Installation Manual

Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
Main Repeater
Wall
#6 (M3) screw
recommended
(2 included)
Vertical
Ceiling
Horizontal
1.06
(26.9)
Level Surface
0.19
(4.8)
dia.
Use these instructions to install the model numbers listed above.
For system Setup Guide and tools visit: www.lutron.com/radiora2
Features
Supports system setup and ensures error-free communication between system components.
Add up to (4) Auxiliary Repeaters to extend range for larger system applications.
Test button: enters the system diagnostic mode.
Verify that the Repeaters in a system are communicating effectively.
Add button: enters the system address mode.
– Allows new devices to be easily added into a system.
RS485 port to connect to other Repeaters through a wired link (daisy-chain).
RS232 port for integration.
Ethernet port for integration and PC connectivity.
Important Notes
Environment
Ambient operating temperature: 32 °F to 104 °F (0 °C to 40 °C), 0% to 90% humidity,
non-condensing. Indoor use only.
Codes
Install in accordance with all local and national electrical codes.
Cleaning
To clean, wipe with a clean damp cloth. DO NOT use any chemical cleaning solutions.
DC Adapter Power
NOTICE: Using a DC adapter not rated at the proper specifications could damage the
Repeater and possibly overheat the DC adapter. Use only the DC adapter that meets the
specification listed above.
For California residents only
The batteries in these devices contain Perchlorate Material special handling may apply.
For more information visit www.dtsc.ca.gov/hazardouswaste/perchlorate
RF Device Placement
All dimmers, switches, keypads and shades / draperies must be located within 30 ft
(9 m) of a Repeater. All Repeaters must be within 60 ft (18 m) of another Repeater.
Programming
For programming instructions, see the system Setup Guide included with the Main
Repeater or visit the website listed above.
Installation
1. Find a suitable location for the Main Repeater. For more information regarding the proper
placement of a Main Repeater in a system see the system Setup Guide.
2. Mount vertically or horizontally, as shown in the Mounting Diagram, using two #6 (M3)
screws (included). When mounting, allow 7 in (177.8 mm) clearance for the antenna and
ensure convenient access to the power plug. In order to achieve proper RF performance,
do not mount unit in a metal enclosure.
3. Attach the DC adapter cord to the power jack on the Main Repeater and insert the DC
adapter plug into a receptacle.
Technical Assistance:
U.S.A. / Canada: 1.800.523.9466
Mexico: +1.888.235.2910
Brazil: +55 11 3257 6745
United Kingdom: +44.(0)20.7680.4481
India: +91.124.439.0130
United Arab Emirates: +971.4.299.1224
China: 10.800.120.1536
Singapore: 800.120.4491
Other Countries: +1.610.282.3800
Dimensions (front view)
Measurements are shown as: in (mm).
Installation Instructions Please Read Before Installing
Lutron Elec tron ics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299
English
Lutron, RadioRA and
are registered trademarks and RadioRA 2 is a trademark of Lutron Electronics Co., Inc.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.
© 2014 Lutron Electronics Co., Inc.
Warranty: For warranty information, please see the Warranty enclosed
with the product, or visit:
www.lutron.com/TechnicalDocumentLibrary/warranty.pdf or
www.lutron.com/TechnicalDocumentLibrary/Intl_Warranty.pdf
Connection
Mounting Diagram (side view)
Troubleshooting Guide*
Symptom Probable Cause and Action
Dimmers,
keypads,
and shades /
draperies do
not respond
to the Main
Repeater.
Power Not Present
Ensure that the power supply cord is plugged into a
wall outlet and the power jack on the Main Repeater.
Circuit Breaker is OFF or tripped. Reset or turn on
circuit breaker.
Devices not programmed as part of a system.
Program the Main Repeater and all other devices
according to the system Setup Guide.
System devices are not within specified RF range.
Ensure that dimmers, keypads and shades / draperies
are within 30 ft (9 m) of a Repeater.
Verify that all Repeaters are within 60 ft (18 m) of
another Repeater.
Power Jack (to DC adapter)
(IEC PELV/NECR Class 2)
RS232 Cable:
maximum 50 ft
(15 m)
CAT5 Cable:
maximum
328 ft (100 m)
2.72
(70)
5.25
(133.4)
Mounting
hole
detail
0.23
(5.8)
0.31
(7.9)
dia.
4.25
(108)
Mounting holes
3.75
(95.3)
0.63
(16)
RF range:
To repeater 60 ft (18 m)
To other devices 30 ft (9 m)
Front Buttons
Front Buttons
87654321
12345
6789
RS232 and Ethernet Pin Numbering
Ethernet Pin #
T+Ve 1
T-Ve 2
R+Ve 3
R-Ve 6
87654321
12345
6789
RS232 Pin #
TxD 2
RxD 3
GND 5
Operation*
Main or Auxiliary Repeater
RF Link
60 ft (18 m)
maximum
Wired Link 1000 ft
(305 m) maximum
30 ft (9 m)
maximum
30 ft (9 m)
maximum
30 ft (9 m)
maximum
Wired and RF Configuration
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Add
Test
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
Integrate
Program / Integrate
RS232
Ethernet
Add
Test
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Add
Test
Repeater Status LEDs
Displays the status of
the Repeaters in the
system.
Test and Add Buttons
Press and hold to enter
the system into Test
mode or Add mode.
Test and Add LEDs
Flashes green to
indicate that the
system is in Test mode
or Add mode.
RF and wired LEDs
Displays the Tx / Rx
activity on the RF and
wired links.
(Green=Tx; Orange=Rx)
RS485
RS232
Ethernet
9V
Antena
Main Repeater DC Adapter
RR-MAIN-REP-WH Included (T120-9DC-3-BL)
RRK-MAIN-REP-WH Not included (TE240-9DC-3-XX, TU240-9DC-3-XX)
RR-MAIN-REP-WHBA, RRM-MAIN-REP-WH,
RRN-MAIN-REP-WH, RRQ-MAIN-REP-WH
Not included (see LutronR P/N 369561)
* Note: Refer to the system Setup Guide for additional troubleshooting
suggestions and LED feedback.
See table below
Model Dimension
RR-MAIN-REP-WH,
RR-MAIN-REP-WHBA,
RRQ-MAIN-REP-WH
6.25 (158.8)
RRK-MAIN-REP-WH,
RRN-MAIN-REP-WH,
RRM-MAIN-REP-WH
3.13 (79.4)
P/N 044335 Rev. A
02/2014
CE Information
Lutron Electronics hereby declares that model RRK-MAIN-REP-WH is in
compliance with the essential requirements and other relevant provisions
of Directive 1999/5/EC. A copy of the DoC can be obtained by writing to:
Lutron Electronics Co., Inc.
7200 Suter Road, Coopersburg, PA 18036 U.S.A.
G
Main Repeater: 9 V- 300 mA
DC Adapter: Power Jack (to DC adapter) (IEC PELV / NECR Class 2)
T120-9DC-3-BL: Input: 120 V~ 60 Hz 6.5 W Output: 9 V- 300 mA
TE240-9DC-3-XX: Input: 100 – 240 V~ 50/60 Hz 0.3 A Output: 9 V- 300 mA
TU240-9DC-3-XX: Input: 100 – 240 V~ 50/60 Hz 0.3 A Output: 9 V- 300 mA
Typical power consumption:
3.1 W
Typical Power Consumption test conditions: one LED on, Ethernet cable plugged in,
Repeater powered by the 9 V - adapter (
T120-9DC-3-BL)
.
MUX
N/C
COM
MUX
Wired Link (Daisy-chain)
Maximum 1000 ft (305 m) IEC PELV/NECR Class 2
Two pair one pair 18 AWG (1.0 mm
2
), one pair 18 to 22 AWG
(1.0 to 0.5 mm
2
) twisted shielded.
Returning a Main Repeater to Factory Settings
Note: Returning a Main Repeater to factory settings will erase all
programming from it and all devices and will require the Main Repeater to
be reprogrammed into the system.
1. Triple tap and hold the Test button on a Main Repeater. DO NOT release
the button after the third tap.
2. Keep the Test button pressed on the third tap until all the LEDs start to
flash red slowly (approximately 3 seconds).
3. Release the Test button and immediately triple tap it again. All the LEDs
will flash red quickly. When the LEDs stop flashing, the Main Repeater
has been returned to factory settings

Summary of content (6 pages)