http://www.lgservice.com INSTALLATION MANUAL FRANÇAIS LG Room Air Conditioner ENGLISH LG ESPAÑOL IMPORTANT • Please read this instruction manual completely before installing the product. • When the power cord is damaged, replacement should be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. • Please retain this installation manual for future reference after reading it thoroughly.
Room Air Conditioner Installation Manual TABLE OF CONTENTS Installation Requirements Required Parts Required Tools Safety Precautions .........................3 Introduction .....................................9 Symbols Ued in This Manual......9 Features .......................................9 Installation .....................................10 Installation Parts ........................10 Installation Tools ........................10 Installation Map..........................
Safety Precautions Safety Precautions ■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only. ■ The meanings of the symbols used in this manual are as shown below. Be sure not to do. Be sure to follow the instruction.
Safety Precautions Be cautious when unpacking and installing the product. For installation, always contact the dealer or an Authorized Service Center. Do not install the product on a defective installation stand. • Shape edges could cause injury. Be especially careful of the sharp edges. • There is risk of fire, electric shock, explosion, or injury. • It may cause injury, accident, or damage to the product. Be sure the installation area does not deteriorate with age.
Safety Precautions Do not place a heater or other appliances near the power cable. • Moisture may condense and wet or damage furnishings. Do not store of use flammable gas or combustibles near the air conditioner. • There is risk of fire or product failure. x Wa Thinner Do not use the product in a tightly closed space for a long time. When flammable gas leaks, turn off the gas and open a window for ventilation before turning the product on. Do not use the telephone or turn switches on or off.
Safety Precautions Ventilate the product from time to time when operating it together with a stove, etc. Unplug the appliance before performing cleaning or maintenance. When the product is not be used for a long time disconnect the power supply plug or turn off the breaker. • There is risk of fire or electrical shock. • There is risk of electric shock. • There is risk of product damage or failure, or unintended operation. Take care to ensure that nobody could step on or fall onto the outdoor unit.
Safety Precautions Use two or more people to lift and transport the air conditioner Do not install the product where it will be exposed to sea wind (salt spray) directly. • It may cause a problem for your neighbors. • Avoid personal injury. • It may cause corrosion in the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation. Do not direct airflow at room occupants.
Safety Precautions Always insert the filter securely. Clean the filter every two weeks or more often if necessary. Do not drink the water drained from the unit. • A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage. • It is not sanitary and could cause serious health issues. Use a firm stool or ladder when cleaning or maintaining the air conditioner. Replace all the batteries in the remote. • Be careful and avoid personal injury.
Introduction Introduction ENGLISH Symbols Used In This Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that may cause harm to the air conditioner. NOTICE This symbol indicates special notes.
Installation Installation Read carefully, and then follow step by step.
Installation Installation Map ENGLISH NOTICE Installation parts you should purchase. Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealer) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Air Discarge Vertical Air deflector Operation Indication Lamps/ Signal Receptor Forced Operation Button Saddle Vinyl tape (Wide) • Apply after carrying out a drainage test. • To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Installation Confirm The Refrigerant 1. Check the quality label on the indoor and outdoor unit. 2. Make certain that the refrigerant is R-410A. NOTICE THIS PRODUCT CONTAINS R-410A REFRIGERANT 1) Different compressor oil - R-410A(Polyol ester) / R-22(Mineral). - Do not mix the existing mineral oil. - Do not apply used pipe, tools and gauges covered with the existing mineral oil. 2) Absorption of moisture -Compressor’s oil has the high absorption rate of moisture.
Installation Select The Best Location 1. Do not have any heat or steam near the unit. 6. Use a stud finder to locate studs to prevent unnecessary damage to the wall. 2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conveniently routed away. More than 30cm(11.8in) More than 30cm(11.8in) 4. Do not install near a doorway. 5. Ensure that the space around the left and right of the unit is more than 30cm(11.8in).
Installation Piping Length And Elevation Capacity (Btu/h) 12k Pipe Size Suction Evap Standard Length m(ft) Max. Elevation m(ft) Max. length m(ft) Additional Refrigerant g/m(oz/ft) 7.5(25) 7.5(25) 15(49) 20(0.22) Ø12.7mm(1/2") Ø6.35mm(1/4") Outdoor unit Indoor unit B Oil trap A A Outdoor unit Indoor unit Outdoor unit B A Indoor unit B In case more than 5m(16.4ft) • Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Installation How To Mount Installation Plate 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level. ENGLISH The wall you select should be strong and solid enough to prevent vibration Installation Plate Chassis Hook Type “A” 2. Measure the wall and mark the centerline.
Installation Flaring Work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally. 2. Measure the distance between the indoor and the outdoor unit. 3. Cut the pipes a little longer than measured distance. 4. Cut the cable 1.5m(59.1in) longer than the pipe length. Copper pipe Slanted Uneven Rough 90¡ Burrs removal Pipe 1.
Installation Connecting The the Piping Piping ENGLISH Indoor 1. Prepare the indoor unit's piping and drain hose for installation through the wall. 2. Remove the plastic tubing retainer(see the illustration by) and pull the tubing and drain hose away from chassis. 3. Replace only the plastic tubing holder 1, not the holder 2 in the original position. For left rear piping Route the indoor tubing and the drain hose in the direction of rear left.
Installation Connecting the pipings to the indoor unit and drain hose to drain pipe. Wrap the insulation material around the connecting portion. • Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants. • Align the center of the pipings and sufficiently tighten the flare nut by hand. • Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Installation Insert the connecting cable into the indoor unit. • Don't connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later. Flare nut Connection pipe Torque wrench Indoor unit tubing • Connecting cable Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4 Tape Connecting pipe Drain hose Connecting cable A mm 1.1~1.3 1.5~1.7 1.6~1.8 1.6~1.8 1.9~2.1 inch 0.043~0.051 0.059~0.066 0.063~0.070 0.063~0.070 0.074~0.
Installation • Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit piping Connection pipe Vinyl tape (wide) Reroute the pipings and the drain hose across the back of the chassis. Wrap with vinyl tape Pipe Vinyl tape(narrow) Connecting cable Piping for passage through piping hole Reroute the pipings and the drain hose across the back of the chassis.
Installation Installation Information. For left piping. Follow the instruction below. • Press on the upper side of clamp and unfold the tubing to downward slowly. Incorrect case • Following bending type from right to left may cause damage to the tubing.
Installation Connecting the Connection Of The Piping Drain Hose • The drain hose can be connected at two different positions. Use the most convenient position and, if necessary, exchange the position of the drain pan, rubber cap and the drain hose. ➊ Drain pan ➋ Rubber cap ➌ Drain hose ➍ Exchange if necessary • Remove the drain hose. • Securely insert both the rubber plug and drain hose into the drain outlets. Be sure the rubber the cap is securely fastened so that there is no leakage.
Installation Connecting the Connection Of The Piping Cable NOTE Connector trade size for this unit is 1/2" for instructions on connecting depending on the wire type you are using. Wiring Diagram Indoor Unit Terminal (4P) Connecting cable(Low voltage) b 1 Outdoor Unit Terminal (6P) 1 2 2 3 3 4 4 Power supply a L1* 5 L2 6 To branch circuit G Ground * L1 is neutral for 115V models. NOTE 1. shows field wiring. 2. Separately wire the high and low voltage line. 3.
Installation How to use the front panel 1. Front panel opening Hold the two ends of the front panel at the bottom and move it upward. Front panel 2. Front panel closing Move the link upward and close the front panel. 3. Front panel removing Raise the link up to hook hanger and remove front panel forward. CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power circuit specifically for the air conditioner.
Installation Checking The Drainage Connecting area drain hose Leakage checking Drain pan Drain hose Leakage checking Drain piping • The drain hose should point downward for easy drain flow. Downward slope • Avoid these situations. Accumulated drain water Air Do not raise Water leakage Water leakage Waving Tip of drain hose dipped in water Water leakage Less than 50mm gap Ditch Installation Manual 25 ENGLISH • Pour a glass of water on the drain pan.
Installation Forming The Piping Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. • If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately. In cases where the outdoor unit is installed below the indoor unit perform the following. • Tape the piping, drain hose and connecting cable from down to up.
Installation Air Purging Air purging With Vacuum Pump Preparation • Check that each tubing(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Installation Soap water method (1) Remove the caps from the gas side and liquid side valves. (2) Remove the service-port cap from the gas side valve. (3) To open the gas side valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 seconds, and close it. (4) Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
Installation Charging ■ Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 30g(0.32oz) of R-410A per meter(foot). Pipe Size Capacity (Btu/h) Suction 12k Evap Ø12.7mm(1/2") Ø6.35mm(1/4") Standard Length m(ft) Max. Elevation m(ft) Max. length m(ft) Additional Refrigerant g/m(oz/ft) 7.5(25) 7.5(25) 15(49) 20(0.22) Example: A 30ft line set is used 5 additional ft X 0.22 ounce per foot= add 1.
Test Running Test Running 1. Check that all tubing and wiring have been properly connected. 2. Check that the gas and liquid side service valves are fully open. 3. Ensure the difference between the intake temperature and the discharge is more than 46.4°F(8°C) (Cooling) or (Heating). Intake temperature Prepare remote control Discharge air 1. Remove the battery cover by pulling it according to the arrow direction. 2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
Installation guide at the seaside Installation guide at the seaside Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction. Sea wind Sea wind 2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Room Air Conditioner