STAREX-IS BSM Manual Fig. 5.1-83 CAN Rack FAN Fail 5.1.1.2. BSC Occurrence Alarm Message 5.1.1.2.1. CCSB 5.1.1.2.1.1. CCP Processor 1) When A-Side of the duplicated CCP is normal and functional problems occur on the B-Side board Fig. 5.1-84 CCSB CCP Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated CCP has a functional problem Fig. 5.
STAREX-IS BSM Manual Fig. 5.1-86 CCSB CCP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated CCP is removed Fig. 5.1-87 CCSB CCP Dual Board Open Fail 5.1.1.2.1.2. SCP Processor 1) When A-Side of the duplicated SCP is normal and functional problems occur on the B-Side board Fig. 5.1-88 CCSB SCP Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated SCP has a functional problem SMD-011-PMA210 Page:630(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-89 CCSB SCP Dual Function Fail 3) When A-Side of the duplicated SCP is normal and B-Side board is removed Fig. 5.1-90 CCSB SCP Single Board Open Fail 4) When A-Side is removed entire B-Side of the duplicated SCP is removed Fig. 5.1-91 CCSB SCP Dual Board Open Fail 5.1.1.2.1.3. STIA Board 1) When functional faults occur on STIA board SMD-011-PMA210 Page:631(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-92 CCSB STIA Function Fail 2) When STIA board is removed Fig. 5.1-93 CCSB STIA Board Open Fail 5.1.1.2.1.4. PRI Board 1) When A-Side of the duplicated PRI is normal and functional problems occur on the B-Side board Fig. 5.1-94 CCSB PRI Single Power Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated PRI has a functional problem SMD-011-PMA210 Page:632(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-95 CCSB PRI Dual Power Fail 3) When A-Side of the duplicated PRI is normal and B-Side board is removed Fig. 5.1-96 CCSB PRI Single Power Open Fail 4) When A-Side is removed after B-Side of the duplicated PRI is removed Fig. 5.1-97 CCSB PRI Dual Power Open Fail 5.1.1.2.1.5. Others 1) When ABID board is removed SMD-011-PMA210 Page:633(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-98 CCSB ABID Board Open 2) When CCP does not receive 1pps Clock from GPSD normally Fig. 5.1-99 CCSB 1PPS Clock Fail 3) When CCP does not receive 10MHz Clock from GPSD normally Fig. 5.1-100 CCSB 10MHz Clock Fail 4) When faults occur in SubHiway Cable between STIA and VLIA SMD-011-PMA210 Page:634(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-101 CCSB STIA SHW Link Fail 5) When faults occur in CCBU Alarm Cable Fig. 5.1-102 CCSB Alarm Cable Open 5.1.1.2.2. ASMB 5.1.1.2.2.1. NCP Processor 1) When A-Side of the duplicated NCP is normal and functional problems occur on B-Side board Fig. 5.1-103 ASMB NCP Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated NCP has a functional problem Fig. 5.1-104 ASMB NCP Dual Function Fail SMD-011-PMA210 Page:635(877) Issue:1.
STAREX-IS BSM Manual 3) When A-Side of the duplicated NCP is normal and B-Side board is removed Fig. 5.1-105 ASMB NCP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated NCP is removed Fig. 5.1-106 ASMB NCP Dual Board Open Fail 5.1.1.2.2.2. ASCA Board 1) When A-Side of the duplicated ASCA is normal and functional problems occur on the B-Side board Fig. 5.
STAREX-IS BSM Manual Fig. 5.1-108 ASMB ASCA Dual Function Fail 3) When A-Side of the duplicated ASCA is normal and B-Side board is removed Fig. 5.1-109 ASMB ASCA Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated ASCA is removed Fig. 5.1-110 ASMB ASCA Dual Board Open Fail 5.1.1.2.2.3. ASIA Board 1) When A-Side of the duplicated ASIA is normal and functional problems occur on the B-Side board SMD-011-PMA210 Page:637(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-111 ASMB ASIA Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated ASIA has a functional problem Fig. 5.1-112 ASMB ASIA Dual Function Fail 3) When A-Side of the duplicated ASIA is normal and B-Side board is removed Fig. 5.1-113 ASMB ASIA Single Board Fail 4) When A-Side is removed after B-Side of the duplicated ASIA is removed SMD-011-PMA210 Page:638(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-114 ASMB ASIA Dual Board Open Fail 5.1.1.2.2.4. ATSA Board 6) When functional problems occur on ATSA board Fig. 5.1-115 ASMB ATSA Function Fail 7) When ATSA board is removed Fig. 5.1-116 ASMB ATSA Board Open Fail 5.1.1.2.2.5. PRI Board 1) When A-Side of the duplicated PRI is normal and functional problems occur on the B-Side board SMD-011-PMA210 Page:639(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-117 ASMB PRI Single Power Fail 2) When functional problems occur on the A-Side and B-Side of the duplicated PRI has a functional problem Fig. 5.1-118 ASMB PRI Dual Power Fail 3) When A-Side of the duplicated PRI is normal and B-Side board is removed Fig. 5.1-119 ASMB PRI Single Power Open Fail 4) When A-Side is removed after B-Side of the duplicated PRI is removed SMD-011-PMA210 Page:640(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-120 ASMB PRI Dual Power Open Fail 5.1.1.2.2.6. Others 1) When ASMB Alarm Cable opens Fig. 5.1-121 ASMB Alarm Cable Open 5.1.1.2.3. ALSB 5.1.1.2.3.1. ALP Processor 1) When A-Side of the duplicated ALP is normal and functional problems occur on the B-Side board Fig. 5.1-122 ASLB ALP Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated ALP has a functional problem SMD-011-PMA210 Page:641(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-123 ASLB ALP Dual Function Fail 3) When A-Side of the duplicated ALP is normal and B-Side board is removed Fig. 5.1-124 ASLB ALP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated ALP is removed Fig. 5.1-125 ASLB ALP Dual Board Open Fail 5.1.1.2.3.2. ALMA Board 1) When A-Side of the duplicated ALMA is normal and functional problems occur on the B-Side board SMD-011-PMA210 Page:642(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-126 ASLB ALMA Single Function Fail 2) When functional problems occur A-Side after B-Side of the duplicated ALMA has a functional problem Fig. 5.1-127 ASLB ALP Dual Function Fail 3) When A-Side of the duplicated ALMA is normal and B-Side board is removed Fig. 5.1-128 ASLB ALP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated ALMA is removed SMD-011-PMA210 Page:643(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-129 ASLB ALP Dual Board Open Fail 5.1.1.2.3.3. ALPA Board 1) When functional faults occur on ALPA board Fig. 5.1-130 ASLB ALPA Function Fail 2) When ALPA board is removed Fig. 5.1-131 ASLB ALPA Board Open Fail 5.1.1.2.3.4. PRI Board 1) When A-Side of the duplicated PRI is normal and functional problems occur on the B-Side board SMD-011-PMA210 Page:644(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-132 ASLB PRI Single Power Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated PRI has a functional problem Fig. 5.1-133 ASLB PRI Dual Power Fail 3) When A-Side of the duplicated PRI is normal and B-Side board is removed Fig. 5.1-134 ASLB PRI Single Power Open Fail 4) When A-Side is removed after B–Side of the duplicated PRI is removed SMD-011-PMA210 Page:645(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-135 ASLB PRI Dual Power Open Fail 5.1.1.2.3.5. Others 1) When ALSB Shelf Alarm Cable is removed Fig. 5.1-136 ASLB Alarm Cable Open 2) When Loss Of Signal Error occurs in ALPA link Fig. 5.1-137 ASLB ALPA Link Fail((LOS) 3) When Out Of Frame Error occurs in ALPA link SMD-011-PMA210 Page:646(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-138 ASLB ALPA Link Fail((OOF) 4) When Alarm Indication Signal Error occurs in ALPA link Fig. 5.1-139 ASLB ALPA Link Fail((AIS) 5) When Remote Alarm Indication Error occurs in ALPA link Fig. 5.1-140 ASLB ALPA Link Fail((RAI) 5.1.1.2.4. SLB 5.1.1.2.4.1. SMP(SLMA) Processor 1) When functional faults occur on SLMA board SMD-011-PMA210 Page:647(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-141 SLB SMP Function Fail 2) When SLMA board is removed Fig. 5.1-142 SLB SMP Board Open Fail 5.1.1.2.4.2. SLPA Board 1) When functional faults occur on SLPA board Fig. 5.1-143 SLB SLPA Function Fail 2) When SLPA board is removed SMD-011-PMA210 Page:648(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-144 SLB SLPA Board Open Fail 5.1.1.2.4.3. PRI 1) When functional faults occur on PRI board Fig. 5.1-145 SLB PRI Power Fail 2) When PRI board is removed Fig. 5.1-146 SLB PRI Power Open Fail 5.1.1.2.4.4. Others 1) When SLB Shelf Alarm Cable is removed SMD-011-PMA210 Page:649(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-147 SLB Alarm Cable Open 2) When Clock Cable is removed from CCP Fig. 5.1-148 SLB SMP Clock Fail 3) When SAID board is removed Fig. 5.1-149 SLB SMP SAID Open Fail 5.1.1.2.5. VCB 5.1.1.2.5.1. VMP(VCMA) Processor 1) When functional problems occur on VCMA board SMD-011-PMA210 Page:650(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-150 VCB VMP Function Fail 2) When VCMA board is removed Fig. 5.1-151 VCB VMP Board Open Fail 5.1.1.2.5.2. VCPA Board 1) When functional faults occur on VCPA board Fig. 5.1-152 VCB VCPA Function Fail 2) When VCPA board is removed SMD-011-PMA210 Page:651(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-153 VCB VCPA Board Open Fail 5.1.1.2.5.3. VLIA Board 1) When a functional board occurs on VLIA board Fig. 5.1-154 VCB VLIA Function Fail 2) When VLIA board is removed Fig. 5.1-155 VCB VLIA Board Open Fail 3) When Remote Error occurs in the link between VLIA and MSC SMD-011-PMA210 Page:652(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-156 VCB VLIA Link Fail(Remote Error) 4) When Local Error occurs in the link between VLIA and MSC Fig. 5.1-157 VCB VLIA Link Fail(Local Error) 5) When SLIP Error occurs in the link between VLIA and MSC Fig. 5.1-158 VCB VLIA Link Fail(SLIP Error) 6) When BIT Error occurs in the link between VLIA and MSC SMD-011-PMA210 Page:653(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-159 VCB VLIA Link Fail(BIT Error) 5.1.1.2.5.4. PRI 1) When functional faults occur on PRI board Fig. 5.1-160 VCB PRI Power Fail 2) When PRI board is removed Fig. 5.1-161 VCB PRI Power Open Fail 5.1.1.2.5.5. Others 1) When VCB Shelf Alarm Cable is removed Fig. 5.1-162 VCB Alarm Cable Open 2) When Clock Cable is removed from CCP SMD-011-PMA210 Page:654(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-163 VCB VMP Clock Cable Open Fail 3) When SAID board is removed Fig. 5.1-164 VCB SAID Board Open 5.1.1.2.6. FAN and Others 1) When a problem occurs in BSC FAN Fig. 5.1-165 VCB Rack FAN Fail 5.1.1.3. BTS Occurrence Alarm Message 5.1.1.3.1. BSPB 5.1.1.3.1.1. BSP Processor 1) When A-Side of the duplicated BSP is normal and functional problems occur on the B-Side board SMD-011-PMA210 Page:655(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-166 BSPB BSP Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated BSP has a functional problem Fig. 5.1-167 BSPB BSP Dual Function Fail 3) When A-Side of the duplicated BSP is normal and B-Side board is removed Fig. 5.1-168 BSPB BSP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated BSP is removed SMD-011-PMA210 Page:656(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-169 BSPB BSP Dual Board Open Fail 5.1.1.3.1.2. PRI within BSPB, BANB Unit 1) When A-Side of the duplicated PRI is normal and functional problems occur on the B-Side board Fig. 5.1-170 BSPB PRI Single Power Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated PRI has a functional problem Fig. 5.1-171 BSPB PRI Dual Power Fail 3) When A-Side of the duplicated PRI is normal and B –Side board is removed SMD-011-PMA210 Page:657(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-172 BSPB PRI Single Power Open Fail 4) When A-Side is removed after B-Side of the duplicated PRI is removed Fig. 5.1-173 BSPB PRI Dual Power Open Fail 5.1.1.3.1.3. Others 1) When BSP does not receive 1pps Clock from GPSD normally Fig. 5.1-174 BSPB BSP 1PPS Clock Fail 2) When BSP does not receive 10MHz Clock from GPSD normally SMD-011-PMA210 Page:658(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-175 BSPB BSP 10MHz Clock Fail 5.1.1.3.2. BANB 5.1.1.3.2.1. ARIA Board 1) When functional faults occur on ARIA board Fig, 5.1-176 BANB ARIA Function Fail 2) When ARIA board is removed Fig. 5.1-177 BANB ARIA Board Open Fail 5.1.1.3.2.2. BPPA Board 1) When functional faults occur on BPPA board SMD-011-PMA210 Page:659(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-178 BANB BPPA Function Fail 2) When BPPA board is removed Fig. 5.1-179 BANB BPPA Board Open Fail 5.1.1.3.2.3. BCRA Board 1) When A-Side of the duplicated BCRA is normal and functional problems occur on the B-Side board Fig. 5.1-180 BANB BCRA Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated BCRA has a functional problem SMD-011-PMA210 Page:660(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-181 BANB BCRA Dual Function Fail 3) When A-Side of the duplicated BCRA is normal and B-Side board is removed Fig. 5.1-182 BANB BCRA Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated BCRA is removed. Fig. 5.1-183 BANB BCRA Dual Board Open Fail 5.1.1.3.2.4. LICA Board 1) When functional faults occur on LICA board SMD-011-PMA210 Page:661(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-184 BANB LICA Function Fail 2) When LICA board is removed Fig. 5.1-185 BANB LICA Board Fail 5.1.1.3.3. BSTB 5.1.1.3.3.1. BADA Board 1) When BADA Board Alarm Cable is removed Fig. 5.1-186 BSTB BADA Alarm Cable Open 2) When a problem occurs in BADA Board power SMD-011-PMA210 Page:662(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-187 BSTB BADA Power Fail 3) When functional faults occur on BADA board Fig. 5.1-188 BSTB BADA Function Fail 5.1.1.3.4. RISB 5.1.1.3.4.1. RISA Board 1) When RISA Board Alarm Cable is removed Fig. 5.1-189 RISB RISA Alarm Cable Open 2) When a problem occurs in RISA board power SMD-011-PMA210 Page:663(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-190 RISB RISA Power Fail 3) When functional faults occur on RISA board Fig. 5.1-191 RISB RISA Function Fail 5.1.1.3.5. BOTB 5.1.1.3.5.1. BOTA Board 1) When BOTA Board Alarm Cable is removed Fig. 5.1-192 BOTB BOTA Alarm Cable Open 2) When a problem occurs in BOTA board power SMD-011-PMA210 Page:664(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-193 BOTB BOTA Power Fail 3) When functional faults occur on BOTA board Fig. 5.1-194 BOTB BOTA Board Open Fail 5.1.1.3.6. BTGB 5.1.1.3.6.1. GPS-R Board 1) When A-Side of the duplicated GPSR is normal and functional problems occur on B –Side board Fig. 5.1-195 BTGB GPS Single Function Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated GPSR has a functional problem SMD-011-PMA210 Page:665(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-196 BTGB GPS Dual Function Fail 3) When A-Side of the duplicated GPSR is normal and faults occur in B-Side power Fig. 5.1-197 BTGB GPS Single Power Fail 4) When a problem occurs in A-Side power after B-Side power of the duplicated GPSR has a problem Fig. 5.1-198 BTGB GPS Dual Power Fail 5) When A-Side of the duplicated GPSR is normal and B-Side board is removed SMD-011-PMA210 Page:666(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-199 BTGB GPS Single Board Open Fail 6) When A-Side is removed after B-Side of the duplicated GPSR is removed Fig. 5.1-200 BTGB GPS Dual Board Open Fail 7) When GPSR Control Cable is removed Fig. 5.1-201 BTGB GPS Control Cable Open 8) When GPSR Alarm Cable is removed SMD-011-PMA210 Page:667(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-202 BTGB GPS Alarm Cable Open 5.1.1.3.7. DBPB 5.1.1.3.7.1. DBPA Board 1) When functional faults occur on DBPA board Fig. 5.1-203 DBPB DBPA Function Fail 2) When DBPA board is removed Fig. 5.1-204 DBPB DBPA Board Open Fail 5.1.1.3.8. RCCB 5.1.1.3.8.1. RCP Processor 1) When A-Side of the duplicated RCP is normal and functional problems occur on the B-Side board Fig. 5.1-205 RCCB RCP Single Function Fail SMD-011-PMA210 Page:668(877) Issue:1.
STAREX-IS BSM Manual 2) When functional problems occur on the A-Side after B-Side of the duplicated RCP has a functional problem Fig. 5.1-206 RCCB RCP Dual Function Fail 3) When A-Side of the duplicated RCP is normal and B-Side board is removed Fig. 5.1-207 RCCB RCP Single Board Open Fail 4) When A-Side is removed after B-Side of the duplicated RCP is removed Fig. 5.1-208 RCCB RCP Dual Board Open Fail 5.1.1.3.8.2.
STAREX-IS BSM Manual Fig. 5.1-209 RCCB BUDA Function Fail 2) When BUDA board is removed Fig. 5.1-210 RCCB BUDA Board Open Fail 5.1.1.3.8.3. PACA Board 1) When functional faults occur on PACA board Fig. 5.1-211 RCCB PACA Function Fail 2) When PACA board is removed SMD-011-PMA210 Page:670(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-212 RCCB PACA Board Open Fail 5.1.1.3.8.4. PRI Board for Providing DBPB/RCCB UNIT Power 1) When A-Side of the duplicated PRI is normal and functional problems occur on the B-Side board Fig. 5.1-213 DBPB/RCCB PRI Single Power Fail 2) When functional problems occur on the A-Side after B-Side of the duplicated PRI has a functional problem Fig. 5.
STAREX-IS BSM Manual Fig. 5.1-215 DBPB/RCCB PRI Single Power Open Fail 4) When A-Side is removed after B-Side of the duplicated PRI is removed Fig. 5.1-216 DBPB/RCCB PRI Dual Power Open Fail 5.1.1.3.8.5. Others 1) When DBPB/RCCB UNIT Alarm Cable is removed Fig. 5.1-217 DBPB/RCCB Alarm Cable Open 5.1.1.3.9. LPAB 5.1.1.3.9.1. LPAU Board 1) When LPAB Alarm Cable is removed SMD-011-PMA210 Page:672(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-218 LPAB Alarm Cable Open 2) When functional faults occur in LPAB Combiner Fig. 5.1-219 LPAB LPA Combiner Fail 3) When faults occur in LPAB Combiner FAN Fig. 5.1-220 LPAB LPA Combiner FAN Fail 4) When LPA board is removed SMD-011-PMA210 Page:673(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-221 LPAB LPA Board Open Fail 5) When functional faults occur on LPA board Fig. 5.1-222 LPAB LPA Board Function Fail 6) When DC power of LPA board is unstable Fig. 5.1-223 LPAB LPA DC/DC Alarm 7) When much RF power is reflected in output end of LPA board Fig. 5.1-224 LPAB LPA VSWR Alarm 8) When LPA board is disabled SMD-011-PMA210 Page:674(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-225 LPAB LPA Disable Alarm 9) When input power level of LPA board is high Fig. 5.1-226 LPAB LPA Over Power Warning 10) When LPA board temperature is high Fig. 5.1-227 LPAB LPA Over Temperature Alarm 11) When input Power level of LPA board is high SMD-011-PMA210 Page:675(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-228 LPAB LPA Over Power Alarm 5.1.1.3.10. HPAB 5.1.1.3.10.1. HPA Board 1) When HPAB Alarm Cable is removed Fig. 5.1-229 HPAB HPA Alarm Cable Open 2) When HPA board is removed Fig. 5.1-230 HPAB HPA Board Open Fail 3) When functional faults occur on HPA board Fig. 5.1-231 HPAB HPA Power Fail 4) When faults occur in HPA Board Power Supply SMD-011-PMA210 Page:676(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-232 HPAB HPA Power Supply Alarm 5) When much RF power is reflected in HPA output end Fig. 5.1-233 HPAB HPA VSWR Alarm 6) When HPA board is disabled Fig. 5.1-234 HPAB HPA Disable Alarm 7) When HPA board temperature is high Fig. 5.1-235 HPAB HPA Over Temperature Alarm 8) When input Power level of HPA board is high SMD-011-PMA210 Page:677(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-236 HPAB HPA Over Power Alarm 5.1.1.3.11. CFEB 5.1.1.3.11.1. LNA Board 1) When LNA Alarm Cable board is removed Fig. 5.1-237 CFEB LNA Alarm Cable Open Fail 2) When LNA board is removed Fig. 5.1-238 CFEB LNA Board Open Fail 3) When functional faults occur on LNA board Fig. 5.1-239 CFEB LNA Function Fail 5.1.1.3.12. Environment Alarm 1) When outdoor BTS Environment Alarm Cable is removed SMD-011-PMA210 Page:678(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-240 Outdoor BTS ENV Alarm Cable Open 2) When outdoor BTS Rectifier Alarm Cable is removed Fig. 5.1-241 Outdoor BTS ENV Rectifier Unit Alarm Cable Open 3) When outdoor BTS Cold Starter fails Fig. 5.1-242 Outdoor BTS ENV Cold Starter Fail 4) When outdoor BTS Rectifier Unit fails SMD-011-PMA210 Page:679(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-243 Outdoor BTS ENV Rectifier Unit Fail 5) Outdoor BTS Voltage High Alarm Fig. 5.1-244 Outdoor BTS ENV Voltage High Alarm 6) Outdoor BTS Voltage Low Alarm Fig. 5.1-245 Outdoor BTS ENV Voltage Low Alarm 7) When outdoor BTS AC fails Fig. 5.1-246 Outdoor BTS AC Fail 8) Outdoor BTS Battery Voltage Low Alarm SMD-011-PMA210 Page:680(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-247 Outdoor BTS ENV Battery Low Voltage Alarm 9) Outdoor BTS Fuse/Relay Loss Alarm Fig. 5.1-248 Outdoor BTS ENV Fuse/Relay Loss Alarm 10) When outdoor BTS DMC-14 fails Fig. 5.1-249 Outdoor BTS ENV DMC-14 Fail 11) Outdoor BTS Power Cut Alarm SMD-011-PMA210 Page:681(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-250 Outdoor BTS ENV Power Cut Alarm 12) Outdoor BTS Temperature High Alarm Fig. 5.1-251 Outdoor BTS ENV Temperature High Alarm 13) Outdoor BTS Temperature Low Alarm Fig. 5.1-252 Outdoor BTS ENV Temperature Low Alarm 14) Outdoor BTS Water High Alarm Fig. 5.1-253 Outdoor BTS ENV Water High Alarm 15) Outdoor BTS Water Low Alarm SMD-011-PMA210 Page:682(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-254 Outdoor BTS ENV Water Low Alarm 16) Outdoor BTS Fire Alarm Fig. 5.1-255 Outdoor BTS ENV Fire Alarm 17) Outdoor BTS Humidity High Alarm Fig. 5.1-256 Outdoor BTS ENV Humidity High Alarm 18) When outdoor BTS ACU Module fails SMD-011-PMA210 Page:683(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-257 Outdoor BTS ENV ACU Module Fail 19) When outdoor BTS Heat Exchanger Power fails Fig. 5.1-258 Outdoor BTS ENV Heat Exchanger Power Fail 20) When outdoor BTS Heat Exchanger fails Fig. 5.1-259 Outdoor BTS ENV Heat Exchanger Fail 21) When outdoor BTS LPA FAN fails Fig. 5.1-260 Outdoor BTS ENV LPA FAN Fail 22) When outdoor BTS AC Equipment Heater fails SMD-011-PMA210 Page:684(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-261 Outdoor BTS ENV AC Equipment Heater Fail 23) Outdoor BTS Front/Rear Door Open Alarm Fig. 5.1-262 Outdoor BTS ENV Front/Rear Door Open Alarm 24) Outdoor BTS Side Door Open Alarm Fig. 5.1-263 Outdoor BTS ENV Side Door Open Alarm 25) When outdoor BTS FAN fails SMD-011-PMA210 Page:685(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-264 Outdoor BTS ENV FAN Fail 26) When outdoor BTS AC Battery Heater fails Fig. 5.1-265 Outdoor BTS ENV AC Battery Heater Fail 27) Indoor BTS Temperature High Alarm Fig. 5.1-266 Indoor BTS ENV Temperature High Alarm 28) Indoor BTS Temperature Low Alarm Fig. 5.1-267 Indoor BTS ENV Temperature Low Alarm 30) Indoor BTS Flood Alarm SMD-011-PMA210 Page:686(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-268 Indoor BTS ENV Flood Alarm 31) Indoor BTS Door #1 Open Alarm Fig. 5.1-269 Indoor BTS ENV Door #1 Open Alarm 32) Indoor BTS Door #2 Open Alarm Fig. 5.1-270 Indoor BTS ENV Door #2 Open Alarm 33) Indoor BTS Fire Alarm SMD-011-PMA210 Page:687(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-271 Indoor BTS ENV Fire Alarm 34) When indoor BTS Rectifier #1 fails Fig. 5.1-272 Indoor BTS ENV Rectifier #1 fails 35) When indoor BTS Rectifier #2 fails Fig. 5.1-273 Indoor BTS ENV Rectifier #2 Fail 36) When indoor BTS Aircon #1 fails Fig. 5.1-274 Indoor BTS ENV Aircon #1 Fail 37) When indoor BTS Aircon #2 fails SMD-011-PMA210 Page:688(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-275 Indoor BTS ENV Aircon #2 Fail 38) Indoor BTS Water Leakage Alarm Fig. 5.1-276 Indoor BTS ENV Water Leakage Alarm 5.1.1.3.13. Others 1) If a problem occurs in BTS FAN Fig. 5.1-277 BTS Rack FAN Fail 5.1.2. Fault Message 5.1.2.1. Keep-Alive-related Fault Keep-Alive Fault occurs by two reasons. One in Tx section SMD-011-PMA210 Page:689(877) Issue:1.
STAREX-IS BSM Manual 5.1.2.1.1.1. CNP Report 1) CNP NCP section Fig. 5.1-278 Keep-Alive Fault between CNP and NCP 5.1.2.1.1.2. PNP Report 1) PNP NCP section Fig. 5.1-279 Keep-Alive Fault between PNP and NCP 2) PNP PCP section Fig. 5.1-280 Keep-Alive Fault between PNP and PCP 5.1.2.1.1.3. PCP Report 1) PCP CCP section SMD-011-PMA210 Page:690(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-281 Keep-Alive Fault between PCP and CCP 2) PCP PNP section Fig. 5.1-282 Keep-Alive Fault between PCP and PNP 5.1.2.1.1.4. CCP Report 1) CCP NCP section Fig. 5.1-283 Keep-Alive Fault between CCP and NCP 2) CCP PCP section SMD-011-PMA210 Page:691(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-284 Keep-Alive Fault between CCP and PCP 3) CCP BSP section Fig. 5.1-285 Keep-Alive Fault between CCP and BSP 4) CCP SCP section Fig. 5.1-286 Keep-Alive Fault between CCP and SCP 5) CCP SMP section SMD-011-PMA210 Page:692(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-287 Keep-Alive Fault between CCP and SMP 6) CCP VMP section Fig. 5.1-288 Keep-Alive Fault between CCP and VMP 5.1.2.1.1.5. NCP Report 1) NCP CNP section Fig. 5.1-289 Keep-Alive Fault between NCP and CNP 2) NCP CCP section SMD-011-PMA210 Page:693(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-290 Keep-Alive Fault between NCP and CCP 3) NCP PNP section Fig. 5.1-291 Keep-Alive Fault between NCP and PNP 4) NCP CRP section Fig. 5.1-292 Keep-Alive Fault between NCP and CRP 5.1.2.1.1.6. SCP Report 1) SCP CCP section SMD-011-PMA210 Page:694(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-293 Keep-Alive Fault between SCP and CCP 2) SCP STIA section Fig. 5.1-294 Keep-Alive Fault between SCP and STIA 5.1.2.1.1.7. BSP Report 1) BSP CCP section Fig. 5.1-295 Keep-Alive Fault between BSP and CCP 2) BSP RCP section SMD-011-PMA210 Page:695(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-296 Keep-Alive Fault between BSP and RCP 3) BSP BPP section Fig. 5.1-297 Keep-Alive Fault between BSP and BPP 4) RCP DBPA section Fig. 5.1-298 Keep-Alive Fault between RCP and DBPA 5.1.2.2. CCP Processing-related Fault 5.1.2.2.1. VCE Qcelp Algorithm Test Fault 1) Vocoder Clock Fault SMD-011-PMA210 Page:696(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-299 Vocoder Clock Fault 2) QCELP0 Algorithm Fault Fig. 5.1-300 QCELP0 Algorithm Fault 3) QCELP1 Algorithm Fault Fig. 5.1-301 QCELP1 Algorithm Fault 4) QCELP2 Algorithm Fault SMD-011-PMA210 Page:697(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-302 QCELP2 Algorithm Fault 5) QCELP3 Algorithm Fault Fig. 5.1-303 QCELP3 Algorithm Fault 6) VCPA LoopBack Test Fault Fig. 5.1-304 VCPA Loop-Back Test Fault 5.1.2.2.2. VCE DSP Test Fault 1) When faults occur upon DSP ROM TEST SMD-011-PMA210 Page:698(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-305 Vocoder DSP ROM TEST Fault 2) When faults occur upon DSP RAM TEST Fig. 5.1-306 Vocoder DSP RAM TEST Fault 3) When faults occur upon DSP ROM/RAM TEST Fig. 5.1-307 Vocoder DSP ROM/RAM TEST Fault 4) When faults occur upon DSP ALU TEST SMD-011-PMA210 Page:699(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-308 Vocoder DSP ALU TEST Fault 5) When faults occur DSP ROM/ALU TEST Fig. 5.1-309 Vocoder DSP ROM/ALU TEST Fault 6) When faults occur upon DSP RAM/ALU TEST Fig. 5.1-310 Vocoder DSP RAM/ALU TEST Fault 7) When faults occur upon DSP ROM/RAM/ALU TEST SMD-011-PMA210 Page:700(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-311 Vocoder DSP ROM/RAM/ALU TEST Fault 5.1.2.2.3. VLIA T1/E1 Trunk Time Slot Fault 1) When faults occur upon VLIA E1/T1 Trunk Time-Slot TEST Fig. 5.1-312 VLIA E1/T1 Trunk Time-Slot Test Fault 5.1.2.2.4. Call Fail 1) SCI Fault Fig. 5.1-313 SCI Fault 2) BASE ID Fault SMD-011-PMA210 Page:701(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-314 Base ID Fault 3) BTS ID Fault Fig. 5.1-315 BTS ID Fault 4) Sector ID Fault Fig. 5.1-316 Sector ID Fault 5) Neighbor List Fault SMD-011-PMA210 Page:702(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-317 Neighbor List Fault 6) MSC Overload Fault Fig. 5.1-318 MSC Overload Fault 7) CCP Overload Fault Fig. 5.1-319 CCP Overload Fault 8) BSP Overload Fault SMD-011-PMA210 Page:703(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-320 BSP Overload Fault 9) Get Task Function Fault Fig. 5.1-321 Get Task Function Fault 10) Free Task Function Fault Fig. 5.1-322 Free Task Function Fault 11) Get Buffer Function Fault SMD-011-PMA210 Page:704(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-323 Get Buffer Function Fault 12) Authentication Fault Fig. 5.1-324 Authentication Fault 5.1.2.3. RCP Processing-related Fault 1) When a problem occurs in STM SYSTEM TIME Fig. 5.1-325 STM System Time Fault 2) CDM TX Parity Fault SMD-011-PMA210 Page:705(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-326 CDM TX Parity Fault 3) CDM RX Parity Fault Fig. 5.1-327 CDM RX Parity Fault 4) CDM TX Over-Flow Fault Fig. 5.1-328 CDM TX Over-Flow Fault 5) CDM TX M2R DATA Error SMD-011-PMA210 Page:706(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-329 CDM TX M2R DATA Error 6) CDM TX R2B DATA Error Fig. 5.1-330 CDM TX R2B DATA Error 7) CDM RX B2R DATA Error Fig. 5.1-331 CDM RX B2R DATA Error 8) OverHead Channel Config No Received Fault Fig. 5.1-332 OverHead Channel Config No Received Fault 9) OverHead Channel Config Invalid Fault SMD-011-PMA210 Page:707(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-333 OverHead Channel Config Invalid Fault 5.1.2.4. DBPA Processing-related Fault 1) When faults occur in DBPA Internal Even Clock Fig. 5.1-334 DBPA Internal Even Clock Fault 2) When faults occur in DBPA External System Clock Fig. 5.1-335 DBPA External System Clock Fault 3) When DBPA Channel Card can not receive TOD within 10 seconds SMD-011-PMA210 Page:708(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-336 DBPA TOD Not Active Fault 4) DBPA Common Channel No Free Queue Fail Fig. 5.1-337 DBPA CMC No Free Queue Fault 5) When faults occur in DBPA Internal System Clock Fig. 5.1-338 DBPA Internal Sync Clock Fault 6) DBPA Core No Free Queue Fail SMD-011-PMA210 Page:709(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-339 DBPA Core No Free Queue Fault 7) DBPA Queue Put Fail Fig. 5.1-340 DBPA Queue Put Fault 8) DBPA Queue Get Fail Fig. 5.1-341 DBPA Queue Get Fault 9) DPBA S/W WatchDog TimeOut Fail Fig. 5.1-342 DBPA S/W Watchdog Timeout Fault 10) DBPA Fatal Fault SMD-011-PMA210 Page:710(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-343 DBPA Fatal Fault 11) When DBPA Clock and Modem Control are bad Fig. 5.1-344 DBPA Bad Channel Modem Fault 12) When DBPA has a false TOD information Fig. 5.1-345 DBPA External TOD Fault 13) DBPA Internal OS Clock Fail SMD-011-PMA210 Page:711(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-346 DBPA Internal OS Clock Fault 14) DBPA BIT Chip Fail Fig. 5.1-347 DBPA BIT Fail 5.1.2.5. Channel-related Fault 1) When messages cannot be transferred to SVC because Message Queue for messages to be delivered to SVC is empty Fig. 5.1-348 DBPA TC No SVC Free Queue Fail 2) When Queue resources that save messages from BSP and RCP are used up Fig. 5.1-349 DBPA TC No Normal Free Queue Fail 3) When a problem occurs during Built-In Test SMD-011-PMA210 Page:712(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-350 DBPA TC Tx FWHENO Full Fail 4) When Queue resources that save messages to be sent to BSP are used up Fig. 5.1-351 DBPA ACH No Free Queue Fail 5) When Encoder Queue resources are used up Fig. 5.1-352 DBPA PC No Encoder Free Queue Fail 6) When Queue resources that save page messages except General Page messages are used up SMD-011-PMA210 Page:713(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-353 DBPA PC No Page Free Queue Fail 7) When Queue resources that save Quick Page messages are used up Fig. 5.1-354 DBPA PC No Quick Page Free Queue Fail 8) When Queue resources that save Reply Message are consumed as Reply is requested for the messages from BSP Fig. 5.1-355 DBPA PC No Reply Free Queue Fail 9) When Write errors occur more than 20 times continuously as Paging Channel performs Write Frame every 20ms SMD-011-PMA210 Page:714(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-356 DBPA PC Write Frame Fail 10) When Queue resources that save General Page messages from BSP are consumed Fig. 5.1-357 DBPA PC No General Page Free Queue Fail 5.1.2.6. BUDA Processing-related Fault 1) BUDA CHIPx16 Fault Fig. 5.1-358 BUDA CHIPx16 Fault 2) BUDA Forward Sync Fault SMD-011-PMA210 Page:715(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-359 BUDA Forward Sync Fault 3) BUDA Tx Saturation Fault Fig. 5.1-360 BUDA Tx Saturation Fault 4) BUDA Frame Error Fault Fig. 5.1-361 BUDA Frame Error Fault 5.1.2.7. BOTA Processing-related Fault 1) BOTA TOD Error Fault SMD-011-PMA210 Page:716(877) Issue:1.
STAREX-IS BSM Manual Fig. 5.1-362 BOTA TOD Error Fault 2) BOTA TOD Not Active Fault Fig. 5.1-363 BOTA TOD Not Active Fault 5.2. Status Command 5.2.1. Processor Status Change Report When processor status is changed in state block, the status change report messages are displayed on Console Window. This function can allow or inhibit messages display as a function that allows/inhibits the status message display.. 5.2.1.1.
STAREX-IS BSM Manual Fig. 5.2-1 CNP Processor Status Change Report 5.2.1.2. PNP Status Change Report When PNP processor status is changed, the messages are displayed on Console Window. It is the processor that the BSM keeps Alive and displays the messages, judging from the BSM status block. Fig. 5.2-2 PNP Processor Status Change Report 5.2.1.3. PCP Status Change Report When PCP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-3 PCP Processor Status Change Report 5.2.1.4. PMP Status Change Report When PMP processor status is changed, the messages are displayed on Console Window. It is the processor that PCP keeps Alive and reports the messages to the upper level BSM, judging from the PCP status block. Fig. 5.2-4 PMP Processor Status Change Report 5.2.1.5. CCP Status Change Report When CCP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-5 CCP Processor Status Change Report 5.2.1.6. NCP Status Change Report When NCP processor status is changed, the messages are displayed on Console Window. It is the processor that the BSM keeps Alive and displays the messages, judging from the BSM status block. Fig. 5.2-6 NCP Processor Status Change Report 5.2.1.7. SCP Status Change Report When SCP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-7 SCP Processor Status Change Report 5.2.1.8. SMP Status Change Report When SMP processor status is changed, the messages are displayed on Console Window. It is the processor that the CCP keeps Alive and reports the messages to the upper level BSM, judging from the CCP status block. Fig. 5.2-8 SMP Processor Status Change Report 5.2.1.9. VMP Status Change Report When VMP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-9 VMP Processor Status Change Report 5.2.1.10. ALP Status Change Report When ALP processor status is changed, the messages are displayed on Console Window. It is the processor that the CCP keeps Alive and reports the messages to the upper level BSM, judging from the CCP status block. Fig. 5.2-10 ALP Processor Status Change Report 5.2.1.11. BSP Status Change Report When BSP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-11 BSP Processor Status Change Report 5.2.1.12. CRP Status Change Report When CRP processor status is changed, the messages are displayed on Console Window. It is the processor that the NCP keeps Alive and reports the messages to the upper level BSM, judging from the NCP status block. Fig. 5.2-12 CRP Processor Status Change Report 5.2.1.13. RCP Status Change Report When RCP processor status is changed, the messages are displayed on Console Window.
STAREX-IS BSM Manual Fig. 5.2-13 RCP Processor Status Change Report 5.2.1.14. BPP Status Change Report When BPP processor status is changed, the messages are displayed on Console Window. It is the processor that the BSP keeps Alive and reports the messages to the upper level BSM, judging from the BSP status block. Fig. 5.2-14 BPP Processor Status Change Report 5.2.2.
STAREX-IS BSM Manual 5.2.2.1. Overload Status Occurred Message When overload occurs in CCP or BSP processor, it is reported to upper level BSM. Overload occurs when Level is 12. Fig. 5.2-15 Overload Status Occurred Message 5.2.2.2. Overload Status Change Message After overload occurs in CCP or BSP processor, when overload status is changed, it is reported to upper level BSM. Fig. 5.2-16 Overload Status Change Message 5.2.2.3.
STAREX-IS BSM Manual Fig. 5.2-17 Overload Status Released Message 5.3. Loading Message 5.3.1. Processor Initialization Start Message Processor initialization start message is displayed when a target processor starts initialization. The following messages are displayed depending on the initialization type. Classification Message Type Initial Loading S2002 PROCESSOR INITIALIZATION START Standby Loading S2002 PROCESSOR STANDBY INITIALIZATION START Fig. 5.3-1 Processor Initialization Start Message 5.
STAREX-IS BSM Manual Processor initialization end message is displayed when a target processor ends initialization. The following messages are displayed depending on the initialization type. Classification Message Type Initial Loading S2100 PROCESSOR INITIALIZATION END Standby Loading S2100 PROCESSOR STANDBY INITIALIZATION END Fig. 5.3-2 Processor Initialization End Message 5.3.3.
STAREX-IS BSM Manual Fig. 5.3-3 Loading Start Message 5.3.4. Loading Completion Message Processor loading completion message is a message that reports loading completion of each block upon loading target processor. The following messages are displayed depending on the loading type.
STAREX-IS BSM Manual 5.3.5. Loading Failure Message Processor loading failure message is a message displayed when block fails in loading upon loading target processor. The following messages are displayed depending on the loading type. Classification Message Type General Loading S2105 PROCESSOR LOADING FAIL Block Loading S2105 PROCESSOR BLOCK LOADING FAIL Activation Loading S2105 PROCESSOR ACTIVATION LOADING FAIL Standby Loading S2105 PROCESSOR STANDBY LOADING FAIL Fig. 5.
STAREX-IS BSM Manual 6. Trouble Shoot This chapter describes problems caused by operating and solution to them. 6.1. If BSM is not operated 6.1.1. If BSM is not initialized 6.1.1.1. Shared Memory or Queue Problem 6.1.1.1.1. IPC Initialization Problem If the following messages are displayed start of MMI_server program [mmi] mmi is already in service. You can remove a file "IPCHEAD" and try again...
STAREX-IS BSM Manual 6.1.1.1.3. If IPC is not deleted If IPC is not deleted by “rmipc” command to operate BSM, delete it by force through the following command. ipcrm [ -m shmid ] [ -q msqid ] [ -Q msgkey ] [ -s semid ] [ -M shmkey ] [ -S semkey ] Description of each factor -m shmid Remove the shared memory identWhenier shmid from the system. The shared memory segment and data struc- ture associated with it are destroyed after the last detach.
STAREX-IS BSM Manual semaphores and data structure associated with it. 6.1.2. It can not function normally despite of its initialization 6.1.2.1. Informix Problem BSM Applications are saved as temporary data and data for reference in other blocks using Informix Database. Therefore, if Informix does not operate, BMS Applications cannot be run or run abnormally. 6.1.2.1.1.
STAREX-IS BSM Manual 6.2.1. Environment Variables 6.2.1.1. Display Setup Problem Register the system that corresponds to /etc/host files to protect BSM from external Access and allow to use the authenticated system. Make the format consistent with the following contents: 6.2.1.1.1. Main Server Name 150.150.62.100 zen.lgic.co.kr zen loghost In the above example, it is /etc/hosts file to operate the host called “zen” as a main server.
STAREX-IS BSM Manual The above is an example when GUI is not operated in spite of the attempt to operate GUI called “stmGUI”. It means that libXpm.so.x.xx file does not exist as shown above. In this case, two problems can be taken into consideration. 6.2.1.2.1. LD_LIBRARY_PATH Setup Setting up GUI Library is to change the system environment variables called LD_LIBRARY_PATH. The following is an example of how to set up variables.
STAREX-IS BSM Manual 6.2.2.2. If it is not registered in /etc/hosts file It is when registration is not allowed for security reasons. In this case, refer to how to compile /etc/hosts file of BSM environment variables setting among the above items and then add remote server name. SMD-011-PMA210 Page:735(877) Issue:1.
STAREX-IS BSM Manual 7. CHG- Appendix 7.1. Alarm/Fault Message Description and List 7.1.1. Alarm Message Description and List 7.1.1.1. CAN Generated Alarm Message Table 7.
STAREX-IS BSM Manual A8721 CAN PMPA DUAL ABNORMAL A8730 CAN ENPA SINGLE ABNORMAL A8731 CAN ENPA DUAL ABNORMAL A8740 CAN BCRA SINGLE ABNORMAL A8741 CAN BCRA DUAL ABNORMAL A8800 CAN PCPA 1PPS CLOCK FAIL A8810 CAN PCPA 10MHz CLOCK FAIL A8820 CAN FERA LINK FAIL A8840 CAN FERA PDSN LINK FAIL A9000 CAN CAMU SINGLE POWER FAIL A9001 CAN CAMU DUAL POWER FAIL A9010 CAN PCFU(PCP) SINGLE POWER FAIL A9011 CAN PCFU(PCP) DUAL POWER FAIL A9020 CAN PCFU(PMP) SINGLE POWER FAIL A9021 CAN PCFU(PMP
STAREX-IS BSM Manual 7.1.1.2. BSC Generated Alarm Message Table 7.
STAREX-IS BSM Manual A6220 BSC ASIA SINGLE ABNORMAL A6221 BSC ASIA DUAL ABNORMAL A6240 BSC AOTA BOARD DELETION A6250 BSC AOTA FUNCTION FAIL A6260 BSC ATSA BOARD DELETION A6270 BSC ATSA FUNCTION FAIL A6280 BSC ALPA BOARD DELETION A6290 BSC ALPA FUNCTION FAIL A6300 BSC STIA BOARD DELETION A6310 BSC STIA FUNCTION FAIL A6350 BSC STIA SHW LINK FAIL A6400 BSC SLPA BOARD DELETION A6410 BSC SLPA FUNCTION FAIL A6500 BSC VCPA BOARD DELETION A6510 BSC VCPA FUNCTION FAIL A6520 BSC VLIA B
STAREX-IS BSM Manual 7.1.1.3. BTS Generated Alarm Message Table 7.
STAREX-IS BSM Manual A0420 BTS RECTIFIER #1 FAIL A0421 BTS RECTIFIER #2 FAIL A0430 BTS AIRCON #1 FAIL A0431 BTS AIRCON #2 FAIL A0440 BTS WATER LEAKAGE ALARM A0500 BTS GPSR CONTROL CABLE OPEN A0600 BTS ALARM CABLE OPEN A0610 BTS FAN CABLE OPEN A0620 BTS ENVIRONMENT ALARM CABLE OPEN A0800 BTS RACK FAN FAIL A1000 BTS GPS SINGLE ABNORMAL A1001 BTS GPS DUAL ABNORMAL A1500 BTS BCRA SINGLE ABNORMAL A1501 BTS BCRA DUAL ABNORMAL A1550 BTS DRAN POWER FAIL A1560 BTS DRAN FUNCTION FAIL
STAREX-IS BSM Manual A2330 BTS BUDA FUNCTION FAIL A2340 BTS PACA BOARD DELETION A2350 BTS PACA FUNCTION FAIL A2400 BTS BADA POWER FAIL A2410 BTS BADA FUNCTION FAIL A2420 BTS LICA BOARD DELETION A2430 BTS LICA FUNCTION FAIL A2440 BTS ARIA BOARD DELETION A2450 BTS ARIA FUNCTION FAIL A2470 BTS BOTA POWER FAIL A2480 BTS BOTA FUNCTION FAIL A2490 BTS RISA FUNCTION FAIL A2491 BTS RISA POWER FAIL A2500 BTS LPA BOARD DELETION A2510 BTS LPA FUNCTION FAIL A2520 BTS LPA CONBINER FAIL A2
STAREX-IS BSM Manual 7.1.2. Fault Message Description and List Table 7.
STAREX-IS BSM Manual F1600 BTS DBPA NO PC ENCODER BUFFER ERROR F1610 BTS DBPA PC NO PAGE FREE QUEUE ERROR F1620 BTS DBPA PC NO QUICK PAGE FREE QUEUE ERROR F1630 BTS DBPA PC NO REPLY FREE QUEUE ERROR F1640 BTS DBPA PC WRITE FRAME FAIL F1650 BTS DBPA PC NO GEN PAGE FREE QUEUE ERROR F1700 BTS BUDA CHIPx16 FAULT F1710 BTS BUDA FORWARD SYNC FAULT F1720 BTS BUDA TX SATURATION FAULT F1730 BTS BUDA FRAME ERROR FAULT F2000 BTS BPPA TOD ERROR F2010 BTS BPPA TOD NOT ACTIVE FAULT F3000 BSC PRO
STAREX-IS BSM Manual A0110 (BTS) Generated when temperature in BTS is below the basic level, or sensor and ACU are abnormal Generated when BTS is submerged (BTS) owing to natural disaster and other reasons, or sensor and ACU are abnormal (BTS) Generated right before low temperature, check if heater(Heating PAD) is normal, and upon normal temperature, replace sensor and ACU. A0120 A0130 Upon BTS is submerged owing to natural disaster and other reason, or sensor and ACU are abnormal.
STAREX-IS BSM Manual abnormal abnormal A0320 If normal, DC 27V is abnormal, but it (BTS) is generated when voltage of more than 28.5V is supplied. A0321 Generated when (BTS) voltage is BTS below 24V rectifier (AC- commercial power fail) A0330 (BTS) Generated when AC (220V/60Hz) input power is abnormal Replace rectifier if the status continues upon restart. If it continues while AC is normal, replace rectifier.
STAREX-IS BSM Manual A0420 (BTS) A0421 (BTS) A0430 (BTS) A0431 (BTS) Rectifier #1 Fault Replace rectifier. Rectifier #2 Fault Replace rectifier. Check Aircon #1 fault AirCon operates, and replace that upon non-operation. Check Aircon #2 fault if AirCon operates, and replace that upon non-operation. A0440 (BTS) if Prevent A/C water leakage from its Water leakage affecting BTS operation. Replace sensor and ACU.
STAREX-IS BSM Manual (BTS) A1501 (BTS) other board is abnormal while one LED side of dual BCRA is normal operation/ BCRA HW check Generated when both sides of dual BCRA are abnormal. red or OFF, BCRA non- BCRA HW mounting check or INIT LED red or OFF, BCRA non- operation/ BCRA HW check A1700 Generated when the other side is Upon board deletion, reinstall that, (BTS) abnormal while one side of dual or BSP(UCPA) is normal execution/R.C result. check FAIL LED ON/R.
STAREX-IS BSM Manual (BTS) A1860 (BTS) deleted. and mount that if removed. Generated when CPU or FPGA Fail occurs in RCMD board. Check the following as to RCMD.( check FAIL LED ON/R.C execution/R.C result) A2000 Generated when one side of dual PRI Check power and replace that if (BTS) boards of BSPB, BANB is abnormal. A2001 Generated when both sides of dual (BTS) PRI boards of BSPB, BANB are abnormal. abnormal. Check power and replace that if abnormal.
STAREX-IS BSM Manual - shunt port open - Aging Fail : Backboard shunt open (enable)/Short(disable). A2400 (BTS) Generated +27V status is abnormal. A2410 (BTS) PWR_FAIL : Check up+27V status supplied from BUS BAR. - MS_OPEN MS_OPEN, MAT_OPEN, : check MS status. - MAT_OPEN : DPDT_OPEN or CTL_OPEN(BDCD) check BRMD status. DC power (27V, +/-12V, 5V) or - DPDT_OPEN: Reset check DPDT status. - CTL_OPEN : A2420 (BTS) check BDCD status.
STAREX-IS BSM Manual (BTS) - PLL LOCK Fail : TTL High - PLL Lock Fail : RISA status check or board replacement A2491 (BTS) Power - Power Fail : TTL High +12V, -12V, +5V, -5V Power Short : H/W replacement and repair A2500 LPA reportsd the status of insertion Check if LPA is normally installed in (BTS) and deletion to combiner. combiner. A2510 (BTS) DC Power off, or switch off, or Major alarm and Disable, or H/W reset. A2520 (BTS) A2530 (BTS) Combiner DC power off or Combiner H/W reset.
STAREX-IS BSM Manual (BTS) End or detect the status of supplied voltage and RF device, and composite them for provision at TTL Active High upon fail with one pin. A2700 Reports (BTS) insertion/deletion. A2710 (BTS) the status of HPA HPA DC power off or power failure. Check if HPA cable is normal. Check if HPA DC power is normally supplied. A2720 (BTS) A2730 (BTS) A2740 (BTS) A2750 (BTS) A lot of RF power reflected on HPA output port.
STAREX-IS BSM Manual ALP(UCPA) is normal.( Board execution/R.C result. deletion, CPU or FPGA Fail) A5511 A5550 Generated when both sides of dual Reinstall board upon deletion, or ALP(UCPA) are abnormal. ( Board check FAIL LED deletion, CPU or FPGA Fail) execution/R.C result. ON/R.C Generated when the other side is abnormal while one side of dual - check ALMA HW status. ALMA - INIT LED red or OFF, ALMA CPU is fail, normal.
STAREX-IS BSM Manual deletion, CPU or FPGA Fail) execution/R.C result. A5720 Generated when SLMA is abnormal. (BSC) (board deletion, CPU fail, SW reset, HW reset, remote reset, power failure) A5730 Generated when VCMA is (BSC) abnormal. (board deletion, CPU fail, SW reset, HW reset, remote reset, power failure) A5800 Generated when CCP fails to receive (BSC) 1pps Clock from GPS-D, or the received clock is wrong.
STAREX-IS BSM Manual A6221 Generated when both sides of dual (BSC) ASIA are abnormal. (board deletion, CPU fail, SW reset, HW reset, remote reset, power failure) A6260 (BSC) - check ASIA HW status. - INIT LED red or OFF, ASIA HW check Check ATSA Slot, and if normal, ATSA Board deletion check BackBoard Pin, and if abnormal, replace the board.
STAREX-IS BSM Manual generating watchdog, and Fault - Function Fail continuously occurs. address/bus error occurs owing to SLPA Application malfunction, and hardware is reset A6500 (BSC) Check VCPA Slot, and if normal, VCPA Board deletion check BackBoard Pin, and if abnormal, replace the board.
STAREX-IS BSM Manual (BSC) Shelf is removed. and if fault occurs despite its connection, replace ABID BOARD. A6611 (BSC) Generated when ABID Board of ASMB Shelf is removed. and if fault occurs despite its connection, replace ABID BOARD. A6620 (BSC) Check the status of ABID BOARD, Check the status of SAID BOARD, SAID Board of SLB Shelf is removed. and if fault occurs despite its connection, replace SAID BOARD.
STAREX-IS BSM Manual FRAME) A7500 Generated when GPS-R Control Check (CAN) Cable is open A7600 Alarm cable connected to CAMB, (CAN) CPNB, PCFB is open or other fault Cable, and if abnormal, replace that. occurs A7800 (CAN) BackBoard Check cable status, and if normal, replace cable. Check FAN power status and alarm CAN Rack FAN failure. cable status, and if normal, replace FAN or Cable. A8000 (CAN) As Generated when the other side is abnormal while one side of dual GPS-R is normal.
STAREX-IS BSM Manual (CAN) CNP(UCPA) are abnormal. ( Board board or if not, check FAIL LED deletion, CPU or FPGA Fail) ON/R.C execution /R.C result. A8550 Generated when the other side is (CAN) abnormal while one side of dual - check ASCA HW status ASCA is normal.
STAREX-IS BSM Manual Ethernet is abnormal. be taken. A8710 Generated when the other side is (CAN) abnormal while one side of dual PCP(UCPA) is normal.( Board deletion, CPU or FPGA Fail) Upon board deletion, reinstall that, or check FAIL LED ON/R.C execution/R.C result. A8711 Generated when both sides of dual Upon board deletion, reinstall that, (CAN) PCP(UCPA) are abnormal.
STAREX-IS BSM Manual between FERA and FETA of the replace FERA, FETA. other side. A8840 (CAN) Failure in link between FETA and PDSN Check the link between FETA and PDSN, and if normally connected, replace FETA. A9000 One side failure of dual PRI board of Check up power and replace that if (CAN) CAMB. abnormal. A9001 Both side failure of dual PRI board of Check up power and replace that if (CAN) CAMB. abnormal.
STAREX-IS BSM Manual (CAN) abnormal. (board deletion, CPU fail, SW reset, HW reset, remote reset, - INIT LED red or OFF, ASIA HW check power failure) A9240 (CAN) AOTA Board deletion Check AOTA HW status. A9250 In-CAMB AOTA Board CPU fail, SW (CAN) reset, HW reset, remote reset, power failure, etc. A9260 (CAN) INIT LED red or OFF, AOTA nonoperation/ AOTA HW check Check ATSA Slot, and if normal, In-CAMB ATSA Board deletion check BackBoard Pin, and if normal, replace the board.
STAREX-IS BSM Manual FAULT F1000 Description Generated response when after there Measures is Processor no Check Network Link, and if Keep abnormal, check Network Card. Alive, and link is blocked or there is actual problem in processor. F1110 Tx Parity Fault in CDMA Data 1. Check BUDA contact Combine Module. F1170 over RCP 2. Switch 3. Replace BUDA Channel Configuration info receipt Check BSP and network between failure. BSP/RCP, and if normal, switch over or reset RCP.
STAREX-IS BSM Manual F1510 Generated when there is no queue Reset Channel Card. resource to store message to be sent to BSP. F1600 When there is no Encoder Queue Reset Channel Card. resource. F1610 No queue resource to store page Reset Channel Card. message except for General Page message. F1620 No queue message to generate and Reset Channel Card. store Quick Page message. F1630 No queue resource to store Reply Reset Channel Card. Message when reply is required regarding message from BSP.
STAREX-IS BSM Manual and replace that if necessary. F3050 If call is not connected in the course Check PLD Data and modify wrong of call processing, this cause is DATA. displayed. Check Parameter DATA error cause and value and request the person in charge to take measures. F4000 Generated when there is no Check Network Link, and if there is response after keeping alive the any error, check Network Card..
STAREX-IS BSM Manual 7.2. Status Message Description and LIST Status Definition and LIST Table 7.
STAREX-IS BSM Manual S3211 AMP GPSR Status Change Displayed upon device status change Display S3220 NCP ASIA Status Change Display Displayed upon device status change S3221 NCP ASCA Status Change Displayed upon device status change Display S3222 NCP ATSA Status Change Displayed upon device status change ALMA Status Change Displayed upon device status change Display S3224 ALP Display S3230 BSP GPS Status Change Display Displayed upon device status change S3501 CCP Overload State Change Dis
STAREX-IS BSM Manual NOR_S Normal Standby Normal Standby (dual node) ABN_D Abnormal Deletion Card deltion ABN_F Abnormal Fault Local Fault ABN_M Abnormal MMC Block Abnormal MMC block Despite being equipped in PLD, processor in INIT Initial charge of corresponding device malfunctions from the start to the present. AB_OB Abnormal Online Block N_EQP Not Equipped Device blocked as normal call is impossible diw to other device fault Card type is not defined in PLD Table 7.
STAREX-IS BSM Manual ABN_F Abnormal Fault (Test: As a result of DSP Chip Hardware test, NOK) ABN_M Abnormal MMC Block INIT Initial AB_OB Abnormal Online Block IDLE Idle (CE, VCE) BUSY Busy (CE, VCE) N_EQP Not Equipped in PLD READY Device mounted although not defined in PLD UNDEF Undefined status ABN_I H/W Reset isolation ABN_B On-demand BER Test status NOR_PB Status until call is disconnected if there is a call when blocking CHC, Chip, Status until call is terminated for vocoder test
STAREX-IS BSM Manual 7.3.1.1.1. Input asf [all/off] : If a factor is not set in asf command, or as a factor, all is set, it can trace all messages from BSM. It can stop Tx message trace set to asf off command. asf sigid [dstaddr] : It can be used to trace only Tx message to specific IP or specific signal ID value without tracing all messages.
STAREX-IS BSM Manual Message Tx time => ASF(qid:5101) at Fri Feb Msg_flag [0xF634] 2 10:40:25 2001 Msg_len [0028] Message length Src_IP [0x1DC00001] Src_TID [000682] Remain_conn [FALSE ] Dest_IP [0x11400101] Dest_TID [000000] Sig_id Dest(target) IP & Task ID [0x0A66] signal ID Remain_time [00 sec] Src(BSM) IP and Task ID 7.3.1.2. arf Command 7.3.1.2.1. Input arf [all/off] : This can trace all messages received to BSM if a factor is not set in arf command, or all is set as factor.
STAREX-IS BSM Manual Info on App to receive message Message Rx time => ARF[0x0A65](qid:5105/pid:670) at Fri Feb Msg_flag Src_IP [0xF634] 2 10:40:25 2001 Msg_len [0225] [0x11400201] Message length Dest_IP [0x1DC00001] Dest_TID [000000] IP & Dest(BSM) Src_TID [000074] Task ID Remain_conn [FALSE ] Sig_id [0x0A65] Signal ID Remain_time [00 sec] Src(Target) IP & Task ID SMD-011-PMA210 Page:772(877) Issue:1.
STAREX-IS BSM Manual 7.3.2. Function to test Function This function includes sis and ipclog console command. sis command is to send IPC signal message for test to message queue, and ipclog command is to send test message to monitor the status of slave processor. 7.3.2.1. sis Command 7.3.2.1.1.
STAREX-IS BSM Manual COMPLETED! (sis) ERROR! sending IPC message... (sis) 7.3.2.2. ipclog Command 7.3.2.2.1. Input Enter ipclog in DCI console to display a window for ping test on target. To adjust $DISPLAY environmental variable, use display command(see 5.5). Figure 7.3-1 IP Input Request Window in DCI Window Factors to enter are as follows: Target IP?(HEX or DOTTED-DECIMAL) 11400201 IP address of target to send test message Target=17.64.2.
STAREX-IS BSM Manual 7.3.2.2.2. Output The result of test message sending is as follows: ### RESULT ### ==================================== TargetIP SEND RECV CORRUPT -----------------------------------11400201 0020 0016 0001 ==================================== message number with broken contents message number with test message received target address sent number of messasges sent 7.3.3. Status Display Funciton This function includes ipcs, isig, status, rsock, ssock, etc.
STAREX-IS BSM Manual ### IPC Status Information ### TX Errors RX Errors txerr_msgq: 000000 rxerr_msgq: 000000 txerr_leng: 000000 rxerr_leng: 000000 txerr_sock: 000028 rxerr_sock: 000000 message Tx related message Rx rxerr_udst: 000032 related accumulated accumulated--------------------------------------------------- error number error number QKEY QID CBYTES QNUM FLUSH RLOST --------------------------------------------------0200 00000800 00000000 000000 000000 000000 0201 00000001
STAREX-IS BSM Manual queue key ### Initial Signal ID Information ### [#2561] SID(0x0A01) / QKey(0x020D) / PID(00779) signal ID [#2562] SID(0x0A02) / QKey(0x020D) / PID(00779) application to receive corresponding signal [#2563] SID(0x0A03) / QKey(0x020D) / PID(00779) [#2573] SID(0x0A0D) / QKey(0x020D) / PID(00779) process id [#2656] SID(0x0A60) / QKey(0x0205) / PID(00787) … … … … [#2690] SID(0x0A82) / QKey(0x0207) / PID(00792) [#2691] SID(0x0A83) / QKey(0x0208) / PID(00798) [#2705] SID(0x0A91) / QK
STAREX-IS BSM Manual 7.3.3.4.1. input Withput factor, rsock should be input. 7.3.3.4.2. Output The output of rsock command is reported in the following format. ### RECEIVE SOCKET TABLE ### [0] FD[4] IP[11400201] READY[0] CREAT[02-26 12:06:11] [1] FD[6] IP[12400501] READY[1] CREAT[02-26 11:03:23] [2] FD[7] IP[11400101] READY[0] CREAT[02-26 11:22:13] … socket target receipt message descriptor IP address connection creation time waiting status 7.3.3.5. ssock command 7.3.3.5.1.
STAREX-IS BSM Manual 7.3.4. Other Supplementary Function ls command can display available command list in window. log command is used to switch on and off the function to store event generated from DCI console and DCI in log file, and eprt command is used to switch on and off the function to display error generated from DCI in window. History related command is used for convenience in the case of repeatedly executing the previous command in DCI console.
STAREX-IS BSM Manual DCI_CON>> history ### Command History ### 9 : 8 : ls 7 : asf a01 6 : arf a03 11400101 5 : arf off 4 : rsock 3 : ipclog 2 : isig 1 : status 0 : ls DCI_CON>> !2 isig ### Initial Signal ID Information ### [#2690] SID(0x0A82) / QKey(0x0207) / PID(00792) [#2691] SID(0x0A83) / QKey(0x0208) / PID(00798) … 7.3.4.5. display command By display command, you can change the address to display ipclog window.
STAREX-IS BSM Manual 7.4. Statistic Message 7.4.1. Traffic Related 7.4.1.1. Traffic Statistics by Service Option 7.4.1.1.1. SERVICE OPTION Table 7.4-1 IS-2000 Service Option Type VOICE Basic Variable Rate (8K Voice) VARI_VOICE Enhanced Variable Rate (8K Voice) ASYNC Asyncronous Data (9.6 Kbps) : To provide Dial Up MODEM function, it provides AT command, and subscriber can use this for end-to-end communication or access public data network. G3FAX Group 3 Facsimile (9.
STAREX-IS BSM Manual 7.4.1.1.2. ORIGINATION Table 7.
STAREX-IS BSM Manual 7.4.1.1.3. TERMINATION Table 7.
STAREX-IS BSM Manual SEL_UNA No selector available 7.4.2. Handoff Statistic Function 7.4.2.1. Handoff Statistic Type Table 7.
STAREX-IS BSM Manual INTER_CCP_TO OTHER_FAIL Timeout between Source CCP and Target CCP Fail other than #2 ~ 14 7.4.3. Call Related Statistic Function 7.4.3.1. Channel Element Statistics Table 7.
STAREX-IS BSM Manual 7.4.3.3. Network Link Statistics 7.4.3.3.1. (ALPA,LICA,ASCA,ASIA) Table 7.4-8 ATM Network Statistics (LINK/PORT statistics) ITEM DESCRIPTION Rx_cnt Cell Counter received from Link Tx_cnt Cell Counter sent from Link 7.4.3.3.2. BSC-MSC Trunk Statistics Table 7.
STAREX-IS BSM Manual 7.4.3.5. Processor Statistics Table 7.4-11 Processor Statistic Item ITEM DESCRIPTION CPU Load : xx.xx * 100 CPU_IDLE SEND_IPC_NUM Total IPC Send Number RECEIVE_IPC_NUM Total IPC Receive Number SEND_AVERAGE_LENGTH Average Send IPC Length RECEIVE_AVERGAE_LENGTH Average Receive IPC Length 7.4.3.6. Selector Statistics Table 7.
STAREX-IS BSM Manual ms_1000 ms_1100_over Under 1100ms, origination call setup count Over 1100ms, origination call setup count s_3_under Under 3SEC, termination call setup count s_3 Under 4SEC, termination call setup count s_40 Under 4.
STAREX-IS BSM Manual order Count of having sent various messages to MS through paging channel ch_asign Count of having sent information of forward call channel to MS data_burst Count of having sent data BURST message ser_redir Count of having sent Service Redirection message 7.4.3.10. NO.7Statistics Table 7.4-16 NO7 Statistic Item ITEM Description MTP related SL_NO Signaling Link Number LOSS MSG Missed MSU count ERR_MSG number of Signal Unit in error NACK_NO number of negative ack.
STAREX-IS BSM Manual 1.2 K 1.0 ~ 1.2 Km 1.4 K 1.2 ~ 1.4 Km 1.6 K 1.4 ~ 1.6 Km 1.8 K 1.6 ~ 1.8 Km 2.0 K 1.8 ~ 2.0 Km 2.5 K 2.0 ~ 2.5 Km 3.0 K 2.5 ~ 3.0 Km 3.5 K 3.0 ~ 3.5 Km 4.0 K 3.5 ~ 4.0 Km 5.0 K 4.0 ~ 5.0 Km 6.0 K 5.0 ~ 6.0 Km 7.0 K 6.0 ~ 7.0 Km 8.0 K 7.0 ~ 8.0 Km 9.0 K 8.0 ~ 9.0 Km 10.0K 9.0 ~ 10.0 Km OVER_10K 10.0 Km or above 7.4.3.12. RF MIN/MAX Statistics Table 7.
STAREX-IS BSM Manual TOTAL_SDB_FORWARD_Byte TOTAL_SDB_REVERSE_KByte Total bytes of SDB from MS to PDSN in dormant state TOTAL_SDB_REVERSE_Byte TOTAL_ACT_FORWARD_KByte Total bytes of packet from PDSN to SLP in active state TOTAL_ACT_FORWARD_Byte TOTAL_ACT_REVERSE_KByte Total bytes of packet from SLP to PDSN in active state TOTAL_ACT_REVERSE_Byte 7.4.4.2. Packet Control Table 7.
STAREX-IS BSM Manual ITEM Dormant_HO_Cnt DESCRIPTION Dormant HO count Serving_PCF_HO_Cnt Serving PCF HO count Target_PCF_HO_Cnt Target PCF HO count HO_FAIL_CNT SMD-011-PMA210 HO failure count Page:792(877) Issue:1.
STAREX-IS BSM Manual 7.5. PLD Data Structure 7.5.1. BSM layer 7.5.1.1. St_Bsm_Cfg.dg Table 7.5-1 St_Bsm_Cfg Data Type N a m e default byte ccp_id 0 ~ 12 byte bts_eqp[MAX_BTS] Remarks Current BTS equip ( 0: Not_equip byte smp_eqp[MAX_SMP] 1 : Equip ) Current SMP equip ( 0: Not_equip byte vmp_eqp[MAX_VMP] byte msc_id 0 ~ 255 MSC Identification byte pcf_equ[MAX_PCF] 0 ~ 255 CAN PCF equip (0:Not_equip 1 : Equip ) 1 : Equip) MAX_PCF : 3 ccp_id=0 is only valid.
STAREX-IS BSM Manual 12(2), LINK_TYPE_STM14(3), LINK_TYPE_E1(4), LINK_TYPE_T1(5)) byte link_status 1 ATM Link Acktivity Init/Active/Block (LINK_STS_NONE(0), LINK_STS_ACTIVE(1), LINK_STS_ONL_BLOCK(2), LINK_STS_MMC_BLOCK(3)) byte connect_type Node Connection ID: End-User’s own ID (see Appendix Connection ID) byte fabric_no Switch Fabric No.
STAREX-IS BSM Manual byte equipage[4096] byte node_a[4096] Peer1 connection ID byte sub_a[4096] Peer1 Logical Info byte node_b[4096] Peer2 Connection ID byte sub_b[4096] Peer2 Logical info byte no_vc[4096] Number of VC to be used between Allocated VC Number Peers byte link_type[4096] Link Usage AAL1/2/5, Test (LINK_AAL2(0), LINK_AAL5(1), LINK_TEST(2)) word16 link_bw[4096] 0x100 VC Link Bandwidth (Cell Bandwidth(~0x40) to be assigned to Link) word32 vpci_a[4096] Peer1 VPI/VCI(Ingre
STAREX-IS BSM Manual ( LINK_AAL2(0), LINK_AAL5(1), LINK_TEST(2)) word16 link_bw[512] VC Link BandWidth (Cell Bandwidth(~0x40) to be assigned to Link) 7.5.2.5. St_re_can_net_cfg.dg Table 7.
STAREX-IS BSM Manual byte no_addr_hdr ATM Address Header Len byte reserved[2] byte rnc_equip[MAX_RNC] byte atm_addr_hdr[20] ATM Address Header byte rnc_conn_type[MAX_RNC] RNC Connectino ID byte atsa_conn_type[12] ATSA Connection ID word32 rnc_addr[MAX_RNC] RNC NCP Network Address word32 camu_addr[16] CAMU Device Network Addr.
STAREX-IS BSM Manual 7.5.3. PNP ONLY 7.5.3.1. St_re_cand_node.dg Table 7.
STAREX-IS BSM Manual byte link_id key byte equip Number byte link_type full equip (MAX_SUB_LINK:32) of Equip as below pcf LINK_NOT_EQUIP(0), LINK_EQUIP(1) 1 ATM Link Type STM-1,STM-4,Cell Bus LINK_TYPE_NONE(0), LINK_TYPE_STM1(1), LINK_TYPE_STM12(2), LINK_TYPE_STM14(3), LINK_TYPE_E1(4), LINK_TYPE_T1(5) byte link_status 1 ATM Link Acktivity Init/Active/Block LINK_STS_NONE(0), LINK_STS_ACTIVE(1), LINK_STS_ONL_BLOCK(2), LINK_STS_MMC_BLOCK(3) byte byte connect_type fabric_no Default 1
STAREX-IS BSM Manual 7.5.3.4. St_re_cand_pvc.dg Table 7.5-13 St_re_cand_pvc Type N a m e default byte dummy key word16 no_entry Remarks # of Valid Entries, number of defined PVC information (~4096) word16 reserved byte equipage[4096] byte node_a[4096] Peer1 connection ID byte sub_a[4096] Peer1 Logical Info byte node_b[4096] Peer2 Connection ID byte sub_b[4096] Peer2 Logical info byte no_vc[4096] Number of VX to be used between Allocated cand_pvc.
STAREX-IS BSM Manual byte node_b[512] Peer2 Connection ID byte sub_b[512] Peer2 Logical info byte no_vc[512] Number of VCs to be used between Allocated VC Number Peers byte link_type[512] Link Usage AAL1/2/5, Test LINK_AAL2(0), LINK_AAL5(1), LINK_TEST(2) word16 link_bw[512] 0x100 Cell Bandwidth(~0x40) to be assigned to VC Link Bandwidth-Link word32 vpci_a[512] Peer1 VPI/VCI(Ingress VPCI) word32 vpci_b[512] Peer2 VPI/VCI(Egress VPCI) 7.5.3.6. St_re_cand_svc.dg Table 7.
STAREX-IS BSM Manual Link) 7.5.3.7. St_re_cand_net_cfg.dg Table 7.5-16 St_re_cand_net_cfg Type N a m e default Remarks byte can_net_shelf_id key full equip (MAX_CAN_NET_SHELF: 2) byte can_net_slot_id key full equip (MAX_CAN_SLOT: 22) byte equip ‘0’ byte bd_type Network Board Type byte no_sub # of Sub Device byte no_link # of Physical Link byte hw_ctrl HW Reset byte link_type[MAX_LIN 1 : 0(Init), 1, 2, 3 added Physical Link Type : STM1, E1,...
STAREX-IS BSM Manual rnc equip byte pcf_conn_type[6][2] PCF Connectino ID byte rnc_conn_type[MAX_RNC] RNC Connection ID word32 pcp_addr[6] word32 ncp_addr[MAX_RNC] RNC NCP Network Address word32 camdu_addr[16] CAMD Device Network Addr. (0 : ASCA_A, 1 : ASCA_B, 2 : ASIA0_A, 3 : ASIA0_B, 4 : ASIA1_A, 5 : ASIA1_B 6 : ASIA2_A, 7 : ASIA2_B, 8 : ASIA3_A, 9 : ASIA3_B, 10 : AOTA0, 11 : AOTA1, 12 : AOTA2, 13 : AOTA3, 14 : ATSA0, 15 : ATSA1) 7.5.3.9. St_re_cand_data5_con.dg Table 7.
STAREX-IS BSM Manual 7.5.4. PCP ONLY 7.5.4.1. St_pdsn_addr_data_type Table 7.5-20 St_pdsn_addr_data_type Type Name byte dummy byte no_of_pdsn default Remarks 1 Number of equipped PDSN. Of MAX_PDSN_NO, the number of correct PDSN should be checked. word32 pdsn_ip[MAX_PDSN_NO] PDSN IP MAX_PDSN_NO = 2 (temporal) IP used by PDSN for Public Networkinterface. Home Agent IP. As several PDSNs can be interfaced, extendibility is considered.
STAREX-IS BSM Manual Type Name byte dummy word16 Trp_lifetime default Remarks 1800 PCF timer. Range : 0 ~ 65,535 unit : 60sec 0x0000 = Release 0xFFFF = Infinite word16 Tbsreq9 5000 PCF timer. Range : 0 ~ 5000 Unit : 1msec word16 Tdiscon9 5000 PCF timer. Range : 0 ~ 5000 unit : 1msec word16 Twaitho9 10000 PCF timer. Range Unit word16 Tregreq 5000 : 0 ~ 10000 : 1msec PCF timer.
STAREX-IS BSM Manual 1 : Nonce word32 pcp_ip[MAX_PCF_SH PCP IP, MAX_PCF_SHELF = 2 ELF][MAX_PCP_NO] PMP IP MAX_PCP_NO = 2 PCP/PMP IP executing F/E interface. [0][0] : PCP (Active) [0][1] : PCP (Standby) [1][0] : PMP (Active) [1][1] : PMP (Standby) word32 pip_ip[MAX_PCF_SH PIP IPs ELF][MAX_PIP_NO] MAX_PCF_SHELF = 2 MAX_PIP_NO = 11 PIP IP executing F/E interface. word32 net_mask[MAX_PCF_ 0 SHELF][MAX_PIP_NO To be judged. PLD add.
STAREX-IS BSM Manual byte byte pkt_zone_id 0 UDR_MSID_TYPE 0 MSID Type in UDR that PDSN sends to AAA Server 1 : IMSI 0 : MIN byte reserved[32] 0 7.5.4.4. St_pifu_HW_Reset_data_type Table 7.5-23 St_pifu_HW_Reset_data_type Type Name default Remarks byte shelf_id 0~1 key byte pcp_isolation[11] 0 0: not isolation 1:isolation byte bcra_isolation[2] 0 0: not isolation 1:isolation byte fera_isolation[2] 0,1 0: not isolation.................................................
STAREX-IS BSM Manual mode. (0 ~ 100) byte fast_down_delta 1 Gain down delta. Applied during gast down mode. (0 ~ 100) byte nominal_gain 50 Nominal tx gain of primary/secondary traffic. (0 ~ 127) byte max_tx_gain 80 Max.tx gain of primary/secondary traffic byte min_tx_gain 40 Min.tx gain of primary/secondary traffic. byte fer_threshold 6 % Frame Error Rate threshold determines the gain increase amount.(0 ~ 20) byte big_up_delta 10 Gain increase delta.
STAREX-IS BSM Manual word16 state_chg_thresh 250 Number of consecutive good frames brings about good run state.(0 ~ 10000) word16 erase_meas_frames 250 Cumulative erasure measuring period.(0 ~ 65535) byte cont_erase_eftv 2 Number of consecutive erasures brings about tx gain increase. If 0, burst erasures have no effect.(0 ~ 127) byte cumul_erase_eftv 4 Number of cumulative erasures brings about tx gain increase. If 0, non-burst erasures have no effect.
STAREX-IS BSM Manual Type N a m e defaul Remarks t byte bts_id full byte fer_id 0 ~ 1 word16 pnom (pwrctl_nominal) 19416 initial Eb/No(dB) word16 pmax (pwrctl_max ) 23408 Maximum Eb/No(dB) word16 pmin (pwrctl_min)) 8288 Minimum Eb/No(dB) word16 pupf (pwrctl_up_full) 3072 Up for erase in full mode(dB) short pfrr (pwrctl_full_run_reset) -2 Fulls until full mode(count value) word16 pupe (pwrctl_up_erasure) 248 Up for erase in erase run(dB) word16 pupel(pwrctl_up_erasure_little
STAREX-IS BSM Manual word16 rpc_small_up_delta 2304 Pwrctl threshold up delta. Applied when a pwrctl-threshold-up condition is encountered during GOOD-STATE. byte rpc_non_erase_wait 2 Non-erasure rate waiting frame count after increasing pwrctl threshold. During the period, erasure rate frame has no effect. byte rpc_max_down_delta 48 Maximum pwrctl threshold down delta. byte rpc_min_down-delta 2 Minimum pwrctl threshold down delta.
STAREX-IS BSM Manual Type N a m e default Remarks BYTE VMP_ID full 0 ~ 7 VMP IDENTIFICATION BYTE VCP_ID full 0 ~ 15 VCP IDENTIFICATION BYTE SHELF_TYPE 0 0: PHASE1 BYTE VCP_STS 0 BYTE VCP_SLAVE_STS[2] 0 0: UNBLOCK 8: BLOCK BYTE VCE_STS[8] 0 0: UNBLOCK 8: BLOCK byte reserved_byte[34] 0 1: PHASE2 0: UNBLOCK 8: BLOCK 7.5.5.7. St_Trunk_data_type Table 7.
STAREX-IS BSM Manual byte sbp_no 0 ~ 14 byte svc_no 0 ~ 15 byte vce_no 0 ~ 7 word cic byte dummy byte sbp number of vocoder channel that is matched to each time slot svc number of vocoder channel matched to each time slot vocoder channel number matched to each time slot Number matched to all time slots, that is, each time slot’s own number. reserved_byt e[34] 0 7.5.5.9. St_Bsc_data_type Table 7.
STAREX-IS BSM Manual Type N a m e default byte Dummy 0 Remarks byte voice_8k 1 Basic Variable Rate (8K Voice) byte loopback_8k 1 8K Loopback : IS-126 byte evrc 1 Enhanced Variable Rate Code Asycronous Data(9.6 Kbps) : Provides Dial Up byte async 1 Modem function and AT command, and subscriber uses this for end-to-end communication or accesses public data network. Group 3 Facsimile(9.
STAREX-IS BSM Manual byte wll_offhook 1 byte rs1_markov 1 rate set 1 Markov Call byte rs2_markov 1 rate set 2 Markov Call byte fch_fer 1 byte sch_fer 1 byte dcch_fer 1 byte Sch_loopback 0 byte Sch_loopback2 0 byte Reserved_byte[ 31] RC3 data service (0~31) RC3 data service (0~31) RC3 data service (0~31) 0 7.5.5.11. St_MAHHO_data_type Table 7.
STAREX-IS BSM Manual If total Ec/Io value is lower than total threshold regarding serving frequency, it does not search the pilot of Candidate Frequency. As power difference threshold between received serving frequency byte diff_rx_pwr_thresh 0 and candidate determines frequency, whether to this search candidate frequency. byte min_total_pilot_ec_io 0 Ec/Io threshold of active set of candidate frequency Threshod to add pilot to acticve set of candidate frequency.
STAREX-IS BSM Manual Type N a m e default byte bts_id full byte sector_id full Remarks After byte set Action time, frame duration until first PUF probe. action_time_frame unit Before PUF pulse transfer, duration sent with nominal power power control group unit. byte puf_setup_size byte puf_pulse_size word16 puf_interval Interval between PUF Probes. frame unit byte puf_init_pwr Initial PUF Probe power. in units of dB byte puf_pwr_step PUF pulse power increase.
STAREX-IS BSM Manual FFCOLS). 0.125dB unit byte fpc_fch_min_setpt byte fpc_fch_max_setpt Minimum value of FFCOLS. 0.125dB unit FFCOLS’s Maximum value. 0.125dB unit Forward Dedicated Control Channel byte fpc_dcch_init_setpt Outer Loop (hereinafter Eb/Nt setpoint FDCCOLS) initial value. 0.125dB byte fpc_dcch_min_setpt FDCCOLS’s Minimum value. 0.125dB byte fpc_dcch_max_setpt FDCCOLS’s Maximum value. 0.
STAREX-IS BSM Manual Attribute Adjustment gain value. byte rl_att_adj_gain_2700[2] byte rl_att_adj_gain_4800[2] byte rl_att_adj_gain_9600[2] byte rl_att_adj_gain_1800[2] byte rl_att_adj_gain_3600[2] byte rl_att_adj_gain_7200[2] byte rl_att_adj_gain_14400[2] byte norm_att_gain_9600_5ms[2] 20ms frame, 2700bps Reverse Link Attribute Adjustment gain value. 20ms frame, 4800bps Reverse Link Attribute Adjustment gain value. 20ms frame, 9600bps Reverse Link Attribute Adjustment gain value.
STAREX-IS BSM Manual Attribute Adjustment gain byte rl_att_adj_gain_230400[2][2] byte rl_att_adj_gain_460800[2][2] byte rl_att_adj_gain_1036800[2][2] byte fpc_subchan_gain byte rl_gain_adj byte rlgain_traffic_pilot byte rlgain_sch_pilot byte reserved_byte[33] 20ms frame, 230400bps Reverse Link Attribute Adjustment gain 20ms frame, 460800bps Reverse Link Attribute Adjustment gain 20ms frame, 1036800bps Reverse Link Attribute Adjustment gain 0 7.5.5.14. St_sch_param_data Table 7.
STAREX-IS BSM Manual Active Set order changes. As threshold necessary so that MS judges PSMMM transfer, this is necessary upon such mode as MS sending PSMMM whenever the order of active set changes. byte order_interval Interval to report the difference between two pilot strengths through PSMMM. in units of 20ms byte num_pilots Parameter necessary for MS to send PSMMM. Pilot number reported through PSMMM byte periodic_interval Interval that MS sends PSMMM.
STAREX-IS BSM Manual byte T5 60 (0~255) Facilities Management(sec) byte T6 75 (0~255) Facilities Management(sec) byte T7 10 (0~255) Handoff(sec) byte T9 10 (0~255) Handoff(sec) byte T10 5 (0~99) Handoff(sec) byte T12 60 (0~255) Facilities Management(sec) byte T13 55 (0~255) Facilities Management(sec) byte T16 60 (0~255) Facilities Management(sec) byte T20 5 (0~99) Call Processing(sec) byte T30 5 (0~99) Call Processing(sec) byte T40 5 (0~99) Call Processing(sec) b
STAREX-IS BSM Manual byte T790 10 (0~60) Handoff (sec) byte T3113 5 (0~99) Call Processing (sec) byte T3210 30 (0~99) Mobility Management (sec) byte T3220 10 (0~99) Mobility Management (sec) byte T3230 5 (0~99) Call Processing (sec) byte T3240 5 (0~99) Mobility Management (sec) byte T3260 30 (0~99) Mobility Management (sec) byte T3270 5 (0~99) Mobility Management (sec) byte T3271 15 (0~99) Mobility Management (sec) byte T3272 5 (0~99) Mobility Management (sec) byte
STAREX-IS BSM Manual Byte EquipPage According to 0: Not Equip 1: Equip Equip status Byte VMP_Isolation 0 0: not_isolation 1: isolation Byte VCP_Isolation[16] 0 0: not_isolation 1: isolation Byte VLIA_Isolation[2] 0 0: not_isolation 1: isolation Byte reserved_byte[34] 0 7.5.5.17. St_Slbu_HW_Reset_data_type Table 7.
STAREX-IS BSM Manual LINK_STS_ONL_BLOCK(2), LINK_STS_MMC_BLOCK(3) byte connect_type End-User’s own ID connected to Link(see Appendix Connection ID) byte fabric_no Fabric is a serial number of APC. Index(0~8) of total APCs 0 : ASCA APC0, 1 : ASIA0 APC0, 2 : ASIA0 APC1, 3 : ASIA1 APC0, 4 : ASIA1 APC1, 5 : ASIA2 APC0, 6 : ASIA2 APC1, 7 : ASIA3 APC0, 8 : ASIA3 APC1 byte reserved[7] 7.5.6.2. St_re_slb_node.dg Table 7.
STAREX-IS BSM Manual Type N a m e Default Remarks byte vmp_id Key full equip MAX_VCB:8 byte link_id key full equip (MAX_SUB_LINK:32) byte equip Vmp As many as Node Config below, Equip 1: Equip, number 0:Not-Equip 1 STM-1, STM-4, Cell Bus byte link_type (LINK_TYPE_NONE(0),LINK_TYPE_STM1(1),LINK_TYPE _STM12(2), LINK_TYPE_STM14(3), LINK_TYPE_E1(4), LINK_TYPE_T1(5)) byte link_status 1 Link status LINK_STS_NONE(0), LINK_STS_ACTIVE(1), LINK_STS_ONL_BLOCK(2), LINK_STS_MMC_BLOCK(3) byte
STAREX-IS BSM Manual byte connect_type End-User’s own ID connected to Link (see Appendix Connection ID) byte fabric_no 0 Index(0~8) of total APCs 0 : ALMA APC0 byte reserved[7] 7.5.6.5. St_re_bs_atm_node.dg Table 7.
STAREX-IS BSM Manual byte alpa_id key full equip MAX_ALPA: 5 byte link_id key full equip MAX_ALS_LINK: 16 byte equip BS LINK_NOT_EQUIP(0), LINK_EQUIP(1) dependent byte link_type 1 E1, T1, STM-1 (LINK_TYPE_NONE(0),LINK_TYPE_STM1(1),LINK_TY PE_STM12(2), LINK_TYPE_STM14(3), LINK_TYPE_E1(4), LINK_TYPE_T1(5)) byte link_status 1 LINK_STS_NONE(0), LINK_STS_ACTIVE(1), LINK_STS_ONL_BLOCK(2), LINK_STS_MMC_BLOCK(3) byte bs_id byte alloc_type Link Peer BS/BTS ID 1 PVC Active/PVC Standby/SVC -
STAREX-IS BSM Manual word32 addr[8] Each Processor IP Address 7.5.6.8. St_re_bs_addr.dg St_re_bs_addr Type N a m e default Remarks byte bs_id key full equip MAX_BS: 48 byte shelf_id key full equip (MAX_BS_SHELF: 12) byte slot_id key full equip (MAX_BS_SLOT: 22) byte equip ‘0’ Equit/Not Equip byte bd_type Processor/Device Board Type(TBD) byte no_sub Number of processors mounted byte reserved Not Used word32 addr[8] Each Processor IP Address 7.5.6.9. St_re_atm_pvc.
STAREX-IS BSM Manual (Cell Bandwidth(~0x40) to be assigned to Link) word32 vpci_a[4096] Peer1 VPI/VCI (Ingress VPCI) word32 vpci_b[4096] Peer2 VPI/VCI (Egress VPCI) 7.5.6.10. St_re_slb_pvc.dg Table 7.5-48 St_re_slb_pvc Type N a m e default Remarks byte dummy key word16 no_entry # of Valid Entries, defined PVC information number (~512) word16 reserved byte equipage[512] byte node_a[512] Peer1 connection ID (Ingress Node Conn.
STAREX-IS BSM Manual word16 reserved byte equipage[512] byte node_a[512] Peer1 connection ID (Ingress Node Conn. ID) byte sub_a[512] Peer1 Logical Info (measns final peer connection) byte node_b[512] Peer2 Connection ID (Egress Node Conn.
STAREX-IS BSM Manual word32 vpci_a[512] Peer1 VPI/VCI (Ingress VPCI) word32 vpci_b[512] Peer2 VPI/VCI (Egress VPCI) 7.5.6.13. St_re_loc_bs_pvc.dg Table 7.5-51 St_re_loc_bs_pvc Type N a m e default Remarks byte dummy key word16 no_entry # of Valid Entries, defined PVC information number (~512) word16 reserved byte equipage[512] byte node_a[512] Peer1 connection ID (Ingress Node Conn.
STAREX-IS BSM Manual byte node_a[512] Peer1 connection ID (Ingress Node Conn. ID) byte sub_a[512] Peer1 Logical Info byte node_b[512] Peer2 Connection ID byte sub_b[512] Peer2 Logical info byte no_vc[512] Number of VC to be used between Allocated VC (Egress Node Conn.
STAREX-IS BSM Manual Link BandWidth(TBD,Link) 7.5.6.16. St_re_rnc_net_cfg.dg Table 7.5-54 St_re_rnc_net_cfg Type N a m e default Remarks byte rnc_net_shelf_id key full equip (MAX_RNC_NET_SHELF: 2) byte rnc_net_slot_id key full equip (MAX_RNC_SLOT: 22) byte Equip ‘0’ byte bd_type Network Board Type byte no_sub # of Sub Device byte no_link # of Physical Link byte hw_ctrl HW Reset byte link_type[MAX_LINK] 1 : 0(Init), 1, 2, 3 added Physical Link Type : STM1, E1,...
STAREX-IS BSM Manual byte link_type[MAX_LINK] 1 Physical Link Type : STM1, E1,...(MAX_LINK: 64) (LINK_TYPE_NONE(0),LINK_TYPE_STM1(1), LINK_TYPE_STM12(2),LINK_TYPE_STM14(3), LINK_TYPE_E1(4), LINK_TYPE_T1(5)) byte sub_type[MAX_SUB] Sub Device Type (MAX_SUB : 16) (SBTYPE_NONE(0), SBTYPE_APC(1), SBTYPE_APPD(2)) byte sub_id[MAX_SUB] Sub Device ID:Device Serial Number (MAX_SUB : 16) 7.5.6.18. St_re_rnc_net_data.dg Table 7.
STAREX-IS BSM Manual CBU] byte als_conn_type[4] 5~8 ALSU Connection ID byte pip_conn_type[8] 29~36 PIP Connection ID byte cmp_conn_type 15 CMP connection ID byte reseved[6] word32 ccp_addr CCP IP Address word32 alp_addr ALP IP Address word32 cnp_addr[2] CNP/CNP-D IP Address 0 : CNP Address, 1 : PNP Address word32 smp_addr[MAX_SLBU] word32 asmu_addr[16] SMP IP address (MAX_SLBU : 5) 2 ~ 17 ASMU Device Network Addr (for HDLC) 0: ASCA_A, 1: ASCA_B, 2: ASIA0_A, 3: ASIA0_B, 4: ASIA1_
STAREX-IS BSM Manual word32 AAL2 Start VC Id. aal2_vc_id [MAX_LICA][MAX_LICA_LINK] MAX_LICA : 3, MAX_LICA_LINK : 16 7.5.6.21. St_re_rnc_slb_con.dg Table 7.5-59 St_re_rnc_slb_con Type N a m e default Remarks byte Dummy key word32 start_aal5_vc_id[20] word16 no_aal5_vc word16 Reserved Applied to all SMPs in the same way AAL5 Start VC Id 1024 20VPs Number of AAL5 VCs 20VPs 7.5.6.22. St_re_rnc_vcb_con.dg Table 7.
STAREX-IS BSM Manual Type N a m e default Remarks byte bs_id key full equip MAX_BS : 48 byte msc_id msc_no Core Network ID byte rnc_id rnc_no My RNC ID byte bs_id bs_no My BS ID byte no_addr_hdr ATM Address Header Len byte atm_addr_hdr[20] ATM Address Header byte lica_conn_type[3] byte reserved word32 svc_id 146 147 148 LICA Connection ID [4/37] = BS SSCF-UNI Signalling VC 0x40025 word32 crp_addr CRP IP Address word32 banu_addr[5] BANU Device Network Addr 7.5.6.25.
STAREX-IS BSM Manual Type N a m e default Remarks byte dummy key byte msc_id msc_no MSC ID byte rnc_id rnc_no RNC/BSC ID byte reserved word32 ncp_addr NCP Network Address word32 alsu_addr[16] ALS Device Network Addr 7.5.6.28. St_re_rnc_cmp5_con.dg Table 7.5-66 St_re_rnc_cmp5_con Type N a m e default byte dummy key word32 start_aal5_vc_id [10/32] = Remarks AAL5 Start VC Id. 0xA0020 word16 no_aal5_vc word16 reserved 1024 #of AAL5 VCs 7.5.7. SCP ONLY 7.5.7.1.
STAREX-IS BSM Manual 1 : slc_no[1] 2 : slc_no[2] 3 : slc_no[3] 255 : rest word16 vmp_no[16] 0 : vmp_no[0] 0 : vmp_no[1] 0 : vmp_no[2] 0 : vmp_no[3] 255 : rest word16 trk_no[16] 16:trk_no[0] Signal data link code 48: trk_no[1] 80: trk_no[2] 112: trk_no[3] 0xffff: rest byte reserved_byt 0 e[35] 7.5.7.2. St_Lnit_dataST.dg Table 7.
STAREX-IS BSM Manual Type N a m e default Remarks byte dummy 0 key word16 T1 45000(msec) Timer “alignment ready”(40~50sec) word32 T2 0xffff(msec) Timer “not aligned”(5~150sec) word16 T3 1250(msec) Timer “aligned”(1-2sec) word16 T4n 8000(msec) Normal proving period at 64 kbit/s(7.5~9.
STAREX-IS BSM Manual to next initial alignment command word16 T22 240(sec) Local inhibit test timer3-6 minutes word16 T23 240(sec) Remote inhibit test timer3-6 minutes word16 SLTackT 5(sec) Time to wait for signal link test answer, with range of 4sec~12sec byte reserved[2 0 0] 7.5.7.5. St_SCCP_timer.dg Table 7.
STAREX-IS BSM Manual Type N a m e default Remarks byte bts_id full byte EquipPage Equip dependent 0 : Not Equip word16 Sid 0x08ae As System Identification Number, 0 ~ 1 : Equip 32767(215 -1) word16 Nid 15 As Netword Identification Number, Network is system subset.
STAREX-IS BSM Manual word16 EXT_CDMA_FREQ 525 Upon use of RC3 or more or QPCH, see this field.
STAREX-IS BSM Manual revision, it can increase the number of calls that can be provided. Enable/disable flag of corresponding function. byte reserved_byte[32] 0 7.5.8.3. St_cdmach_data_type.dg Table 7.
STAREX-IS BSM Manual holds ZONE_LIST, and it is a field to determine duration that an entry in ZONE_LIST is removed from list. That is, the loggest entry from ZONE_LIST is the priority. 000(1 min),001(2 min),010(5 min),011(10 min), 100(20 min),101(30 min),110(45 min),111(60 min) As boolean home_reg 1 Home registration ID, to enable auto location registration, set this field to ‘1’, and to disable that, set that to ‘0’.
STAREX-IS BSM Manual boolean parameter_reg 1 Parameter-change registration indicator This is used for the calculation of MAX value counted to execute Timer based registration, byte reg_prd 64 and Timer based registration is executed when counter reaches REG_COUNT_MAX is REG_COUNT_MAX, calculated as and follows: REG_COUNT_MAX = [ 2reg_prd/4 ] registration distance 0 : Personal Stations are not to perform word16 reg_dist 0 distance based registration.
STAREX-IS BSM Manual certain intervals. power report mode delay(min time between power byte pwr_rep_delay 5 requests) time from MS report to reattempt. After receiving this system parameter, for boolean rescan 0 reinitialization or system reobtaining, set this fiel to ‘1’, and if not, set that to ‘0’. As pilot detection threshold, this is used to byte t_add 26 determine whether to transmit Pilot Strength Measurement Messag. BTS sets this field as pilot detection threshold.
STAREX-IS BSM Manual only one side should be used ( 0 : not changed 1 : change subject to message byte PRI_NGHBR_LIST byte USER_ZONE_ID byte byte byte ) Field for BS to check the status of Private NGHBR_LIST Msg through Paging Channel Message Field to check the status of User_zone_id Msg through Paging Channel Message Field EXT_GLOBAL_REDI to check Ext_global_redirection RECT the Msg status through of Paging Channel Message EXT_CHAN_LIST reserved_byte[3 2] 1 Field to check the status of
STAREX-IS BSM Manual consists of tmsi_zone and tmsi_code. BS sets this field as the number of octet included in tmsi_zone. Byte tmsi_zone[8] 0 Length : 8*tmsi_zone_len byte bcast_index 6 To enable periodic broadcast paging, BS sets this field to ‘1~7’, and if not, set that to ‘0’. byte IMSI_T_SUPPORT ED byte P_REV 6 Protocol revision level BS sets this filed to ‘00000110’.
STAREX-IS BSM Manual (1) set this field to ‘1’, and if not, set this field to ‘0’. byte EC_THRESH Pilot power threshold. (0 or 5) If RESELECT_INCLUDED is set to ‘1’, BS includes this field and sets that as follows: (pilot_power_threshold + 115) pilot_power_threshold pilot power(Ec), and MS measns performs system reselection if the output of corresponding pilot is below this filed. byte EC_IO_THRESH Pilot Ec/Ic threshold.
STAREX-IS BSM Manual and if not, set this field to ‘0’. byte ACCESS_HO Access handoff permitted indicator. (0 or 1) If NGHBR_SET_ACCESS_INFO is ‘0’, omit this field, and if ‘1’, it allows MS access handoff. It sets this filed to ‘1’, and if not, it sets that to ‘0’. byte ACCESS_HO_MSG_ Access handoff permitted for message response RSP indicator. (0 or 1) and if ‘1’, it sets this field to 1 and if not it If ACCESS_HO is ‘0’, omit this field, sets this field to 0.
STAREX-IS BSM Manual byte QPCH_SUPPORTED 1 Quick Paging Channel Supported Indication. (1) If BS supports Quick Paging Channel operation, set this field to ‘1’, or not, set that to ‘0’. byte NUM_QPCH 1 Number of Quick Paging Channels. If QPCH_SUPPORTED is ‘0’, omit this field, and (0 or 2) if ‘1’, BS sets this field as many as the number of Quick Paging Channel over CDMA Channel. BS will not set this field to ‘0’.
STAREX-IS BSM Manual (6) Configurations greater than 2. BS sets this field with reverse traffic channel power value. byte reserved_byte[ 0 33] 7.5.8.6. St_nghbr_list_msg_data_type.dg Table 7.
STAREX-IS BSM Manual the current station.
STAREX-IS BSM Manual word16 nghbr_freq[] If freq_incl field is set to ‘1’ this field to the CDMA channel Number freq_incl field is set to ‘0’ byte timing_incl[] disregarded B : MS moves at 2FA -> 5FA B is the value on 3,4,5FA. It is held by 5FA BS. If each Nghbr Sector transmits pilot in DTX mode, it indicates timing information.
STAREX-IS BSM Manual permitted for the corresponding pilot while in the System Access State. If MS is in System Access State, BS sets this field to 1 or not it sets that to 0 if MS access handoff or access probe handoff is allowed. The order of ACCESS_HO_ALLOWED is the same as that of Neighbor List Message, Extended Neighbor List Message or General Neighbor List Message. byte reserved_byte[34] 0 7.5.8.7. St_Qos_param_data Table 7.
STAREX-IS BSM Manual byte Gh_tx_filter 0 Pilot Channel gain int16 R_tx_pilot 0 Minimum trasmit pilot power to transmit total power ratio for sector j. 1/16 step, 0 -255/16 ~ 0/16 byte flnk_call_blk_thresh byte flnk_handoff_blk_thresh 0 Handoff blocking threshold.
STAREX-IS BSM Manual Enabled byte rlnk_cap_limit 0 0: Reverse Link Excess Capacity Link Excess Capacity Limitation Enabled 1: Reverse Limitation Disabled byte reserved_byte[33] 0 7.5.9.2. St_txms_param_data.dg Table 7.5-80 St_txms_param_data Type N a m e default Remarks byte sector_id full Sector Identification byte cdmach_id full CDMA Channel Identification word16 ovhdch_erp 170(1.7W) Overhead Channel Effectiver Radiation Power and 170 means 1.7W(32dBm).
STAREX-IS BSM Manual byte tx_atten No-use 255 Noise attenuator setting for the transmit paths in 0.5 dB steps(0~63.5dB) boolean breathing No-use 0 Whether cell power “breathing” enabled. byte expected_db No-use 16 Cell breathing threshold in db. word16 power_upper_bound No-use 20 TICrecerse power threshold upper bound word16 power_lower_bound No-use 15 TICrecerse power threshold upper bound byte reserved_byte[33] 0 7.5.9.4. St_acc_param_data_type.dg Table 7.
STAREX-IS BSM Manual channel frame number transmitted from access 채 channel preamble. byte psist_0_9 0 As value on access overload grade(0~9), if access pverload grade allows 0~9 MS to transmit request to access channel, BS sets that as continuous value to use this field and if not, it sets that to ‘111111’.
STAREX-IS BSM Manual byte reg_psist 0 MS multiplies [2-MSG_PSIST] to transmission probability. byte probe_pn_ran 0 As a field related to time random for access channel probe, BS sets value of 0~9 so that the range of time random value is 2PROBE_PN_RAN-1 chip. byte acc_tmo 6 Answer time excessive value.
STAREX-IS BSM Manual system. 0 : No return byte delete_tmsi byte EXCL_P_REV_MS 0 Delete TMSI Indicator Indicator to apply Global Service redirection Message(GSRM) to MOB_P_REV 6 or above. byte REDIRECT_P_REV_INCL Indicator to divide the application scope of EGSRM according to MOB_P_REV value. byte EXCL_P_REV_INCL Indicator to exclude the application of GSRM regarding MS that has corresponding MOB_P_REV.
STAREX-IS BSM Manual z) system should be filled. 4(1800Mh 800Mhz: 0 z) 1800Mhz : 4 = domestic 1900Mhz: 1 = overseas Word16 expected_sid 0 If Base station has personal system redirected to other system, this sets this field to SID of redirected system. Word16 expected_nid 0 If Base station has personal system redirected to other system, this sets this field to NID of redirected system.
STAREX-IS BSM Manual When MIC C, D are used for subway, this file is set to ‘0’. byte ttrf_type[12] 0 0 : Not_Equip, 1 : Equip, 2 : Equip and Blocked. 4EA per sector among 12EA. byte fa_use byte risa_eqp byte reserved_byte[34] 0 1 0: 1FA-6Sec 1; 2FA-3Sec 0: not equip, 1: equip Reserved Field 7.5.9.7. St_dru_chc_data_type Table 7.
STAREX-IS BSM Manual word16 tx_div_timing_adv[MAX_SECTORS] 0 Timing advance (Tx Diversity Path) Max : 1264 byte sector_tx_io_format 0 (6 path or 0:tx_output_chipx1, below) 2 (3 1: tx_output_chipx1_fir path or 2: tx_output_chipx2_fir below) word16 cell_radius 511 byte 1 (6 path rev_input_format in units of PN chip or 0:chipx8_rate_input, below) 0 (3 1: chipx2_rate_input path or below) byte ant_enable[MAX_ANTENNAS] MAX_ANTENNAS = 12 byte ant_source[MAX_ANTENNAS] ? byte rev_ce
STAREX-IS BSM Manual int override_search_energy_rc1 No-use int override_search_energy_rc2 No-use int override_search_energy_rc3 No-use int override_search_energy_rc4 No-use int override_search_energy_rc5 No-use int override_search_energy_rc6 No-use word16 turbo_dtx_threshold No-use 240 word16 conv_dtx_threshold No-use 392 byte bin_size No-use byte integration_period No-use word16 srch_win_len[MAX_SECTORS] 1(traffic) byte 0 reserved_byte[32] Range : 1~32 7.5.9.9.
STAREX-IS BSM Manual 7.5.9.10. St_pich_data_type (Pilot Channel) Table 7.5-88 St_pich_data_type (Pilot Channel) Type N a m e default Remarks BYTE SECTOR_ID 0 ~ 2 BYTE CDMACH_ID 0 ~ 7 BYTE PROC_ID PILOT CHANNEL PROCESSOR NUMBER (RCP) BYTE SLOT PILOT CHANNEL SLOT NUMBER BYTE PILOT_GAIN BYTE PILOT_TD_GAIN byte reserved_byte[34] 0 234 pilot channel gain. in unit of dB piot tx_diversity channel gain. 7.5.9.11. St_synch_data_type (Sync Channel) Table 7.
STAREX-IS BSM Manual byte proc_id Paging channel processor number (RCP) byte slot Paging channel slot number BYTE PC_GAIN 217 Paging channel tx gain. in unit of dB byte frame_duration 2 Packet frame size. (5ms/20ms) Range : 0~4 (2:20ms) byte data_rate 0 data rate. Range : 0~1(0:9600bps, 1:4800bsp) byte encoding_rate No-use 1 byte reserved_byte[34] 0 Convolutional channel coding rate. 7.5.9.13. St_qpch_data_type (Quick Paging Channel) Table 7.
STAREX-IS BSM Manual BYTE SECTOR_ID full 0 ~ 2 BYTE CDMACH_ID full 0 ~ 7 BYTE PC_ID full 0 ~ 6 BYTE AC_ID full 0 ~ 31 byte equpage BYTE PROC_ID ACCESS CHANNEL PROCESSOR NUMBER (RCP) BYTE SLOT ACCESS CHANNEL SLOT NUMBER. byte pam_int_prd No-use 2 As integer between 2~4(Walsh symbols), 8-pam _int_prd(Walsh symbol), when detecting access probe preamble, is dector integration period.
STAREX-IS BSM Manual WORD16 SRCH_WIN_SIZE 4(access) Search Window Size. in units of 64PN chip. Range : 1~32(64 PN Chips units) byte reserved_byte[35] 0 7.5.9.15. St_apich_data_type (Auxiliary Pilot Channel) Table 7.5-93 St_apich_data_type (Auxiliary Pilot Channel) Type N a m e default Remarks BYTE SECTOR_ID full 0 ~ 2 BYTE CDMACH_ID full 0 ~ 7 BYTE PROC_ID APICH PROCESSOR NUMBER (RCP) BYTE SLOT APICH SLOT NUMBER byte reserved_byte[32] 0 7.5.9.16.
STAREX-IS BSM Manual byte SR1_OTD_INCL byte SR1_CDMA_FREQ_OTD byte SR1_BCCH_RATE_OTD byte SR3_CAP_IND byte SR3_CDMA_FREQ byte SR3_BCN byte SR3_BRAT byte frame_duration Packet frame size. (5ms/20ms) byte data_rate data rate. byte radio_configurati Convolutional on configuration channel coding rate. Radio (encoding_rate) byte reserved_byte[34] 0 7.5.9.17. St_cpch_data_type (Common Power Control Channel) Table 7.
STAREX-IS BSM Manual 7.5.9.18. St_cach_data_type (Common Assignment Channel) Table 7.5-96 St_cach_data_type (Common Assignment Channel) Type N a m e default Remarks BYTE SECTOR_ID full 0 ~ 2 BYTE CDMACH_ID full 0 ~ 7 BYTE CACH_ID full 0 ~ 6 byte equipage BYTE PROC_ID CACH PROCESSOR NUMBER (RCP) BYTE SLOT CACH SLOT NUMBER byte frame_duration Packet frame size. (5ms/20ms) byte data_rate data rate.
STAREX-IS BSM Manual 7.5.9.20. St_each_data_type (Enhanced Access Channel) Table 7.5-98 St_each_data_type (Enhanced Access Channel) Type N a m e default Remarks BYTE SECTOR_ID full 0 ~ 2 BYTE CDMACH_ID full 0 ~ 7 BYTE FCCCH_ID or CACH_ID full 0 ~ 6 BYTE EACH_ID byte equipage BYTE DUPLEX_ID BYTE PROC_ID EACH PROCESSOR NUMBER (RCP) BYTE SLOT EACH SLOT NUMBER BYTE reserved_byte[33] full 0 ~ 31 0 ~ 1 Redundancy 0 7.5.9.21.
STAREX-IS BSM Manual byte cdmach_id full byte ocns_enable 0 0: Ocns Enabled byte num_of_ocns_ch 0 Ocns Call Number ( 0 ~ 20 ) byte ocns_test_data 5 Test Data Rate 1: Ocns Disabled ( 0 ~ 5 ) ( B, 1/8, 1/4, 1/2, 1, V) word16 ocns_so 0x801f Service Option [ Markov(8002, 801f), LB(2,9) ] byte block_state 0 0: Unblock, 1: Block If current sector FA is ‘block’, MS regards no FA residing in channel list. byte reserved_byte[32] 0 7.5.9.23. St_HW_reset_type Table 7.
STAREX-IS BSM Manual byte bppa byte reserved_byte[23] 0 7.5.9.24. St_Chip_pwr_cntl_para_data( 0:FCH , 1:SCH, 2:SCCH, 3:DCCH ) Table 7.5-102 St_Chip_pwr_cntl_para_data Type N a m e default byte Dummy 0 byte Channel_pwr[MAX_CH_T 224 YPE(4)] byte Data_gain Remarks Forward Traffic Channel Tx Power 0(-63.5dB) ~ 127(0dB). No-use 0.5dB step Data Gain to be added to the Channel Power -31.75dB ~ 31.75dB. byte Pwr_cntl_gain No-use Power Control 0.
STAREX-IS BSM Manual 7.6. Abbreviations Table 7.6-1 Abbreviations in IS-2000 system Abbreviations Description ABID Alarm Buffer Inerface Daughter board ACBB AAL 2 Control Back Board ALP ATM Low speed subs.
STAREX-IS BSM Manual FERA Fast Ethernet Routing Board Assembly FETD Fast Ethernet Termination Board Assembly GPS-D global Positioning System - Distribution GPS-R Global Positioning System - Receiver GUI Graphic User Interface HDLC High-level Data Link Control LICA Line Interface Controller Board Assembly LPA Linear Power Amplifier MAC Medium Access Control MMI Man Machine Interface NCP Network Control Processor OCNS Orthogonal Channel Noise Simulator PACA Power Adjustment Control A