Installation Guide

INSTALLATION GUIDE
PK-A3135-10-00-2B
LINE VOLTAGE DIMMING ROOM CONTROLLERS
CALIFORNIA TITLE 20 COMPLIANT
Cat. Nos. OxC20-MDW/VxC20-MDW/ OxC04-IDW/VxC04-IDW
Rating: 8A @ 120 VAC, 50/60 Hz ,1/4 Hp / Current Consumption: 60-30 mA
Rating: 5A @ 277 VAC, 50/60 Hz, 1/3 Hp / Current Consumption: 60-30 mA
Operating Temperature: 32˚ to 104˚F (0˚ to 40˚C) / Operating Humidity: 10 to 90%, non-condensing
Compatible with 0-10V controlled 120-277VAC loads.
Provolt
TM
WARNINGS AND CAUTIONS:
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
a)
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
b) DO NOT use outdoors.
c) DO NOT mount near gas or electric heaters.
d) Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
e) The use of accessory equipment not recommended by manufacturer may cause an unsafe condition.
f) DO NOT use this equipment for other than the intended use.
SAVE THESE INSTRUCTIONS
TOOLS NEEDEDDESCRIPTION
• Slotted/Phillips Screwdriver
• Small Slotted Screwdriver
• Wire stripper
• Cutters
The next generation of lighting control technology is here with the new
Provolt™ Room Controller with Bluetooth
®
Technology. This innovative
device works using the Leviton Provolt™ app that can be easily downloaded
to smartphones or tablets and paired to the Leviton Provolt™ Room
Controller using Bluetooth
®
technology. Provolt™ Room Controller devices
give users point-to-point local control to automate lighting, bridging the gap
between standard room controllers and whole-building automation systems.
The Leviton Provolt™ app can be easily downloaded to mobile devices and
is compatible with Android and iOS smartphones or tablets. The app is easy
to use with simple, intuitive on-screen menu options to control a Provolt™
Room Controller.
Wiring Diagram 1 (1-Zone units)
Wiring Diagram 2 (2-Zone units)
NOTES:
Both loads of the 2-Zone units MUST be fed from the same phase.
When installing Class 2 wiring use the provided tubing for insulation inside
the junction box.
To mount inside 4" octagon 2.125" deep ceiling electrical box
(Fig. 1).
Dress line voltage wires to provide
enough clearance in electrical box
when device is installed.
Partially thread two #8-32 screws
(not included) into the mounting
holes of the electrical box.
Pull out the two coasters that align
with the two screws.
Align room controller so that it fits
between the mounting holes of
the electrical box and insert over
mounting screws.
Push in the two coasters that align
with the two screws.
Tighten mounting screws
firmly.
To mount inside 4" square 1.5" deep ceiling electrical box with mud ring
(Fig. 2).
Ensure that conduit/cable entry
clamp is located in corner of electrical
box.
Dress line voltage wires to provide
enough clearance in electrical box
when device is installed.
Install a two-gang mud ring
(not included) on electrical box.
Partially thread the two #6-32 screws
provided into the mounting holes of
the electrical box.
Pull out the two coasters that align
with the two screws.
Align room controller so that it fits
between the mounting holes of
the electrical box and insert over
mounting screws.
Push in the two coasters that align
with the two screws.
Tighten mounting screws firmly.
The O5C20-MDW & O6C20-MDW Room Controllers are LINE-voltage
multi-technology (PIR and Ultrasonic) sensors (Occupancy and Photocell)
that automatically control lighting. The room controller is multiple sensors
and technology working together to provide room lighting automatically and
efficiently. Occupancy sensors turn the lights ON and keep them ON, will
turn them OFF when room is vacant and delayed-off timer expires. Photocell
detects natural light and dims room lighting up or down as needed for
additional energy efficiency and circadian rhythm occupant comfort benefits.
The V6C20-MDW LINE-voltage multi-technology Partial Off Room Controller
monitors the space for vacancy. The lights can be turned ON manually by
pressing the low-voltage/momentary toggle switch or PLVSW 1, 2, or 4 button
switch. The sensor turns the lights OFF when vacancy is detected and the
delayed-off time has expired. NOTE: Multiple PLVSW switches can be used
with a single Provolt Room Controller. Multiple 2 and 4 button switches OR
multiple 1 button or low voltage momentary or toggle switches.
The combination of ultrasonic (doppler shift) motion detection which gives
maximum sensitivity and infrared motion detection which gives higher false
triggering immunity yields a sensor with excellent performance.
The O5C04-IDW & O6C04-IDW Room Controllers are LINE-voltage
infrared sensors that automatically control lighting. The room controller is
multiple sensors working together to provide room lighting automatically and
efficiently. Occupancy sensor turns the lights ON and keeps them ON, will
turn them OFF when room is vacant and delayed-off timer expires. Photocell
detects natural light and dims room lighting up or down as needed for
additional energy efficiency and circadian rhythm occupant comfort benefits.
The V6C04-IDW LINE-voltage infrared Partial Off Room Controller monitors
the space for vacancy. The lights can be turned ON manually by pressing
the low-voltage/momentary toggle switch or PLVSW 1, 2, or 4 button switch.
The sensor turns the lights OFF when vacancy is detected and the delayed-
off time has expired. NOTE: Multiple PLVSW switches can be used with a
single Provolt Room Controller. Multiple 2 and 4 button switches OR multiple
1 button or low voltage momentary or toggle switches.
Infrared motion detection gives higher false triggering immunity that yields a
sensor with excellent performance.
These sensors continually analyze and adjust to changing conditions and
use the latest microprocessor-based technology which permits them to
continually adjust and optimize their performance.
PARTS INCLUDED LIST
• Room controller (1)
• 4" x 4" Mounting Plate (1)
• #6-32 x 1-1/2" Screw (2)
• Mid-Range Lens [red frame] (1)
Extended Range Lens
[black frame] (1) (assembled)
• High voltage terminal covers (1)
Angled Light Pipe (1)
Flat Light Pipe (1) (assembled)
• 360˚ Perforated Mask (1)
• Low Voltage Connector (1)
• Half Mask (1)
• Tubing Barrier (1)
(Fig. 1)
(Fig. 2)
MANUAL
INPUT
DIM
+
MS
MS
+
DS
DS
+
Class 1 or Class 2 circuit
DIM
0-10V
50mA Max.
Demand Input
+
DIM +
Demand Input -
DIM -
6
7
8
9
10
11
Manual Switch
+
Manual Switch -
Line
Neutral
Sensor
Line Voltage
Line (L1) Load OUT (L1)
Neut. N
Load
Line
120-277VAC,
50/60Hz
Class 1 or Class 2
circuit
DEMAND
INPUT
For Class 2 instalation:
WIRING SHALL BE
INSTALLED WITHIN
THE PROVIDED
FLEXIBLE TUBING
TO MAINTAIN
SEPARATION.
INSTALLING YOUR ROOM CONTROLLER
Control Wires (Manual Switch, Demand Input and 0-10V)
Wire range: #16-26 AWG, 4.0 - 0.12 mm square
Torque rating: 2.5 lb-in, 2.88 kgf-cm.
NOTE: Maximum system low voltage wire length must be limited to 800 ft.
Line, Neutral, Load Wires (Copper)
Wire range: #12-18 AWG, 3.3 - 0.75 mm square
Torque rating: 20 lb-in, 23 kgf-cm.
INSTALLING YOUR ROOM CONTROLLER:
Insert wires into proper terminals. Use a screwdriver to turn terminal screws
clockwise and secure wires. NOTE: Wires need to be inserted from the top
through the wire holes provided on the room controller and clamped down
using the washer to the terminals. Cover terminals with provided high voltage
terminals covers.
a) Load wire(s) to Load terminal(s).
b) Neutral wire to Neutral terminal.
c) Line wire(s) to Line terminal(s).
d) Connect the Violet wire to the + 0-10V line and the Gray wire to the
common 0-10V line using Class 1 or Class 2 wiring methods as
indicated by the load / ballast installation instructions or label markings.
e) Manual Switch and Demand Input to their respective marked terminals.
3
Wire
Strip Gauge 3/4"
PREPARING AND CONNECTING WIRES:
Connect wires per appropriate WIRING DIAGRAM as follows:
Make sure that the ends of the wires from the electrical box are straight.
Remove insulation from each wire in
electrical box as shown.
Wire per Specifications:
2
WARNING
:
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF
POWER at circuit breaker or fuse and TEST that power is off before
wiring!
1
Line 1
Neutral
Sensor
Line Voltage
(both lines MUST be fed from the same phase)
Line 1 (L1)
Line 2 Line 2 (L2)
Load 1 OUT (L1)
Neut. N
Load 2Load 1
Line
120-277VAC,
50/60Hz
Load 2 OUT (L2)
MANUAL
INPUT
DIM1
+
MS
MS
+
DIM2 +
DS
+
Class 1 or Class 2 circui
t
DIM
0-10V
50mA Max.
Class 1 or Class 2
circuit
DEMAND
INPUT
For Class 2 instalation:
WIRING SHALL BE
INSTALLED WITHIN
THE PROVIDED
FLEXIBLE TUBING
TO MAINTAIN
SEPARATION.
Demand Input
+
DIM1 +
DIM2 +
DIM -
6
7
8
9
10
11
Manual Switch +
Manual Switch -
/
Demand Input -
ENGLISH
WARNINGS AND CAUTIONS:
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT
POWER IS OFF BEFORE WIRING!
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
Use this device with copper or copper clad wire only.
Room controllers must be mounted on a vibration free surface.
Do not terminate using data type wire, such as Cat 5/5E.
Do not mount room controllers closer than 15 feet to each other.
All units must be mounted at least 6 feet away from air vents, air handlers, and reflective surfaces (windows/mirrors).
Do not touch the surface of the lens. Clean outer surface with a damp cloth only.