A & E Specifications
WWW.LABGRUPPEN.COM
Item no. AES-NLB60E - 02.12.2015
Overview and Functions
The network bridge and system controller shall provide an interface
between multiple power ampliers equipped with NomadLink
monitoring/control facilities and a host computer running associated
DeviceControl software. Communication between the network
bridge and system controller and the host computer shall be over an
Ethernet LAN using TCP/IP protocols. The IP address for the network
bridge and system controller and system controller shall be entered
manually from the front-panel or set remotely by a DHCP server.
Communication between the network bridge and system controller
and the power ampliers shall be over a daisy-chained subnet with
interconnections on Cat-5 cable using RJ45 connectors. The subnet
shall accommodate as many as 60 ampliers and as many as 480
amplier channels. The distance between the network bridge and
system controller and any amplier, or between any two ampliers,
shall be up to 300 m (980 ft.) and total length of the subnet cabling
shall be up to 700 m (2300 ft.) when the network forms a closed loop.
When the network is an open daisy-chain, total length shall be up to
400 m (1300 ft). The network bridge and system controller shall be
able to detect a closed loop network, and report an error if the loop
is broken. The network bridge and system controller shall provide
phantom power through the network, thereby maintaining a network
connection when ampliers are powered off or malfunctioning. Mute
on/off function for all channels in the subnet shall be accessible on
front-panel buttons. General faults as well as individual amplier
faults shall be indicated with a red Fault LED on the front-panel and
on the character display. The network bridge and system controller
shall offer three general purpose input (GPI) connections for external
control purposes; one GPI shall sense voltage (above or below
+10 VDC) while two GPIs shall sense contact closure. GPI’s shall
be user congurable to operate amplier subnet power on/off and
mute channels.
Connectors, Controls, and Indicators
The following connectors shall be provided on the rear-panel: one
EtherCon RJ45 for Ethernet; two EtherCon RJ45 for loop subnet
(NomadLink) In and Out; one 2-pole Phoenix input for voltage
sensing GPI; and two 2-pole Phoenix inputs for contact-closure
GPI. The following connector shall be provided on the front-
panel: one standard RJ45 Ethernet in parallel with the rear-panel
Ethernet connection.
The following controls shall be provided on the front-panel: six
navigation and parameter selection keys, and two momentary
switches to activate global power on or off for all power ampliers
connected to the subnet.
The following LED indicators shall be provided on the front-panel:
front-panel operation locked (yellow), fault warning (red), amplier
subnet muted (red); NomadLink (subnet) connected and active
(blue); Ethernet connected (orange), and Ethernet active (yellow).
A 2 x 16 character display with white text on blue background shall
display network status and parameters.
Power Supply
The network bridge and system controller shall have a universal
power supply with automatic selection of AC line sources from
100 V to 240 V at 50 Hz or 60 Hz. Power consumption shall be less
than 20 watts.
Physical
The network bridge and system controller shall be 483 mm (19 in.)
wide, 44 mm (1.75” or 1 U) high, and 208 mm (8.2 in.) deep. Weight
shall be 2.25 kg (5 lbs.). Housing shall be plated and painted steel
with an anodized aluminum front-panel.
The network bridge and system controller shall be approved for
use as specied by CE and CSA. The network bridge and system
controller shall be the Lab.gruppen NomadLink Bridge & System
Controller NLB 60E.
NLB 60E
Architect’s and Engineer’s Specifications
NomadLink Bridge & System Controller