONTROLLER 3-9-5. Compatible Units The TG-2000 has two main functions: centralized control of air conditioners and cost accounting. However, not all functions are available with all air conditioners.
DATA U3 3-11. Electric amount count count software [PAC-YG11CDA] 3-10. Electronic amount software [PAC-YG11CDA (SW-CHANGE)] MITSUBISHI ELECTRIC offers charging function for the air conditioner system. Detailed output of every indoor on electricity consumption of air-conditioning is available. The electricity consumption of air-conditioner is counted based on the refrigerant consumption of every indoor unit, which makes the proportion of electricity consumption precise.
3-11. BM Adapter [BAC-HD150] (BTL Listed) CITY MULTI can easily combine into a Building Management System (BMS) via the BACnet ® and M-NET adapter BAC-HD150. BACnet is an opened transmission protocol widely used at BMS, and related equipment control. CITY MULTI is therefore compatible with large-scaled BMS management via BACnet. BAC-HD150 can control up to 50 units/groups(including LOSSNAY). Specifications Items Rated input Power source Interface Ambient conditions Specifications 100-240 VAC ±10 % 0.
CONTROLLER 3. SYSTEM CONTROLLER System Example (Connecting 50 units/groups) Central monitor BMS LAN LAN ® BACnet /IP M-NET M-NET BAC-HD150 MA remote controller MA remote controller MA remote controller M-NET PAC-SC51KUA LOSSNAY unit AG-150 LAN MA remote controller CONTROLLER (Sept.
CONTROLLER 3. SYSTEM CONTROLLER ® ® interface [LMAP03U] 3-12. LonWorks 3-15. LonWorks interface [LMAP03U] CITY MULTI® can easily combine into a Building Management System (BMS) via the LONWORKS and M-NET adapter LMAP03U. LONWORKS is an opened transmission protocol widely used at BMS and related equipment control. CITY MULTI® is therefore compatible with large-scaled BMS management via LONWORKS . ® ® ® One LMAP03U serves up to 50 indoor units. (CITY MULTI , Mr. Slim , and LOSSNAY .
CONTROLLER 3. SYSTEM CONTROLLER Environment specification Item Description Connected Equipment MITSUBISHI ELECTRIC Number of Units LMAP can control 50 indoor units (including LOSSNAY) Neuron CHIP TMPN3150 (10MHz) CITY MULTI Mr.Slim LOSSNAY Multiple split-type air conditioners Split-type air conditioners Heat recovery ventilators ( For details of the connectable models,please contact the dealer.) Network Transceiver Performance FTT-10A (Free Topology 78kbps) Average communication capacity 2.
3-13. DIDO controller [PAC-YG66DCA] The DIDO controller is used in combination with a(n) AG-150/GB-50ADA/GB-24/TC-24 to operate general-purpose equipment, as well as to monitor operating and error status. It is equipped with two sets of standard terminal s (Channels 1 and 2), and four sets of expansion connectors for the input/output terminals. Expansion cable is optional. Other devices can only be controlled from AG-150/GB-50ADA/GB-24 Web browser and TG-2000.
CONTROLLER 3. SYSTEM CONTROLLER 3-13-1. Specifications 3-13-1-1. Device Specifications Item Power Supply Rating and Specification M-NET communication Standard ON/OFF, (ON) (*4) (OFF) (*4) Expansion Input Output Screw terminal block (M3) (*8) Applied load MAX: 24 VDC, 5 W Non-voltage Relay contact (2) MIN: 5 VDC, 2 mW * AC loads cannot be connected. Screw terminal block (M3.
CONTROLLER 3. SYSTEM CONTROLLER 3-13-1. Specifications 3-13-1-1. Device Specifications Centralized control line Power supply unit PAC-SC51KUA M-NET LAN M-NET Indoor control line DIDO controller CENTRALIZED CONTROLLER AG-150A AG-150 or GB-50ADA *1 CITY MULTI 24 VDC Power supply (a) (b) (c) (d) Ventilation fan, lighting, etc. × up to 6 units DIDO control 24 VDC Power supply (a) (b) (c) (d) AG-150/GB-50ADA Web or TG-2000A*2 Ventilation fan, lighting, etc.
CONTROLLER 3. SYSTEM CONTROLLER 3-13-1. Specifications 3-13-1-2. Parts Purchased Separately Prepare the following parts to install this device. Required Part Specification Unit fixing screws M4 screw Power supply for this device Commercially available power source: 24 VDC 10% 0.
CONTROLLER 3. SYSTEM CONTROLLER 3-13-3. Interlock control The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller. Interlock control covers the units connected to the DIDO controller with M-NET system. AG-150/GB-50ADA/GB-24/TC-24 must be connected to use the function. Ask your dealer for interlock control setting.
3-14. AI controller [PAC-YG63MCA] The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints. Historical measurement data can be displayed via only the AG-150/GB-50ADA Web browser and TG-2000. Temperature and humidity cannot be displayed on the AG-150 LCD. Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
3-14-1. Specifications 3-14-1-1. Device Specifications Item Power Supply Description 24 VDC 10%: 5 W M-NET communication Ch 17 to 30 VDC (*1) Sensor Ch2 (*2) Interlock Function Environment Conditions Dimensions Weight Time Backup During Power Failure Installation Environment Analog Ch1 Analog Interface Input Pt100 (3-wire system) Output CONTROLLER 3.
CONTROLLER 3. SYSTEM CONTROLLER 3-14-1. Specifications 3-14-1-1. Device Specifications Centralized control line Power supply unit PAC-SC51KUA M-NET LAN M-NET TB7 CENTRALIZED CONTROLLER AG-150A AG-150 or GB-50ADA *1 Indoor control line TB3 AI controller CITY MULTI 24 VDC Power Supply (3) (4) AI controller AG-150/ GB-50ADA Web or TG-2000A *2 24 VDC Power Supply (3) (4) (1) (2) Temperature sensor, humidity sensor, etc. Upper/lower limit alarm interlock devices, etc.
CONTROLLER 3. SYSTEM CONTROLLER 3-14-1. Specifications 3-14-1-2. Parts Purchased Separately Prepare the following parts to install this device. Required Part Specification Unit fixing screws M4 screw Power supply for this device Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal Ripple noise: Lower than 200 mVp-p Compatible specification Authorized or CE marked products.
3-14-2. Interlock control AI controller (PAC-YG63MCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units. Interlock control covers the units connected to the AI controller with M-NET system. AG-150/GB-50ADA /GB-24 must be connected to use the function. Ask your dealer for interlock control setting. The setting requires special tool support. CAUTION Before using the interlock control, you must agree to the following. 1.
3-15. Transmission booster [PAC-SF46EPA] The Outdoor unit supplies transmission power 30VDC for the indoor-outdoor transmission line at its connector TB3 and TB7. The power is consumed by the Indoor unit, ME remote controller, Timers and System controllers.
In a multi air conditioner system that is a free plan direct-expansion type, a connector for inputting and outputting signals to/from the outside is fitted as standard on the control board of the indoor and outdoor units. Use this when you want each unit to input/output signals individually. (Note: When there are many control units it is recommended that you use MELANS. This would enable you to save on labor.
CONTROLLER 4. SYSTEM COMPONENT Note 1: Connect the signal input only to the principal unit in a group. (However, the demand input is required to enter into indoor units individually.) Note 2: When using star t/stop input at group operation, Local remote controller is necessary. (MA remote controller or M-NET remote controller) Note 3: When setting to Remote, operation can not be performed from Local remote controller.
It is possible to have ON/OFF control by turning the indoor unit power on and off. You can select functions by setting the DipSW1-9 and 1-10 on the indoor unit. Types of ON/OFF control (indoor unit settings) It is possible to have ON/OFF control for each indoor unit (or group) by dip switches 9 and 10 (SW1-9, SW1-10) of the indoor unit.
CONTROLLER 4. SYSTEM COMPONENT 4-1. Y-, R2-, H2i®, S-Series CITY MULTI system can be monitored or controlled with signal to/from the outside as every control board of Indoor unit or Outdoor unit has input/output signal connectors. Independent control to the individual Indoor or Outdoor can be carried out by using these connectors. Yet, for large-scale control, MELANS would be much easier.
Table 4-2. Control can be achieved by using Indoor input/output connectors. Signal Using connector Function Usage Remote/Local switching *1 Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to Input CN32 ON/OFF *2*3 the connector of the head Indoor in an Indoor group.
4-2. Outdoor unit input/output connector (Y-, R2-, S-Series) 1.Wiring should be covered by insulation tube with supplementary insulation. 2.Use relays or switches with IEC or equivalent standard. 3.The electric strength between accessible parts and control circuit should have 2750V or more. Caution: 4-2-1. Output • State (CN51) Distant control board L1 Lamp power source CONTROLLER 4.
S-Series (1) Step demand and Silent mode (Night mode) (CN3D) Relay circuit Outdoor unit control board Adapter *2 X 1 2 Y 3 Relay circuit CN3D X Adapter *2 1 2 Outdoor unit control board CN3D 3 Preparations in the field Preparations in the field Maximum cable length is 10m X,Y : Relay Contact rating voltage >= 15VDC Contact rating current >= 0.1A Minimum appicable load =< 1mA at DC *2. Optional part : PAC715AD or field supply.
CONTROLLER 4. SYSTEM COMPONENT 4-3. WY, WR2-Series CITY MULTI system can be monitored or controlled with signal to/from the outside as every control board of Indoor unit or water source unit has input/output signal connectors. Independent control to the individual Indoor or water source can be carried out by using these connectors. Yet, for large-scale control, MELANS would be much easier.
Table 4-2. Control can be achieved by using Indoor input/output connectors. Signal Using connector Function Usage Remote/Local switching *1 Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to Input CN32 ON/OFF *2*3 the connector of the head Indoor in an Indoor group.
4-4. Water-source input/output connector 1.Wiring should be covered by insulation tube with supplementary insulation. 2.Use relays or switches with IEC or equivalent standard. 3.The electric strength between accessible parts and control circuit should have 2750V or more. Caution: 4-4-1. Output • State (CN51) Distant control board L1 Lamp power source CONTROLLER 4.
CONTROLLER 4. SYSTEM COMPONENT 4-5. Indoor unit “-E” type input/output connector 1.Wiring should be covered by insulation tube with supplementary insulation. 2.Use relays or switches with IEC or equivalent standard. 3.The electric strength between accessible parts and control circuit should have 2750V or more.
CONTROLLER CNTR-84 CONTROLLER (Sept.