ME-RC Standard Remote Control Owner’s Manual (Revision 2.
Disclaimer of Liability Since the use of this manual and the conditions or methods of installation, operation, use and maintenance of the ME-RC are beyond the control of Magnum Energy, Inc., the company does not assume responsibility and expressly disclaims liability for loss, damage or expense, whether direct, indirect, consequential or incidental, arising out of or in anyway connected with such installation, operation, use, or maintenance.
Important Product Safety Instructions This manual contains safety instructions that must be followed during the installation and operation of this product. Read all instructions and safety information contained in this manual before installing or using this product. Safety Symbols To reduce the risk of electrical shock, fire, or other safety hazard, the following safety symbols have been placed throughout this manual to indicate dangerous and important safety instructions.
Table of Contents 1.0 Introduction................................................................1 2.0 Installation .................................................................2 2.1 2.1.1 2.1.2 2.1.3 2.2 2.2.1 2.3 2.4 2.4.1 2.5 3.0 Pre-Installation ..................................................................... 2 Installation Guidelines ........................................................... 2 Unpacking and Inspection ......................................................
Table of Contents (Cont.) 7.0 Using a ME-AGS-N Module .........................................55 7.1 7.2 7.2.1 7.2.1.1 7.2.1.2 7.3 7.3.1 7.3.2 7.4 7.5 7.6 7.7 7.7.1 7.7.2 7.7.3 7.7.4 7.8 7.8.1 7.8.2 7.8.3 7.8.4 8.0 8.1 8.1.1 8.1.2 8.2 8.3 8.4 8.4.1 8.5 9.0 9.1 ME-AGS-N Setup ................................................................. 55 AGS Functional Tests ........................................................... 59 Remote to Generator Communication Test ..............................
List of Figures Figure 1-1, Front Panel Features .......................................................... 1 Figure 2-1, Remote Cable ................................................................... 3 Figure 2-2, Remote Control Connections ............................................... 3 Figure Figure Figure Figure Figure Figure Figure 2-3, 2-4, 2-5, 2-6, 3-1, 3-2, 3-3, ME-RC Remote Dimensions ................................................. 4 Flush Mounting the ME-RC ...............................
List of Figures (Cont.) Figure 5-13, Full Charge Mode........................................................... 41 Figure 5-14, Load Support AAC Mode ................................................. 41 Figure 5-15, Load Support VDC Mode ................................................. 42 Figure Figure Figure Figure Figure Figure Figure 5-16, 5-17, 5-18, 5-19, 5-20, 5-21, 5-22, Silent Mode .................................................................. 42 AC Backfeed Fault............................
1.0 Information 1.0 Introduction The ME-RC remote control allows you to monitor and customize the operating parameters for your Magnum inverter/charger. This remote can be used on all Magnum inverter/charger models so there is no cross-platform confusion. The ME-RC50 comes standard with a 50-foot, 4-conductor (twisted-pair) telephone cable and includes nonvolatile memory (preserves adjustable settings, even if power to the remote or inverter is removed).
2.0 Installation 2.0 Installation Review this section and the Important Product Safety Instructions on page ii before proceeding with the installation of your remote. WARNING: Installations should be performed by qualified personnel, such as a licensed or certified electrician. The installer determines which safety codes apply and ensures all applicable installation requirements are followed. Applicable installation codes vary depending on the specific location and application.
2.0 Installation 2.2 Connecting the Remote Cable The ME-RC comes with a remote cable to enable communication between the inverter and the remote. The remote cable is a 50-foot, 4-conductor, round twisted-pair, telephony standard with 6P4C (6-position/4-conductor) connectors on each end. When the 6P4C connectors are held side by side with both of the connector tabs facing the same way, the color of the conductors in each connector is the opposite from top to bottom (see Figure 2-1).
2.0 Installation 2.3 ME-RC Remote Dimensions Use the information below (Figures 2-3 and 2-4) in preparation for mounting the ME-RC remote. Directions for mounting follow in Section 2.4. ~1 ⅝" (4.1 cm) ~1" (2.5 cm) 5 ¼” (13.3 cm) 3 ¼” (8.3 cm) 3 ⅞" (9.8 cm) 2 ¾" (7.0 cm) .9" (2.3 cm) 1 ⅛" (2.9 cm) 1 ½" 5 ⅞" (14.9 cm) (3.8 cm) Figure 2-3, ME-RC Remote Dimensions 2.4 Mounting the ME-RC Remote The ME-RC can be flush mounted through an opening in the wall.
2.0 Installation 2.4.1 Flush Mount Installation Procedure To flush mount, the wall opening must have at least a 2” (5 cm) depth to allow room for the remote and the cable. 1. Cut an opening in the wall (Figure 2-4). Ensure there are no openings around the display and enough material for the screws to secure the unit. 2. Drill four pilot holes for the #8 x 3/4 screws that will attach the remote to the wall (refer to Figure 2-3 for remote hole locations and dimensions). 3.
2.0 Installation 2.5 Power-up Self Test Info: All power to operate the remote control is provided by the inverter/charger through the remote cable. When the ME-RC is first connected to an inverter, a power-up self test is initialized. The LCD automatically displays the following screens (Figure 2-5): PWR FAULT No LEDs light CHG INV PWR lights green FAULT lights red CHG lights green INV lights green MAGNUM ENERGY Self Test PWR FAULT CHG INV (C)2003-2013 Connecting to..
3.0 Setup 3.0 Setup When the remote is connected to a Magnum inverter/charger, the settings in the remote control determine the inverter/charger’s operating parameters. The default settings in the remote control are adequate for most installations (see Table 3-5); however, you have the option to change some of the operating parameters. This section shows you how to navigate the remote and gives you an understanding of the function of each adjustable setting. 3.
3.0 Setup 1. Press the SETUP menu button. Inverting 01 Search Watts Bottom line shows a menu heading. 2. Turn the SELECT knob to the desired menu item. Inverting 04 Battery Type When the bottom line shows the desired menu heading: 3. Press the SELECT knob. Bottom line shows current setting.* Inverting BatType=Flooded *[If this setting is correct, rotate the SELECT knob to continue to the next menu item.] 4. Press the SELECT knob to change the desired setting.
3.0 Setup 3.2 Remote Feature to Inverter Compatibility The ME-RC has many settings and is designed to work with the standard features in your Magnum inverter—and/or other Magnum devices (i.e., MEAGS-N or ME-BMK). The ME-RC communicates with your inverter to allow the set up and enabling of these standard features.
3.0 Setup Table 3-1, ME-RC Compatibility Matrix (cont.) Button FEATURES/SETTINGS Menu Heading AGS (Cont.) 08 AGS TECH Menu Item METER 02 BM: SOC Default Setting Gen Run: Read only display ≥Level 1 Read Only AGS VDC: Read only display ≥Level 1 Read Only Temp: Read only display ≥Level 1 Read Only AGS Rev: Read only display ≥Level 1 Read Only =RV, Other ≥Level 1 RV DC: ##.
3.0 Setup Table 3-1, ME-RC Compatibility Matrix (cont.) Button FEATURES/SETTINGS Main Menu Menu Heading/Item 01 Search Watts Search= 02 Low Batt CutOut LBCO= 03 Absorb Time Absorb Hrs= 04 Battery Type Model/ Level Required Default Setting OFF, 5-50W ≥Level 1 5W 9.0-12.2 VDC* ≥Level 1 10.0 VDC 0.0-25.5 Hrs ≥Level 4 [4] 1.5 Hrs Gel, Flooded, AGM1, AGM2 ≥Level 1 Flooded Selections/ Adjustments Range Absorb= (12.0-16.0V)* BatType= Custom [2] Float= (12.0-16.0V)* 14.
3.0 Setup Table 3-1, ME-RC Compatibility Matrix (cont.) Button FEATURES/SETTINGS Main Menu Menu Heading/Item TECH (Cont.) 03 InvModel Model: 04 Load Defaults Defaults in x.
3.0 Setup Bottom line shows current saved setting. SHORE Press If a different setting is required: Status... Shore Max=**A If this setting is correct, press another menu button to access another menu item. Status... Shore Max = 5A Status... Max = 30A ... Shore Rotate to desired selection: Status... Shore Max = 40A Press to save Status... Max = 60A ...
3.0 Setup MM, MM-AE and MMS Series (and any export version of these models): These models do not monitor current on the input, therefore cannot benefit from the Shore Max setting or feature. On these models, the Shore Max setting may be displayed and allow selection/adjustment, but will not do anything to reduce the battery charger current. 3.3.
3.0 Setup from the inverter to run an AC load—either using the batteries in Inverter mode, or from the AC input source in Standby mode. The reading is negative (–) to indicate power is being returned to the inverter through the AC output terminals—possible in an AC coupled installation. (MS-PAE, MS-PE and MSH Series models only) Input Amp: Displays the total AC amps being used by the inverter for charging and for powering any connected load at the output of the inverter.
3.0 Setup SETUP Rotate to Press Status... 01 Search Watts Status... Search = OFF Press to select Status... Search = 5W Rotate to desired selection: Status... Search = 10W ... Press to save Status... Search = 50W Figure 3-6, SETUP: 01 Search Watts Selections Info: When the Search Watts feature is active, “Searching” appears on the top line of the LCD display and the green INV LED will slowly flash.
3.0 Setup SETUP Rotate to Press Status... 02 LowBattCutOut Status... LBCO = 9.0VDC Press to select Status... LBCO = 9.1VDC ... Rotate to desired selection: Status... LBCO = 10.0VDC Press to save Status... = 12.2VDC ... LBCO Figure 3-7, SETUP: 02 LowBattCutOut Selections (12v) Where do I set the LBCO setting? If you want to cycle the batteries slightly—but don’t want to discharge them more than 20%*—then the LBCO setting should be set from 11.5-12.2 VDC (12-volt models), 23.0-24.
3.0 Setup SETUP Rotate to Press Status... 03 Absorb Time Status... Absorb Hrs=0.0 Press to select Status... Absorb Hrs=0.1 ... Rotate to desired selection: Status... Absorb Hrs=1.5 ... Press to save Status... Absorb Hrs=25.5 Figure 3-8, SETUP: 03 Absorb Time Selections Where do I set the Absorb Time setting? Select the setting based on the 20-hour amp-hour (AH) capacity of your battery bank.
3.
3.0 Setup Info: The voltage settings in Table 3-4 are based on the Battery Temperature Sensor (BTS) at a temperature of 77° F (25° C), or the BTS not connected. If the BTS is connected, the actual charge voltage will increase if the temperature around the BTS is below 77° F (25° C), and decrease if higher than 77° F (25° C). This ensures the batteries receive the correct charge voltage regardless of temperature.
3.0 Setup • SETUP: 05 Charge Rate – Sets the maximum charge rate allowed to charge the batteries during Bulk, Absorption, Float, and Equalize charging. The Max Charge = 0% setting helps minimize charging while continuing to allow pass-thru power. The rest of the selections are provided to limit the charge rate to the battery bank, which helps prevent battery overheating caused by charging at too high a charge rate.
3.0 Setup • SETUP: 06 VAC Dropout – Used to select the minimum AC voltage that must be present on the input before the inverter/charger switches from Inverter to Standby mode. This setting also determines the minimum AC voltage threshold where the charger disengages and the inverter (when turned on) will provide AC power from the batteries. This protects AC loads from utility outages.
3.0 Setup • SETUP: 07 Power Save – This setting allows you to turn off the Power Save feature, or to select a time (from 1 minute to 60 minutes) that determines how often the display goes into Power Save mode. Default setting: PwrSave = 15min Range: OFF, 1-60 Minutes SETUP Rotate to Press Status... 07 Power Save Status... PwrSave = OFF Press to select Rotate to desired selection: Status... = 15min Status... PwrSave = 1min … PwrSave Press to save Status...
3.0 Setup • SETUP: 09 Final Charge – The Final Charge stage setting is the stage to which the charger will transition after the absorption stage has finished—as set in the 03 Absorb Time menu. Default setting: Final = Multi Range: Multi, Float, Silent (Rebulk) Set Final Charge = Multi – The Multi setting (which is short for “MultiStage”), transitions from the Absorption stage to Float. Once in the Float stage for four hours with no DC load on the batteries, the charger will enter the Full Charge stage (i.
3.0 Setup ReBulk – When Silent mode is selected, you must also set the DC voltage set-point where the charger restarts the Bulk Charge mode. This setting should be at the lowest DC volts you want the batteries to fall before starting a new bulk charge. Typically, the lowest DC volts the batteries are allowed to fall is 12.0 to 12.2 VDC (12-volt systems), 24.0 to 24.4 VDC (24-volt systems), and 48.0 to 48.8 VDC (48-volt systems) respectively. Default setting: Rebulk = 12.0V (for 12v inverter) Ranges: 12.
3.0 Setup TECH Rotate to Status... 01 Temperatures Press Status... BTS: ##C/ ##F Status... Tfmer: ##C/##F Rotate to desired display: Press to select Status... FETs: ##C/ ##F Status... AGS: ##C/ ##F Figure 3-14, TECH: 01 Temperatures Display • TECH: 02 Revisions – Displays the revisions of the devices that are connected to the Magnum network. Rotate the SELECT knob to scroll through the revisions.
3.0 Setup TECH: 04 Load Defaults – This menu restores all settings on the inverter/charger, and any settings on accessories that are networked and controlled by the inverter (i.e., ME-AGS-N) to the factory default settings. To restore, press and hold the rotary SELECT knob for 5 seconds. Once restored, the display will show DEFAULTS LOADED. The inverter/charger’s factory defaults are listed in Table 3-5. Note: If a password (PIN) has been previously set, this menu will be unavailable (i.e., locked).
3.0 Setup • TECH: 05 Ext Control – Magnum has an open protocol policy that allows certain functions (VAC Dropout, Charge Rate, or Shore Max settings) of the inverter/charger to be controlled externally—such as with a third party communications device. INT: the setting has not changed, even if an external device is in control. EXT: an external device is controlling the setting—and, the external device has changed the setting. TECH Rotate to Press Status... 05 Ext Control Status...
3.0 Setup Unlock Setup – Press SELECT to allow all users to access the SETUP button menus. Lock Setup – Press SELECT to restrict access to the SETUP button menus to only those users with the valid PIN. Change PIN – Press SELECT to change the existing PIN. Entering an Existing PIN When entering a menu (or pressing the SETUP button) the “PIN = 0***” menu displays. The correct PIN must now be entered in order to access the menu. If the incorrect PIN number is entered, “Invalid PIN” displays.
4.0 Menu Map 4.0 Menu Map: ME-RC Remote Control Figures 4-1 thru 4-4 are a complete overview of the inverter/charger settings and information displays available in the ME-RC. SHORE 5A Status... R Shore Max = 10A Status... Shore Max = 60A R Status... Shore Max = 50A Status... Shore Max = Status... Max = 30A ... Shore R R Status... Shore Max = 40A AGS Refer to Section 7.0 in this manual and to the ME-AGS-N Owner’s Manual (PN: 64-0039) for detailed information on this menu.
4.0 Menu Map SETUP continued…. * LBCO settings are dependent on inverter model (values for a 12-volt model shown) Status... 02 LowBattCutOut P Status... LBCO = 9.0VDC* R R Status... LBCO = 9.1VDC Status... LBCO = 12.2VDC ... ... Status... LBCO = 10.0VDC R Status... LBCO = 10.1VDC Status... 03 Absorb Time P Status... Absorb Hrs= 0.0 R Status... Absorb Hrs= 0.1 R Status... Absorb Hrs= 0.2 R R Status... Absorb Hrs=25.5 ... Status... Absorb Hrs= 1.5 ... Status... 04 Battery Type P Status...
4.0 Menu Map SETUP continued…. Status... 08 Screen Setup P Status... Contrast = 0% R Status... Contrast = 10% R Status... Contrast = 20% Status... Contrast =100% Status... Contrast = 30% R P Status... Brightness= R 0% ... R Status... Brightness= 10% Status... Brightness=100% ... R Status... Brightness= 20% Status... Brightness= 50% R ... Status... 09 Final Charge P R Status... Final = Multi R Status... Final = Silent R Status...
4.0 Menu Map TECH continued Status... 03 Inv Model P R Read Only display Status... Model:######## Press and hold SELECT button for 5 seconds. Seconds will count down. Status... 04 Load Defaults P R Status... Defaults in 4.9 Read Only displays . INT= internal control , EXT= external control Status... 05 Ext Control P R Displays after 5 second countdown. Status... P DEFAULTS LOADED Status... VAC Dropout: ### R Status... Charge Rate: ### R Status... Shore Max : ### Status... 06 Set PIN P Status.
5.0 Operation 5.0 Operation This section explains how to operate the inverter/charger using the MERC remote. It also provides information on the LED indicators and the LCD display that are used to show the operational status of the inverter/charger. 5.1 Front Panel The ME-RC’s front panel contains LED indicators and a LCD display for viewing system status, buttons to control system operation, and a rotary knob that enables you to locate and select system information and settings.
5.0 Operation 5.1.3 • • ON/OFF Pushbuttons ON/OFF INVERTER – This button toggles the inverter function on and off. The green INV LED turns on and off with the button. ON/OFF CHARGER – This button toggles the charger function on and off whenever the charger is actively charging. The green CHG LED turns on and off with the button. This button is also used to initiate an Equalize charge. For more information on using the Equalize charge feature, see Section 5.2.
5.0 Operation 5.2 Operating the Inverter/Charger 5.2.1 Inverter Mode Turning the inverter on: Press the ON/OFF INVERTER button to activate the inverter function. The inverter will either be actively “inverting” by using power from the batteries to power the AC loads; or, the inverter will be “searching” for a load by using very little power from the batteries, if in Search mode. The green INV LED is on when the inverter is actively inverting, and flashes while searching.
5.0 Operation 5.3 System Status Messages A status message may be an operational or fault message indicating the inverter/charger’s current operating status. This section will cover the inverter/charger’s operating and fault modes, and the available status messages under each mode. Use the displayed status message and the status LEDs on your ME-RC remote (Figure 5-2) to determine the inverter/charger’s current operating status, and to help troubleshoot the system if a fault occurs.
5.0 Operation PWR FAULT CHG INV Off Settings/Info.. Off appears on the LCD. All LEDs are off. Figure 5-5, Off Mode • Off – No AC available on the inverter’s AC output. The inverter function is off, and there is no utility/shore or generator AC power sensed on its input. PWR FAULT CHG INV Searching Settings/Info.. Searching appears on the LCD. The PWR (green) LED is on solid, and the INV (green) LED slowly flashes. The FAULT (red) and CHG (green) LEDs are off.
5.0 Operation PWR FAULT CHG INV Bulk Charging Settings/Info.. Bulk Charging appears on LCD. PWR (green) is on solid, and CHG (green) LED is typically on solid, but may blink slowly. FAULT (red) LED is off. INV (green) LED could be on or off. Figure 5-8, Bulk Charging Mode • Bulk Charging – The battery charger is delivering maximum current (determined by the SETUP menu’s 05 Charge Rate setting) to the batteries.
5.0 Operation PWR FAULT CHG INV Equalizing Settings/Info.. Equalizing appears on LCD. PWR (green) and CHG (green) LEDs are on solid. FAULT (red) LED is off, and INV (green) LED could be on or off. Figure 5-11, Equalizing Mode • Equalizing – The battery charger is delivering the equalize voltage to the batteries; see Table 3-4 to determine the equalize voltage for your battery type. Equalize charging can be enabled by the ON/OFF CHARGER button—if the SETUP menu’s 04 Battery Type selection allows.
5.0 Operation PWR FAULT CHG INV Float Charging Settings/Info.. Float Charging appears on LCD. PWR (green) LED is on solid, and CHG (green) LED is on solid, but may blink slowly. FAULT (red) LED is off, and INV (green) LED could be on or off. Figure 5-12, Float Charging Mode • Float Charging – At the end of the Absorb Charging time, the charger reduces the charge voltage and tries to maintain the batteries at the Float Charge voltage setting.
5.0 Operation Info: When the inverter is in Inverter Standby mode (charging and pass-thru), the current is normally a positive value. However, in Load Support AAC mode, the inverter amps reading is a negative number to indicate how much current is being provided/removed from the inverter batteries. The inverter batteries will continue to provide current to assist the AC input current until the battery reaches 0.5 volts (12-volt systems), 1.0 volts (24-volt systems) , and 2.
5.0 Operation 5.3.3 Fault Mode Messages The FAULT LED comes on and a fault status is displayed when an abnormal condition is detected. View the LCD display and use the information in this section to determine and correct the issue. Info: Many of the faults will automatically restart when the fault is cleared. Some faults will require a manual restart (ON/OFF INVERTER button on remote is pressed and released). Finally, if the fault does not clear, an inverter reset (Section 6.2) may be required. 5.3.3.
5.0 Operation PWR FAULT CHG INV Breaker Tripped Settings/Info.. Breaker Tripped appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LEDs are off. Figure 5-19, Breaker Tripped Fault • Breaker Tripped – The AC input breaker on the inverter/charger has opened due to excess current flow through the inverter to the AC loads. Remedy: After reducing the AC loads, push in the inverter’s AC input circuit breaker to reset and resume operation.
5.0 Operation PWR FAULT CHG INV High Battery Settings/Info.. High Battery appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LEDs are off. Figure 5-22, High Battery Fault • High Battery – The inverter has turned off because the battery voltage is at a very high level. The fault occurs when the battery voltage is above the High Battery Cut-Out (HBCO) value. The inverter will automatically restart and resume operation when the battery voltage drops 0.
5.0 Operation PWR FAULT CHG INV High Volts AC Settings/Info.. High Volts AC appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LEDs are off. Figure 5-24, High Volts AC Fault • High Volts AC – This fault causes the charger to be disabled because a very high AC voltage (>150 VAC) has been detected on the AC input. Remedy: Remove all AC power from the inverter’s AC input for at least 15 minutes to automatically restart this fault.
5.0 Operation PWR FAULT CHG INV Overcurrent Settings/Info.. Overcurrent appears on the LCD and the FAULT (red) LED is on. The PWR (green), CHG (green) and INV (green) LEDs are off. Figure 5-27, Overcurrent Fault • Overcurrent – This fault shuts down the inverter to protect internal power components. It may be caused by an excessive AC load. If the overload condition lasts for less than 10 seconds, the unit will automatically restart and resume operation.
5.0 Operation Remedy: The AC pass-thru relay is most likely stuck. A relay usually sticks because of damage to the contacts from trying to handle currents greater than they are rated. This is usually caused by not protecting the relay from handling high continuous currents, or by switching high current inductive loads. The internal relay contacts are rated to handle 30 amps AC continuously and should be protected with a breaker sized no larger than 30 amps.
5.0 Operation 5.3.3.2 Stacking Fault Messages A fault condition may occur when two inverters are stacked in series—using the stacking interface—that is not possible on a single inverter installation. Refer to the following fault messages to help troubleshoot the inverters. PWR FAULT CHG INV StackClock Fault Settings/Info.. StackClock Fault appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LEDs are off.
5.0 Operation 5.3.3.3 Internal Fault Messages The inverter continually monitors several internal components and will shut down to help protect itself if one of the following “internal” faults occurs. Remedy: If an “internal” fault occurs, perform an inverter or power reset to clear it (see Sections 6.2 & 6.3). After the reset, turn the inverter on. If the internal fault remains or returns, the inverter will require repair at an authorized service facility. PWR FAULT CHG INV Internal Bridge Settings/Info..
5.0 Operation 5.3.4 LED Indicator Guide Use the LEDs along with the LCD display to determine the operating status. Table 5-1, LED Indicator Guide LED PWR (green) FAULT (red) CHG (green) Status Meaning OFF 1. Inverter is disabled; 2. Remote is in Power Saver mode – press any button to activate LEDs; 3. No power to remote (check remote cable or power to inverter); or, 4. No AC power at the inverter’s AC output terminals.
6.0 Troubleshooting 6.0 ME-RC Remote Troubleshooting The remote may not be functioning correctly, use the following table to help find a solution. Table 6-1, Remote Control Troubleshooting Guide Symptom Possible Cause Solution Display shows unrecognizable letters or symbols Static electricity may have been discharged into the LCD display. Refresh display: Press and hold the SELECT button for 10 seconds.
6.0 Troubleshooting 6.1 Inverter/Charger Troubleshooting Tips 6.1.1 Inverter Problems • Inverter turned on, green INV LED on inverter blinking, no output: Inverter is in Search mode. Either turn off Search mode—if not needed—or turn on loads greater than the Search Watts setting. 6.1.2 Charger Problems • Unit won’t transfer to Charge mode with AC applied: Is charge (CHG) LED on remote blinking? If not, then the charger does not recognize the incoming AC being within acceptable limits.
6.0 Troubleshooting 6.2 Performing an Inverter Reset To perform an inverter reset (i.e., “soft reset”): 1. Remove all AC power (utility or generator power) to the inverter. 2. Press and hold the inverter’s Power ON/OFF pushbutton (see Figure 6-1) for approximately fifteen (15) seconds—until the inverter’s Charging/ Inverting Status LED comes on and flashes rapidly. 3. Once the rapid flashing has begun, release the Power ON/OFF pushbutton. The Status LED will go off after the button is released. 4.
7.0 Using an AGS Module 7.0 Using a ME-AGS-N Module The ME-RC remote’s AGS menus under the AGS and TECH buttons allow you to customize and monitor the operating parameters for your autostart/ autostop generator system. To help configure and operate the AGS with your ME-RC, refer to the mini index below to direct you to the appropriate section. 7.1 ME-AGS-N Setup page 55 7.2 ME-AGS-N Functional Tests page 59 7.3 ME-AGS-N Operation/Monitoring page 59 7.4 Enabling the ME-AGS-N page 62 7.
7.0 Using an AGS Module AGS: 03 Run Time Hour Menu This menu provides the settings that determine the length of time the generator will run once it has been autostarted by the AGS. Default setting: Run Time = 2.0 Hrs Range: 0.5 - 25.5 Hrs (0.5 hr increments) How long should I set the generator run time? This depends on whether you are using the high temperature or low battery voltage autostart feature.
7.0 Using an AGS Module sensor (or thermostat control) reading is above the AGS: 04 Start Temp F setting, the generator will continue to run for a second run time period. At the end of this second run time period, the temperature sensor reading (or thermostat control) is checked again. This cycle continues as long as the AGS: 01 AGS Control menu is set to Enable (or Enable w/QT). If the temperature autostart feature is not needed, set to the OFF position.
7.0 Using an AGS Module Info: The default settings and range are automatically determined based on the connected inverter and the measured VDC. Where should I set Start Volts? When setting the VDC start voltage, it must be high enough to not over-discharge the battery, but also low enough to keep from nuisance starting the generator. Typically, start volts is set based on what is determined to be approximately 50% of the battery capacity.
7.0 Using an AGS Module 7.2 AGS Functional Tests Once you establish all the autostart/autostop settings you need, perform the following tests to verify that the AGS system is functioning correctly and the communication from the remote/inverter to the ME-AGS-N is correct. 7.2.1 Remote to Generator Communication Test This section describes how to determine the current AGS status and how to use the ME-RC remote to start the generator. 7.2.1.
7.0 Using an AGS Module AGS: 01 AGS Control Menu This menu is used to enable the AGS (selecting Enable or Enable w/QT). A “Test” setting is also available to ensure the start/stop wiring from the generator to the ME-AGS-N is correct. The available settings are: • OFF – This option disables the AGS’s generator start/stop functions. It also turns the generator off if it is running from an autostart command. When OFF is selected, the generator will not start automatically. This is the default setting.
7.0 Using an AGS Module AGS: 08 AGS TECH Menu This menu displays meter data on the operating condition of the generator and AGS, and has an AGS mode setting. • Gen Run – Displays the number of hours the generator has been currently running from an autostart condition. This menu does not determine run time when the generator has been manually started. • AGS VDC – Displays the battery voltage currently connected to the AGS (on Terminals #3 and #4).
7.0 Using an AGS Module Press the ME-RC’s TECH button, and then rotate and press the SELECT knob to access the following menus: TECH: 01 Temperatures Menu (AGS) This read-only menu displays the ambient temperature reading of the AGS’s temperature sensor (if installed). Note: This AGS temperature meter displays the same info as the AGS: 08 AGS TECH menu’s Temp meter (see info for this meter on previous page).
7.0 Using an AGS Module 7.6 ME-AGS-N Menu Map using the ME-RC AGS Status... 01 AGS Control P Status... AGS= R OFF Status... AGS= Enable R Status... AGS= R Test R Status... AGS=Enable w/QT Status... 02 AGS Status P Read Only display Status... AGS: Status Available Statuses: AC In Manual Run No Comm Off Quiet Time Ready Start Temp R Status... 03 Run Time Hour P R Status... Run Time= 0.5Hr Start Test Start VDC Fault Gen Run Fault Temp Fault Test Fault VDC Lockout Status... Time= 2.
7.0 Using an AGS Module Cont. AGS Status... 08 AGS TECH P Read Only displays (except AGS Mode) Status... Gen Run: #.#Hr R Status... AGS VDC: #.# Status... Temp: ##C/##F Status... Status... AGS Mode:RV P R R AGS Rev: Status... AGS Mode=RV R #.# Status... R AGS Mode=Other TECH Status... 01 Temperatures P ... R Read Only displays Status... AGS: ##C/##F Status... 02 Revisions P … Read Only displays Status... AGS: #.# LEGEND Menu Button AGS Press button Status...
7.0 Using an AGS Module 7.7 ME-AGS-N Remote Status Messages A status message may be an operational or a fault message. Access the AGS status menu (AGS button’s 02 AGS Status menu) to view the AGS’s current operating status. This menu is important when determining if the AGS is working correctly, or for troubleshooting an AGS installation. 7.7.1 AGS Remote Operational Statuses Refer to Table 7-3 for a brief description of the possible AGS operational statuses that may display.
7.0 Using an AGS Module 7.7.2 AGS Remote Start Statuses The following “Start” statuses identify the condition that autostarted the generator. If you determine that the autostart condition occurred sooner than expected (or didn’t want this autostart condition), refer to the Setup section for that condition to change (or defeat) the autostart setting. Table 7-4, AGS Remote Start Statuses STATUS DESCRIPTION Start Temp The generator has started based on the AGS: 04 Start Temp F setting.
7.0 Using an AGS Module starts or until all its start attempts are reached, which causes the AGS to go into a fault condition (indicated by a blinking FAULT indication on the remote and a solid red STATUS indicator on the AGS Module). If using the temperature autostart feature in an RV coach, set the air conditioner thermostat slightly less than the setting (04 Start Temp F menu). If using two air conditioners, set the second air conditioner thermostat 2° to 5° higher than the first air conditioner.
7.0 Using an AGS Module 7.8.2 Resolving Operational Statuses The following operational statuses can display on your remote control, and some may indicate an abnormal condition. Use the info below to resolve. • No Comm – This is a normal status if there is no AGS installed. If an AGS is installed, use the information below to determine the remedy. Remedy: If an AGS is installed, then follow these steps: 1.
7.0 Using an AGS Module Fault Gen Run – The generator successfully started and ran for more than two minutes, but the generator unexpectedly stopped by itself before the active AGS autostop condition was finished. Info: The AGS module determines the generator is running by monitoring the gen run sense voltage/signal. When this gen run sense voltage/signal is no longer available, the AGS thinks the gen is off or has stopped. Info: Gen run fault detection is not active if the generator is manually started.
8.0 Using a BMK 8.0 Using a ME-BMK This section discusses how to set up and operate the BMK using the ME-RC50 remote. It also shows what BMK menu options are available using this remote. 8.1 Understanding Charge Efficiency The first section provides information about charge efficiency and how to manually access/adjust this setting. Normally, the ME-BMK battery monitor automatically calculates the battery’s efficiency.
8.0 Using a BMK 8.1.2 Adjusting the Charge Efficiency Setting The Charge Efficiency setting determines how the battery monitor calculates the battery’s charge efficiency. The charge efficiency can be calculated automatically using the Auto setting, or can be manually programmed by the user (see Figure 8-2). The battery monitor is shipped with the charge efficiency set to Auto.
8.0 Using a BMK 8.3 ME-RC50 Remote’s BMK METER Menu Maps The diagram below is a complete overview of the battery monitor settings and information displays available from the ME-RC50 remote’s METER menu. METER R METER Status... 02 BM: SOC P R Status... Batt SOC: ##% Status... 03 BM: Meters P Status... Status... DC Volts: #.## R DC Amps: + #.# Status... tAH Out: R Status... 04 BM: Status P #.#k Status... + R AH I/O: R Status... rAH Out: # R #.
8.0 Using a BMK 8.4 Operating the BMK using the ME-RC This section explains how the ME-BMK battery monitor works, and how to use the ME-RC50 remote control to obtain battery bank information. It also covers the various LCD displays that are related to the battery monitor and the status of the Sense Module’s LED indicator. 8.4.1 How the Battery Monitor (ME-BMK) Operates The ME-BMK battery monitor uses a precision resistor known as a shunt to measure current flow into and out of the battery.
8.0 Using a BMK point. While this reference point is being calculated, the display will show “Think’n”, to indicate that the SOC reference point is being calculated. After the batteries are fully charged, the display will change from Think’n to 100% and begin to provide accurate SOC percentage values. Info: Think’n can take up to several days depending on the charge source and its ability to completely recharge the batteries (e.g.
8.0 Using a BMK • tAH Out (Total AHrs Removed) – This meter displays the total AHrs removed from the battery since the Sense Module was first connected. This display can be used as a battery service life indicator. The value is displayed in 0.1k [or 100 AHrs (“k” equals 1000)] resolution up to a maximum of 6,553.5k AHrs (6,553,500 AHrs). The displayed number resets to 0.0k when the Sense Module is disconnected from power.
9.0 Service and Warranty Info 9.0 Service and Warranty Info Magnum Energy, Inc., (hereafter “Magnum”) warrants the ME-RC remote to be free from defects in material and workmanship that result in product failure during normal usage, according to the following terms and conditions: 1. The limited warranty for this product extends for a maximum of 12 months from the product’s original date of purchase. 2.
Magnum Energy, Inc. 2211 West Casino Rd Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390 Web: www.magnumenergy.