Planning The longer distance to disturbance, i.e. the longer straight duct before the UltraLink®, the higher the measurement accuracy will be. It is not recommended to mount the UltraLink® so that the first flow sensor (* in the table on the next page) is placed on an outer radius of a fitting. Never use an UltraLink® on the outlet side of a duct fan. Place it on the inlet side or in worst case use a flow conditioner if it must be placed on the outlet side.
Disturbance * Placement of first flow sensor Measurement uncertainty ± % or 1 l/s depending wich is the greatest a 2-4·Ød >4-5·Ød >5·Ød a Bend Ød Inner radius 5 5 5 Outer radius (Not recommended) 20 10 5 Side 10 5 5 Inner radius 10 5 5 Outer radius (Not recommended) 20 10 5 Side 10 5 5 Duct diameter decrease 5 5 5 Duct diameter increase 10 5 5 * * a Bend Ød * a Bend Ød a T-piece Ød * * a T-piece Ød * a T-piece Ød a Reducer Ød * a Reducer Ød * 3
lindab | we simplify construction Declaration of incorporation for partly completed machinery and FCC statement Ultrasonic device – FTCU Company: Lindab Ventilation AB Stålhögavägen 115 26982 Båstad Sweden Telephone +46 431 85000 www.lindab.com Hereby declares that the partly completed machinery of the type: FTCU FCC Caution: are in conformity with the following essential requirements in Annex 1 of the Machinery directive 2006/42/EC: 1.1.2, 1.1.3, 1.3.4.