Product Card

KV440C2
Engine type
TAD1344GE
Alternator type KH01741T
Performance class
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
Optional control panel
Optional control panel
POWER
ESP
PRP
Voltage
kWe
kVA
Standby Amps
200/115 352 440 320 400 1270
240 TRI 352 440 320 400 1059
230 TRI 352 440 320 400 1105
220 TRI 352 440 320 400 1155
DIMENSIONS COMPACT VERSION
Length (mm)
3160
Width (mm)
1340
Height (mm)
1805
Dry weight (kg)
3110
Tank capacity (L)
470
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure
M228
4475
1410
2430
4080
470
78
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A)
98
This document is not contractual - Kohler Co. reserves
the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-06004 (KV440C2) 03/17
50
400/230
DEC4000
APM802
M80
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
Electronic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
24 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
68
415/240 352 440 320 400 612
400/230 352 440 320 400 635
380/220 348 435 316 395 661

Summary of content (5 pages)