Installation Instructions The following section contains installation and wiring instructions for the MarineSync RUM Transponder in an outdoor enclosure (pedestal). If technical assistance is required at any point during the installation, contact information can be found on the first page of this manual. MarineSync Corporation is not responsible for damage to the transponder or pedestal caused by incorrect wiring.
FCC This equipment has been tested and found to comply with the limits for a class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
RUM Transponder Assembly //Data2/MarineSync-Sales Marketing/Approved Technical Docs/RUM 4
Mounting the Transponder It is recommended the transponder be mounted near the sub-meter and/or power supply. The transponder should not be positioned in a manner that makes it difficult to gain access. The transponder is equipped with an internal antenna. To maximize performance, the transponder should be mounted as high as possible. Mount the transponder in a vertical orientation where possible. If installing within a weather-resistant enclosure or pedestal, the transponder may be mounted horizontally.
Mounting the Power Supply It is recommended the DC power supply be installed in an accessible location within the pedestal. Only use MarineSync supplied AC/DC power supply. The power supply must be directly wired to an unmetered, uninterrupted power source 100-240VAC. In some applications, the pedestals lighting circuit may provide an adequate connection point. Ensure the power supply is not installed between a photocell or switch. Power Supple Dimensions & Mounting Power Supply: EP2000.
Preparing the Transponder Remove the RUM splash cover using a #1 Phillips Screw Driver. Use caution not to lose the stainless hardware. To remove the terminal connector from the transponder, firmly pull the desired connector away from the transponder. As required, use 16-22AWG tinned copper wire for field wiring; strip field wiring to .20 to .24 inches. Wiring the Transponder Only use MarineSync supplied AC/DC power supply. Locate the “Monitoring” connector on the RUM transponder.
Remote Utility Monitoring - Connecting a Digital kWh Meter Preparing the Transponder Remove the RUM splash cover using a #1 Phillips Screw Driver. Use caution not to lose stainless hardware. To remove the terminal connector from the transponder, firmly pull the desired connector away from the transponder. If required, use 16-22AWG tinned copper wire for field wiring; strip field wiring to .20 to .24 inches. Wiring the Transponder The RUM transponder accepts up to four (4) meter outputs.
When connecting more than one meter to the RUM Transponder, use terminal #8, #10 and #11. If the utility meter provides more than one output resolutions (10, 100, 1000), determine the appropriate resolution for your application (fig 2) and connect to the RUM meter input. If you need assistance selecting a resolution, contact MarineSync.
Remote Utility Monitoring – Ground Fault Monitoring Preparing the Transponder Remove the RUM splash cover using a #1 Phillips Screw Driver. Use caution not to lose stainless hardware. Remove terminal connector from the transponder by firmly pulling the desired connector away from the transponder. Use 16-22AWG tinned copper wire for most field wiring applications, strip field wiring to .20 to .24 inches.
Reconnect conductors to the buss bar and secure. Connect the brown/blue leads from the Current Transformer to the RUM Transponder – Terminal 13 & 14. This connection is not polarity specific. Ground Fault CT Connecting Ground Fault Indicator Light (LED) – Optional Only use MarineSync supplied LED Indicator Light. Panel mount the LED in a visible location on the exterior of the pedestal.
Remote Utility Monitoring – Remote Load Disconnect (Relay) Wiring the Transponder Remove the RUM splash cover using a #1 Phillips Screw Driver. Use caution not to lose stainless screws. Wiring terminals (3) are removable by firmly pulling the connector away from the transponder. Use 16-22AWG tinned copper wire for most field wiring applications, strip field wiring to .20 to .24 inches. Use a 2.