Specification

G11-121 (Model RXT Automatic Transfer Switch) 6/12a Page 1
Automatic Transfer Switch
100--400 Amps
Model: RXT
Model RXT Automatic Transfer Switch
The Model RXT automatic transfer switch is designed for use
only with Kohlerr generator sets equipped with RDC2 or DC2
generator set/transfer switch controls. The transfer switch
operation is controlled by the RDC2/DC2 integrated generator
set/transfer switch controller, which is mounted on the following
Kohlerr generator set models:
d 14RESA/RESAL
d 20RESA/RESAL
d 48RCL
Standard Features
D Allows utility voltage display on the RDC2/DC2 integrated
generator set/transfer switch controller, available exclusively
on Kohlerr residential and light commercial generator sets
D Interface board for connection to the M odel RDC2 or DC2
generator set/transfer switch controller (mounted on
generator set models listed above)
D UL listed
d Models with load centers, UL 67 listed, file # E251086
d Models without load centers, UL 1008 listed, file #E58962
D CSA certified, file # LR58301 (not applicable to service
entrance or load center models)
D Corrosion-resistant NEMA 3R aluminum enclosure:
d Padlockable
d Approved for indoor or outdoor installation
d ANSI 49 gray
D Contactor electrically and mechanically interlocked
D Double throw inherently interlocked design
D Contactor manually operable for maintenance purposes
D Silver alloy main contacts
D Transfer switches are 100% equipment rated and can be
applied at the rated current without derating (non-service
entrance models)
D 100, 200, and 400 amp standard and service entrance
models are available; see page 6 for available models
D 100 amp standard single-phase models are available with or
without 16-space load center. Up to 8 tandem breakers can
be used for a total of 24 circuits.
D Service entrance models include disconnect circuit breaker
on the utility (normal) source side (80% rated)
D Five-year limited warranty
D Optional status indicator available:
d LED indicators for source availability and contactor
position
d View transfer switch status without removing enclosure
cover