MITSUBISHI ELECTRIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM MODEL 2033A SERIES OWNERS / TECHNICAL MANUAL
Preface Revision 2.5 Sep.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: i TABLE OF CONTENTS LIST OF TABLES ................................................................................................ ii LIST OF FIGURES .............................................................................................. iii HOW TO USE THIS MANUAL ............................................................................ iv 1.0 INTRODUCTION...............................................................
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: ii LIST OF TABLES Table 1.1 UPS Installation Environment ....................................................... 1-6 Table 1.2 Rating of Bypass input circuit breaker .......................................... 1-7 Table 1.3 Power Specifications..................................................................... 1-16 Table 1.4 UPS Module Information...............................................................
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: iii LIST OF FIGURES Figure 1.1 Single Line Diagram-Normal Operation........................................ 1-10 Figure 1.2 Single Line Diagram-Bypass Operation ....................................... 1-11 Figure 1.3 Single Line Diagram-Battery Operation........................................ 1-12 Figure 1.4 Single Line Diagram - UPS on Maintenance Bypass Operation.. 1-12 Figure 1.5 UPS Parts Location...................
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: iv HOW TO USE THIS MANUAL This manual is designed for ease of use, giving the user easy and quick reference to information. This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of this manual.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 1.0 Page Number: 1-1 INTRODUCTION The Mitsubishi Uninterruptible Power Supply (UPS) is designed to provide many years of reliable power supply and protection from power failure, brown-outs, line noise and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions accordingly. This manual contains descriptions for the installation and operation procedures of the UPS.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 1-2 1.1 SAFETY PRECAUTIONS The safety precautions are categorized as DANGER and CAUTION in this manual. DANGER : A dangerous situation may occur if improperly handled, leading to severe or fatal injuries. CAUTION: A dangerous situation may occur if improperly handled, leading to minor serious injuries. Note that some items described as CAUTION may lead to severe results depending on the situation.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-3 CAUTION PRECAUTIONS FOR INSTALLATION Do not block the intake/exhaust ports. -If the intake/exhaust ports are blocked, the internal temperature of the UPS will rise and could lead to fires from battery electrolyte leakage, fire ignition or part deterioration. Follow the UPS instruction manual carefully when installing the unit. -Improper installation could lead to injury such as the UPS falling over, etc.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 1-4 CAUTION PRECAUTIONS FOR MAINTENANCE AND INSPECTION The inside of the UPS must be inspected or repaired only by qualified personnel. -Failure to observe this could lead to electrical shocks, injuries, burns, smoke generation or fires. Periodically replace the battery. -Batteries that have exceeded the replacement life could lead to fires from electrolyte leakage or fire ignition.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-5 APPLICATION This UPS shall NOT be applied to support equipment (*) that could affect the human lives. Special considerations are required when applying this UPS to the equipment (**) that affect human safety and/or maintain public services. Be sure to contact/inform MITSUBISHI if it is such a case. The application without special consideration may cause serious accidents.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC WARNING Page Number: 1-6 3 The UPS is to be installed in a controlled environment. Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions. Keep the installation environment per standard described as follows: UPS Installation Environment TABLE 1.1 No.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC WARNING Page Number: 1-7 4 This UPS does not include a Bypass Input circuit breaker (MCCB). The Bypass Input contactor (CB3) does not protect against load induced short circuits. The bypass input circuit breaker (MCCB) is field supplied and installed. When Bypass Input is fed by an input transformer the requirement for Bypass Input circuit breaker can be met with circuit breaker (MCCB) on the primary side of the transformer.
MITSUBISHI ELECTRIC 1.2 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-8 GENERAL The Mitsubishi 2033A Series UPS is designed to provide continuous and clean electrical power to a critical load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time. If the input power is not restored promptly, back up power from the UPS battery permits the orderly shutdown of equipment supported by the UPS.
MITSUBISHI ELECTRIC 1.3 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-9 DEFINITIONS UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cabinet includes the batteries which function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System".
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 1.4 Page Number: 1-10 OPERATION OVERVIEW The UPS provides two power paths between the utility source and the critical load as shown in Figures 1.1 and 1.2. FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered through inverter.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 1-11 FIGURE 1.2 Single Line Diagram - Internal Bypass. Load fed through static bypass line.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 1-12 FIGURE 1.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-13 The rotary maintenance bypass switch is identified as 52CS in Figure 1.4. 52CS is a two position make-before-break transfer switch. The two positions are identified as NORMAL and BYPASS. In the NORMAL position the load is fed by the UPS - either through the inverter or through the static bypass line. In the BYPASS position the load is powered by an external source such as the utility or a generator.
FIGURE 1.5 Page Number: 1-14 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC UPS Parts Location UPS module FRONT VIEW Converter & Inverter Unit 11. 52CS 13. SW2 14. CB101 CB3 5. Grounding Bar 3. CB2 2. CB1 4. External contact signal terminal block UPS module BACKSIDE OF FRONT DOOR Inverter Start/Stop switch 6. Error RESET 12. Switch PCB DPAU-55 LCD panel Buzzer Stop INV START STOP CNV SW ON Main PCB UPER-V/UPFR-G 1.
Page Number: 1-15 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Description of Figure 1.5: 1. Emergency bypass switch (SW1) This switch activates the bypass power supply for emergency reasons if the UPS is turned off. Normal position is “TRANSFER is PERFORMED”. 2. AC Input circuit contactor (CB1) Contactor for converter input power. 3. Battery Disconnect circuit contactor (CB2) Contactor for battery input. 4.
Page Number: 1-16 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 1.5 SPECIFICATIONS The UPS name plate displays the rated kVA as well as nominal voltages and currents. The nameplate is located on the interior side of the UPS front door. TABLE 1.
Page Number: 1-17 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC TABLE 1.6 Input/Output Transformer Cabinet Information (480V input, 480V output) HEAT LOSS UPS CABLE WIDTH DEPTH HEIGHT WEIGHT (kVA) ENTRY (in/mm) (in/mm) (in/mm) (lb.) 30 TOP / BOTTOM 24.1 / 610 29.1 / 740 70.9 / 1800 930 6.7 40 TOP / BOTTOM 24.1 / 610 29.1 / 740 70.9 / 1800 1255 9.0 50 TOP / BOTTOM 24.1 / 610 29.1 / 740 70.9 / 1800 1350 11.2 75 TOP / BOTTOM 24.1 / 610 29.1 / 740 70.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC TABLE 1.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 1-1
Page Number: 1-19 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC TABLE 1.
Page Number: 2-1 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 2.0 OPERATOR CONTROLS AND INDICATORS The 2033A Series operator controls and indicators are located as follows: Circuit breakers and contactors : Inside the module UPS status indicators : Outside of door FIGURE 2.1 Operation/Display Panel (Front panel) MITSUBISHI 22003333A AS SE ER RIIE ES SU UP PS S 3 4 5 6 2 1 LOAD ON INVERTER BATTERY OP. LOAD ON BYPASS OVERLOAD LCD FAILURE UPS FAILURE 7 EMRG.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 2-2 2.1 LED Display 1) Load on inverter (green) Turned on when power is supplied from inverter to the critical load. (Indicates the state of transfer switch "52C" of inverter.) 2) Battery operation (yellow) Turned on when the battery is operating following an AC power failure.. 3) Load on bypass (yellow) Turned on when power is supplied through bypass to load devices. (Indicates the state of transfer switch "52S" of bypass.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 2-3 2.2 Liquid Crystal Display ( 7 in Figure 2.1 ) The Liquid Crystal Display (LCD) panel indicates the power flow, measured values, operational guidance, data record and error messages. The LCD panel is back-lit to facilitate viewing in different ambient lighting conditions. The LCD will automatically clear if the keyboard is not activated for 3 minutes.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 2-4 2) Input Voltage and Current (Figure 2.4) The voltages displayed are the RMS AC input voltages (line-to-line) between phases A-B, B-C C-A and frequency of the AC input line. The RMS values of phases A, B and C currents are also displayed. FIGURE 2.4 Input screen 3) Output Voltage, Output Current and Trend Graph The voltages displayed on the LCD include the inverter output voltages A-B, B-C, C-A.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 2-5 FIGURE 2.7 Trend graph screen 4) Battery (Figure 2.8) This displays the charging, discharging or float mode of the battery, battery current and battery voltage. FIGURE 2.8 Battery screen 5) Remote / Local Selection (Figure 2.9) The system asks user to select whether the start & stop operation will be performed by a local or remote operation. FIGURE 2.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 2-6 B) OPERATION MENU (Figure 2.10) The following will be displayed when the OPERATION MENU button is pressed on the LCD FIGURE 2.10 Operation menu screen 1) START-UP GUIDANCE The display indicates the operation from closing circuit breakers to starting the inverter. When the inverter is started, the display shows the MAIN MENU. When the display changes, the annunciator sounds 3 times requesting user to perform next procedure.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 2-7 2.2.2 INPUT POWER FAILURE During an Input Power Failure the UPS will run on the Batteries. The following will be displayed. The indication of battery operation, load factor, and time remaining. FIGURE 2.11 Battery Operation Screen The LCD will display a battery low voltage announcement when battery capacity is near depletion. FIGURE 2.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 2-8 2.2.3 FAULT INDICATION (Figure 2.14) The display shows a fault code, description of fault and a guidance of what action is to take place by the user. A maximum of 10 faults are displayed at the same time. When an input power failure occurs during the fault Indication, the fault indication and input power failure are alternatively displayed at 5 second intervals. FIGURE 2.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 2-9 2.3 External Signal Terminal Block The UPS is equipped with a series of input/output terminals for the external annunciation of alarms and the remote access of certain UPS functions. A functional description of the input/output port is presented below. Layout of terminals is shown in Figure 2.15 FIGURE 2.
Page Number: 2-10 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC A) Output Contacts(for external alarm annunciation) Output contacts consist of form “A” dry type contacts. Rated value of all output contacts is 120Vac/0.5Aac or 30Vdc/1Adc. Operate all dry contacts at their rated values or lower. Figure 2.16 illustrates typical installation. The external relay can also be a lamp, LED, computer, etc. Connection not to exceed NEC Class 2. FIGURE 2.
NOTE: Page Number: 2-11 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC. for set-up information. B) Input Contacts(for remote access of UPS) External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly.
Page Number: 2-12 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC remote operation. Refer to Operations Menu for procedure. Terminals 13 to 14 "Power Demand Command" contact input (IN2) Used to control the input current limit to the UPS converter (usually during generator operation). Power demand is turned ON when the contact is closed. Power demand is turned OFF when the contact is open.
Page Number: 3-1 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 3.0 INSTALLATION AND OPERATION 3.1 Transportation and Installation TABLE 3.1 How to transport and install the system Transportation Installation Transport unit with forklift. Using the holes (4 - 24) pre drilled into the Use eye bolts (supplied) to carry with UPS channel base, anchor the unit using overhead crane. appropriate hardware. Note : Do not transport in a horizontal position.
Page Number: 3-2 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC D) External Battery Supply Please refer to the following when installing batteries: 1. The customer shall make reference to the battery manufacturer's installation manual for battery installation and maintenance instructions. 2. The maximum permitted fault current from the remote battery supply and the DC voltage rating of the battery supply over-current protective device are shown in Table 3.3. TABLE 3.
Page Number: 3-3 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC input power terminals identified as A10, B10, C10 in Figures 3.2-a~b and Figures 3.3-a~m. Input cables must be sized for an ampacity larger than the maximum input drawn by the converter. Refer to Table 3.4.a for recommended cable sizes. B. Confirm that an external bypass input circuit breaker (MCCB) is installed (refer to WARNING 2).
MITSUBISHI ELECTRIC 3. 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 3-4 For configurations that utilize an Input Trans/MBP Combination Cabinet: A. Connect the bypass input power cables from Bypass Input Isolation Breaker (MBP SW1) Terminals A, B and C to the UPS bypass input power terminals identified as A30, B30 and C30. Connect Input Transformer/MBP Neutral to UPS Terminal N60. Refer to Figures 3.2-a~b and Figure 3.3.e.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 3-5 NOTES: 1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and "CB3" are open before energizing UPS. 2. UPS power terminals are supplied with stud type fittings. It is recommended that compression lugs be used to fasten all UPS input/output power cables. Refer to Table 3.5.a for recommended compression lugs and appropriate crimping tool. 3.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Table 3.4.a UPS Capacity (kVA) 30kVA (208V) 30kVA (480V) 30kVA (600V) 40kVA (208V) 40kVA (480V) 40kVA (600V) 50kVA (208V) 50kVA (480V) 50kVA (600V) 75kVA (208V) 75kVA (480V) 75kVA (600V) Page Number: 3-6 Recommended cable size and torque requirements (for UPS) Input Side * 1, 2 Cable Torque Size (in. lbs) 1 AWG 100-135 or larger in. lbs 1 AWG 100-135 or larger in. lbs 1 AWG 100-135 or larger in. lbs 1/0 AWG 200-269 or larger in.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 3-7 Table 3.4.
Page Number: 3-8 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC TABLE 3.5a Crimp Type Compression Lug (UPS) WIRE SIZE WIRE STRAND (CODE) CLASS VENDOR CAT. NO.
Page Number: 3-9 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC TABLE 3.5.b Crimp Type Compression Lug (Transformer Field Terminations) WIRE SIZE WIRE STRAND (CODE) CLASS VENDOR CAT. NO.
Page Number: 3-10 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC FIGURE 3.1 UPS Terminal Designation AC Bypass Input Static Transfer Switch Terminals: A30, B30, C30, N60 CB3 CONVERTER AC input Terminals: A10, B10, C10 CB1 INVERTER 52S Output Terminals: A60, B60, C60, N60 52C FC Terminals: BP,BN FB CB2 Battery cabinet UPS Module Table 3.6 Wiring configuration Figure Input Output One feed Input Output Voltage Voltage / Two feed Transformer Transformer 3.
FIGURE 3.
MITSUBISHI ELECTRIC Page Number: 3-12 2033A SERIES UPS OWNERS / TECHNICAL MANUAL FIGURE 3.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-13 FIGURE 3.3 a Wiring configuration for 208V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-14 FIGURE 3.3 b Wiring configuration for 208V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-15 FIGURE 3.3 c Wiring configuration for 480V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-16 FIGURE 3.3 d Wiring configuration for 480V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-17 FIGURE 3.3 e Wiring configuration for 480V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-18 FIGURE 3.3 f Wiring configuration for 480V input / 480V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-19 FIGURE 3.3 g Wiring configuration for 480V input / 480V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-20 FIGURE 3.3 h Wiring configuration for 480V input / 480V output with transformer cabinet.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-21 FIGURE 3.3 i Wiring configuration for 600V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-22 FIGURE 3.3 j Wiring configuration for 600V input / 208V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-23 FIGURE 3.3 k Wiring configuration for 600V input / 600V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-24 FIGURE 3.3 l Wiring configuration for 600V input / 600V output.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-25 FIGURE 3.3 m Wiring configuration for 600V input / 600V output with transformer cabinet.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-26 3.4 Operating Procedures A) UPS Start-up Procedure 1. Verify that SW2 (contactor CB3 operator) is in the OFF position. 2. Close Control Circuit Breaker (CB101). 3. Verify that the External Bypass input Circuit Breaker(user supplied. Refer to warning 2) is closed. Place SW2 in the ON position. 4.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 3-27 2. Select "STOP MENU" from the Operations menu. 3. Press the "INVERTER STOP" key in the START/STOP menu on the LCD panel. The UPS will transfer the load to the static bypass line. 4. When the "LOCAL" is displayed on the LCD panel, the operation can be performed at the UPS front panel. When the "REMOTE is displayed on the LCD pane, the Inverter can be stopped by remote operation only.
2. Page Number: 3-28 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Confirm via the flow diagram on the LCD that the load is fed from the UPS’ static bypass line. 3. After confirming Step2, rotate cam switch from NORMAL (UPS) to BYPASS (maintenance bypass). 4. UPS can now be powered down per instructions on the LCD’s OP. MENU. 5. Transfer is now complete. Load is fed from external source (Utility or generator). B) Transfer of load from internal maintenance bypass to inverter 1.
MITSUBISHI ELECTRIC B) Page Number: 3-29 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Transfer of load from external maintenance bypass to inverter 1. On MBP, close SW1. If UPS has dual feeds, Verify/Close External AC Input Circuit Breaker (user supplied) for UPS and Battery Disconnect if applicable. 2. On UPS LCD, select “Operation Menu”. Select “Start Menu”. Start UPS and Inverter per instructions. 3. On UPS LCD, select “Operation Menu”. Select “Stop Menu”. 4.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 4-1 4.0 RESPONSE TO UPS FAILURE UPS FAULT Depress Silence Alarm Key on MAIN menu. Annunciator Silence Refer to the list of fault codes for the description of the error. Recording of Fault Take necessary action per the guidance on the display. Primary Action When faults occur continuously contact the Authorized Information to Service Center Mitsubishi Service Representative or call Mitsubishi at 1-800-887-7830.
Page Number: 5-1 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC 5.0 PARTS REPLACEMENT Contact Mitsubishi or its Authorized Service Center on all issues regarding the replacement of parts. A) Battery Battery lifetime may vary according to the frequency of use and the average ambient operating temperature. Battery end of life is defined as the state of charge resulting in an ampere-hour capacity less than, or equal to, 80% of nominal capacity.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 6-1 6.0 FAULT CODES This section covers the fault codes, their description and required action. At time of error : A) Verify and record the occurrence of the alarm. Note details of alarm message on the LCD display panel. Contact Mitsubishi Electric Power Products, Inc. at 1-800-887-7830. B) If a circuit breaker (MCCB) is in the trip state, depress the toggle to reset the breaker before closing it again.
6-2 Fault Code List Note 11.
6-3 Note 11.
6-4 Note 11.
2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Page Number: 6-5 (Note 1) Numbered guidance: 1: Contact Mitsubishi. 2: Verify battery is operating within recommended voltage and temperature ranges. 3: Verify input power source is properly connected. 4: Reduce load. 5: Verify bypass power source is within amplitude and frequency. 6: Close CB1. 7: Close CB2. 8: Close CB101. 9: Reduce load and restart. 10: Press the reset button.
MITSUBISHI ELECTRIC 2033A SERIES UPS OWNERS / TECHNICAL MANUAL Page Number: 6-6 (Note 7) For other than sealed-type battery. (Note 8) Place UPS Emergency Bypass switch in the BYPASS position. Contact Mitsubishi. (Note 9) If the specified time passes, will transfer to the bypass power supply. (Note 10) Shows only when corresponding option settings are made.
MITSUBISHI ELECTRIC Page Number: 7-1 2033A SERIES UPS OWNERS / TECHNICAL MANUAL 7.0 WARRANTY & OUT OF WARRANTY SERVICE The Mitsubishi Electric UPS Division Service Department has many Authorized Service Centers place strategically throughout the US, Canada and Latin America. For both in warranty and out of warranty service, please contact Mitsubishi Electric Power Products, Inc. at (847) 478-2100.
NOTE: PLEASE READ THE TERMS OF THIS LIMITED WARRANTY CAREFULLY PRIOR TO INSTALLATION AND START-UP OF YOUR NEW MITSUBISHI UNINTERRUPTIBLE POWER SUPPLY SYSTEM. FAILURE TO FOLLOW THESE PROCEDURES MAY VOID YOUR LIMITED WARRANTY! MITSUBISHI ELECTRIC POWER PRODUCTS, INC. UNINTERRUPTIBLE POWER SUPPLY SYSTEM (2033A/2033C/2033D/9700/9800A SERIES) LIMITED WARRANTY POLICY AND PROCEDURES 1. LIMITED WARRANTY: MITSUBISHI ELECTRIC POWER PRODUCTS, INC.
C. ADDITIONAL LIMITATIONS (1) Parts used for replacements are warranted for the longer of 90 days or the remainder of the original Warranty Period. All defective Product parts shall be the property of MEPPI upon replacement. MEPPI reserves the right to make any or all changes to the Products that it may deem necessary without prior notice to customer. Replacement parts may be new or reconditioned or refurbished.
Page Number: 7-2 2033A SERIES UPS OWNERS / TECHNICAL MANUAL MITSUBISHI ELECTRIC Mitsubishi Electric Power Products, Inc. UNINTERRUPTIBLE POWER SUPPLIES 500 Corporate Woods Parkway, Vernon Hills, IL 60061 Phone: (847) 478-2100, Fax: (847) 478-2290 UPS Warranty Registration __ Register UPS for Warranty __ Address Change To validate the Warranty on your UPS this form must be filled out completely by Customer and returned.