Datasheet

0012640
DATA SHEET
Valid from:
12.07.2018
ÖLFLEX
®
EB CY
Creator: LABU/PDC
Released: HAPF/PDC
Document: DB0012640EN
Version: 07
Page 1 of 1
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN
Application
ÖLFLEX
®
EB CY are PVC control cables with blue outer sheath for occasional flexible use and fixed installation in intrinsically
safe circuits. They are also suitable for use in dry, damp or wet areas. They are suitable for outdoor use if the indicated
temperature range is observed. They are suitable for occasional, non-automated movements. The maximum tensile load is
15 N/mm
2
of conductor cross-section during installation and operation. Compulsory guidance is not permitted. The
screening braid protects against interference from electrical fields.
Application range:
Installation of intrinsically safe circuits, where a special cable marking for hazard area type “ i “ intrinsic safety is specified;
The cables meet the requirements of DIN EN 60079-14(VDE 0165-1), section 16.2.2 potentially explosive atmosphere.
Design
Design
based on
DIN EN 50525-2-51 resp. VDE 0285-525-2-51
Conductor
fine wire strands of bare copper acc. to IEC 60228 resp. VDE 0295, Class 5
Core isolation
LAPP special PVC compound P8/1
PVC compound TI2 acc. to DIN EN 50363-3 resp. VDE 0207-363-3 with increased
Requirements acc. to Lapp specification
Core identification
acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334
Wrapping
plastic foil
Screen
braid of tinned copper, coverage = 85% (nominal value)
Outer sheath
PVC compound TM2 acc. to DIN EN 50363-4-1 resp. VDE 0207-363-4-1 with
increased requirements acc. to Lapp specification
colour: blue, similar RAL 5015
Electrical properties at 20°C
Nominal voltage
U
0
/ U: 300 / 500 V
Operating voltage
< 50 V AC resp.
< 75 V DC in intrinsically safe circuits
Test voltage
core / core: 3000 V AC
core / screen: 2000 V AC
Mechanical and thermal properties
Min. bending radius
occasional flexing: 20 x outer diameter
fixed installation: 6 x outer diameter
Temperature range
occasional flexing: -5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Flammability
flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
UV-resistance
acc. to EN 50618 resp. VDE 0283-618
acc. to EN 50620 resp. VDE 0285-620
acc. to EN ISO 4892-2-2013, method A (change of colour allowed)
Tests
acc. to IEC 60811 resp. VDE 0473-811, VDE 0472, EN 50395, EN 50396
EU Directives
These cables are conform to the EU Directive 2014/35/EU (Low Voltage
Directive)