Current Draw & Thermal Dissipation

Current Draw and Thermal Dissipation
PLM
Series: Powered Loudspeaker Management
PLM 10000Q
WWW.LABGRUPPEN.COM
Item no. CDTD-PLM10000Q - 03.12.2015
PLM SERIES
PLM
10000Q
The following tables contain information on measured current consumption as well as calculated heat dissipation during normal operation
(1/8 rated power); and during extreme heavy duty operation (max power).
PLM 10000Q
Level Load Rated power Line current *2) Watt *1) Thermal Dissipation
120 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby, with remote power off 4.8 0 4.8 16 4
Power On, Idling 145 0 145 496 125
Amp (l) Watt *1)
Pink pseudo
noise (1/8
rated power)
16 Ω / Ch. 660 x 4 9.3 4.8 687 330 357
1218 307
8 Ω / Ch. 1300 x 4 16.3 8.5 1250 650 600
2048 516
4 Ω / Ch. 2300 x 4 25.2 13.2 2014 1150 864
2949 743
2,67 Ω / Ch. 2700 x 4 31.3 16.4 2553 1350 1203
410 6 1034
2 Ω / Ch. 2350 x 4 29.2 15.2 2341 1175 116 6
3980 1003
Pink pseudo
noise (1/4
rated power)
*3)
16 Ω / Ch. 660 x 4 14.7 7.7 1098 660 438 1495 377
8 Ω / Ch. 1300 x 4 26.0 13.6 2049 1300 749 2556 644
4 Ω / Ch. 2300 x 4 45.8 23.9 374 6 2300 1446 4935 1243
2,67 Ω / Ch. 2700 x 4 52.5 2 7.4 4420 2700 1720 5870 1479
2 Ω / Ch. 2350 x 4 51.0 26.6 4179 2350 1829 6242 1573
Sine 20 kHz 16 Ω / Ch. 1 x 4 2.7 1.4 160 4 156 532 134
16 Ω / Ch. 0.25 x 4 2.5 1.3 149 1 148 505 127
Mains connector - 230 V CE version / 230 V ETL version / 115 V ETL version 32 A, Neutrik
®
powerCON
®
Twist lock
*1) The amplifier section’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and
specified here is what is known as the “Active Power” of the amplifier section providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw figures measured at 230 V. 115 V figures are converted from 230 V figures.
*3) Figures measured at maximum power before amplifier protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated power.
Note that the maximum power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped
even if operation is in excess of maximum ratings.