Cut Sheet

for current information see: www.lappusa.com • www.lappcanada.com102
ÖLFLEX
®
Flexible cable for drives, motors & assemblies
Application advantage
Construction
ECOLAB
®
is a registered trademark of Ecolab, Inc.
Recommended SKINTOP
®
assumes minimal OD variance. Additional congurations are available; please see our SKINTOP
®
section.
If not otherwise specied, all values relating to the product are nominal values. Photographs are not to scale and are not true representations of the products in question.
Recommended applications
Complete the installation
SKINTOP
®
MS-SC
page 522
EPIC
®
ULTRA HB
page 404
Approvals
VFD cable
Technical data
Minimum bend radius: 7.5 x cable diameter
Temperature range:
- UL/CSA TC: -25°C to +90°C
- for stationary use: -40°C to +105°C
- for exible use: -25°C to +105°C
Nominal voltage:
- UL/CSA TC: 600V
- UL WTTC: 1000V
- UL Flexible Motor Supply: 1000V
- UL/CSA AWM: 1000V
Test voltage: 2000V
Peak voltage: 7500V
Conductor stranding:
- 16 - 6 AWG: Class 5 ne wire
- 4 AWG: Class K ne wire
Color code: b lack with white numbers,
plus green/yellow ground and
one black pair with white numbers
Approvals: UL: TC-ER per UL 1277
MTW per UL 1063
WTTC per UL 2277
AWM 20886
Attributes: UL Oil Res I/II
75°C wet; 90°C dry
-40°C cold bend; -25°C cold impact
sunlight resistant
NFPA 79
NEC: C lass 1 Division 2 per NEC Article 501
Canada: c(UL) CIC/TC FT4
CSA AWM I/II A/B 1000V FT4
Additional: MSHA P-07-KA050011-MSHA
CE & RoHS
Cable attributes page 648
OIL
OR-03
FLAME
FR-03
MOTION
FL-01
MECH.
MP-03
LAPP Surge Guard insulation system
UL TC-ER & c(UL) CIC TC approved
Double-shielded for extra protection
Contains pair for brake or temperature sensor
Resistant to a wide range of disinfecting solutions used
in the food, beverage, chemical and related industries,
according to ECOLAB
®
PM 40-1 test procedure
VFD drive and motor connections with temperature sensors or brake
mechanisms; web presses; HVAC; on/o, slow down/speed up applications
ÖLFLEX
®
VFD with Signal is an extremely oil- and UV-resistant shielded motor power
cable for VFD drives, with an additional pair for brake or temperature sensor. It is
designed with LAPP Surge Guard insulation, which includes a semiconductive layer
made to withstand nonlinear power distortions associated with VFD drives and to
disperse increases in voltage. It is resistant to a wide range of disinfecting solutions
used in the food, beverage, chemical and related industries.
Conductors: nely stranded tinned copper
Insulation: LAPP Surge Guard insulation system
Shielding: barrier tape; triple layer foil tape (100% coverage);
tinned copper braid (85% coverage)
Jacket: specially formulated thermoplastic polymer; black
ÖLFLEX
®
VFD with Signal
Flexible VFD cable with a control pair; 600V/1000V; UL & c(UL) TC-ER approval
LAPP KABEL ÖLFLEX
®
VFD with Signal
Part
number
Number of
conductors
Nominal
outer diameter
Copper
weight
Approx.
weight
SKINTOP
®
MS-SC
SKINTOP
®
MS-M BRUSH
incl. ground in mm lbs/mft lbs/mft PG thread metric thread
16 AWG (1.5 mm²)
7416048 4 + (18 AWG) 0.519 13.2 88 180 53112240 53112676
14 AWG (2.5 mm²)
7414048 4 + (18 AWG) 0.573 14.6 118 216 53112250 53112676
7414044 4 + (14 AWG) 0.600 15.2 141 254 53112250 53112676
12 AWG (4 mm²)
7412048 4 + (18 AWG) 0.632 16.1 162 286 53112250 53112677
7412044 4 + (14 AWG) 0.662 16.8 187 326 53112250 53112677
Part
number
Number of
conductors
Nominal
outer diameter
Copper
weight
Approx.
weight
SKINTOP
®
MS-SC
SKINTOP
®
MS-M BRUSH
incl. ground in mm lbs/mft lbs/mft PG thread metric thread
10 AWG (6 mm²)
7410044 4 + (14 AWG) 0.745 18.9 260 406 53112260 53112677
8 AWG (10 mm²)
7408044 4 + (14 AWG) 0.896 22.8 375 617 53112260 53112678
6 AWG (16 mm²)
7406044 4 + (14 AWG) 1.026 26.1 472 848 53112270 53112678
4 AWG (21 mm²)
7404044 4 + (14 AWG) 1.324 33.6 643 12 51 53112679
( ) = shielded pair
FIRE
PROTECTION

Summary of content (1 pages)