Operation and Installation Service Entrance Rated Automatic Transfer Switches Models: KEP Power Switching Devices: Insulated-Case Circuit Breakers (ICCB) Molded-Case Circuit Breakers (MCCB) 100--4000 Amperes TP-6946 3/16b
Product Identification Information Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits. Transfer Switch Identification Numbers Record the product identification numbers from the transfer switch nameplate.
Table of Contents Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of Related Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7 Service Assistance . . . . .
.3 Accessory Modules (Option Boards) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 Accessory Module Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 Input/Output (I/O) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.3 External Battery Supply Module (EBSM/BOB) . . . . . . . . . . . . . . . . . . . . . 4.3.4 Alarm Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions and Instructions IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment.
Introduction This manual provides operation and installation instructions for the Kohlerr Model KEP service-entrance rated Automatic Transfer Switch (ATS) equipped with the Decision-Makerr MPAC 1500 controller. A separate manual provided with the transfer switch covers the transfer switch controller operation. See List of Related Materials for the document part number. The equipment service requirements are very important to safe and efficient operation.
Service Assistance For professional advice on generator power requirements and conscientious service, please contact your nearest Kohler distributor or dealer. D Consult the Yellow Pages under the heading Generators—Electric. D Visit the Kohler Power Systems website at KOHLERPower.com. D Look at the labels and decals on your Kohler product or review the appropriate literature or documents included with the product. D Call toll free in the US and Canada 1-800-544-2444.
Section 1 Product Description 1.1 General Description An automatic transfer switch (ATS) transfers electrical loads from a normal (preferred) source of electrical power to an emergency (standby) source when the normal source falls outside the acceptable electrical parameters. Figure 1-1 shows a typical single-line diagram. Figure 1-2 shows a typical transfer switch.
1.2 Overcurrent Protection Model KEP service entrance rated transfer switches have integral overcurrent protection supplied on the utility source as standard. Optional integral overcurrent protection may also be selected on the generator source. An upstream overcurrent protection device is required on the generator source if the integral overcurrent protection option is not specified on the generator side of the ATS.
1.4 Model Designation Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Connection Utility Sw. Gen Sw. Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below.
Notes 12 Section 1 Product Description TP-6946 3/16
Section 2 Installation 2.1 Introduction 2.2.2 Lifting WARNING Kohlerr transfer switches are shipped factory-wired, factory-tested, and ready for installation. Have the equipment installed only by trained and qualified personnel, and verify that the installation complies with applicable codes and standards. Switch installation includes the following steps: Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage. D Unpack and inspect the transfer switch upon receipt.
2.2.3 Storage 2.2.4 Store the transfer switch in its protective packing until final installation. Protect the transfer switch at all times from moisture, construction grit, and metal chips. Avoid storage in low-temperature and high-humidity areas where moisture could condense on the unit. See Figure 2-2 for acceptable storage temperatures.
2.3 Multi-Tap Voltage Capability The transfer switch voltage is factory-set. Check the nameplate and confirm that the transfer switch has been configured for the correct system voltage prior to installation. Note: Verify that the transfer switch voltage matches the system voltage. The transfer switch has multi-tap voltage capability at the voltage transformers. See Figure 2-3 for a typical transformer assembly. Figure 2-4 shows typical connections.
2.4 Set Overcurrent Protection For models with integral overcurrent protection, the overcurrent protection must be set prior to operation. The equipment is shipped from the factory with a long-time current setting of 100% (of the equipment rating) and maximum short-time/ instantaneous current and time delay settings. Note: Do not energize this equipment until device settings have been verified to ensure proper system protection and coordination.
2.6 Seismic Certification Automatic transfer switches with seismic certification must be installed according to the instructions in this section. Also refer to ADV-7456, the Certificate of Compliance provided with the ATS, and the installation (ADV) drawings for the transfer switch. Abbreviations: ACI: American Concrete Institute IBC: International Building Coder SDS: Design spectral response acceleration at short period, as determined in Section 1615.1.
2.7 Manual Operation Check DANGER 2.7.1 Manual Operation Test Procedure, 100--1200A MCCB Models Manually operate the transfer switch mechanism, depending on mechanism type, as described below. 100--800 Amp Units: Hazardous voltage. Will cause severe injury or death. Only authorized personnel should open the enclosure. WARNING Hazardous voltage. Backfeed to the utility system can cause severe injury, death, or property damage. See Figure 2-5.
2.7.2 Manual Operation Test Procedure, 800--4000 A ICCB Models See Figure 2-7. Manually operate the power switching units as follows: Push the breaker’s TEST pushbutton. The breaker should then open. Press the reset button to reset the breaker. 1 Repeat for the other power switching unit. 2 1 GM71058 1. Manual operation knob 2. Yoke Figure 2-6 1 1000--1200 Amp MCCB Manual Operation ADV--7884 1.
2.8 Controller Connections The controller is mounted in a plastic housing on the inside of the transfer switch enclosure door. DANGER Figure 2-8 shows the locations of the connectors on the controller. It is not necessary to open the cover to access the Ethernet, Modbusr, and input/output connectors. Opening the cover. If necessary, open the plastic housing by pushing up on the latch on the bottom of the cover and swinging the cover up and out. The cover is hinged at the top.
2.8.1 Controller Input and Output Connections 2.8.2 The controller provides connections for two programmable inputs and two programmable outputs. See Figure 2-8 for the connector location and Figure 2-9 for the I/O connection specifications. Each input has a signal and a return connection. The outputs are C form contacts with ratings of 500 mA @ 120 VAC. See Figure 2-10 for connections. Use #12--24 AWG wire and tighten the connections to 0.5 Nm (4.4 in. lbs.).
2.9 Electrical Wiring DANGER All internal electrical connections are factory-wired and tested. Field installation includes connecting the sources, loads, generator start circuit(s), and auxiliary circuits, if used. Hazardous voltage. Will cause severe injury or death. Refer to the wiring diagrams provided with the transfer switch. Observe all applicable national, state, and local electrical codes during installation.
Drill the entry holes. Cover the transfer switch to protect it from metal chips and construction grit. Then drill entry holes for the conductors at the locations shown on the enclosure drawings. Remove debris from the enclosure with a vacuum cleaner. Note: Do not use compressed air to clean the switch. Cleaning with compressed air can cause debris to lodge in the components and damage the switch. Tighten the lugs. Verify that all connections are consistent with drawings before tightening the lugs.
2.9.2 Engine Start Connection WARNING Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death.
2.9.3 Position-Indicating Contacts Auxiliary position-indicating contacts are available on the ICCB circuit breakers. See Figure 2-15 through Figure 2-17. Some contacts on the circuit breakers are used for factory connections. Refer to the transfer switch wiring diagram for connections. For MCCB position indication, connect to a programmable output and program the output for position indication. See Section 2.8.1 for output connections on the controller.
2.10 Communication and Accessory Connections See Section 4 for accessory and communication connection instructions. 2.11 Functional Tests WARNING Hazardous voltage. Backfeed to the utility system can cause severe injury, death, or property damage. Before energizing the transfer switch, verify that both the normal and emergency contacts are not left in the closed position. The functional tests are a necessary part of the transfer switch installation. Perform the functional tests described in Section 5.
Section 3 Three-Source Systems 3.1 Three-Source Systems The Decision-Makerr MPAC 1500 controller is required for three-source systems. A three-source system provides the means to connect a utility and two generators to a single load. See Figure 3-1. Two generators and two transfer switches are required. Note: The second transfer switch (ATS2) requires an external battery supply module (EBSM or BOB) to provide power to the controller. See Section 4.3.3.
3.5 Three-Source System Connection DANGER commands for generator sets 1 and 2. Observe the polarity of all connections shown in Figure 3-2. Use wire sizes from #14 AWG to #20 AWG for EBSM and I/O module connections. a. Connect the ATS2 engine start contacts to the engine start circuit on generator set 2 (G2). Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure. Servicing the transfer switch. Hazardous voltage can cause severe injury or death.
G1 SINGLE LINE DIAGRAM G2 ATS2 U N ATS1 N L ENGINE START TO G2 E L E ENGINE START N/C NOTE: THE CLOSED IN EMERGENCY AUXILLIARY CONTACT THAT IS USED IN THE ENGINE START CIRCUIT OF THE ATS MUST BE REMOVED FROM THE CIRCUIT WHEN USED WITH THIS THREE SOURCE CONTROL SCHEME. REFERENCE ATS WIRING DIAGRAM FOR CONNECTIONS. LOAD LEGEND Note: ATS2 requires an external battery module to maintain power to the controller.
ATS1 6 12 3 Source System Disable 7 Connect Output 1 terminals TB1-5 and TB1-6 on ATS 1 to Input 1 terminals TB1-1 and TB1-2 on ATS2. 1 Assign ATS 1 main logic board output 1 to 3 Source System Disable. ATS1 TB1 on logic board Assign ATS2 main logic board input 1 to 3 Source System Disable. 1 7 G1 ES Connect one normally closed output from ATS2 to G1 engine start (ES) connections. Assign to Engine Start Source N.
Section 4 Communication and Accessory Connections 4.1 Introduction 4.2.2 This section explains the connection of communication cables and factory-installed accessories. Modbus Connection DANGER Also refer to the following documentation for instructions to install, connect, and operate optional accessories. D Transfer switch wiring diagrams. Hazardous voltage. Will cause severe injury or death.
Use Modbus RTU (remote terminal unit) protocol for communication through the serial port. A map of the Modbus codes for this controller is available. Contact your local distributor/dealer. Note: Modbusr applications require a Modbus software driver written by a trained and qualified systems programmer.
4.2.3 Ethernet Connection The Ethernet communication board allows the transfer switch to be connected to a building’s Ethernet network to communicate with personal computers connected to the same subnet. DANGER Note: For an ethernet connection, obtain an IP address and subnet mask number from the local system administrator. Hazardous voltage. Will cause severe injury or death. Ethernet Port. The ethernet port is a standard RJ-45 jack. See Figure 4-5 for the location of the Ethernet port.
Modbusr TCP/IP Category 5e PC IP xx.xx.xx.02 Ethernet Network Modbusr TCP/IP Category 5e MPAC Controller with Ethernet comm. board IP xx.xx.xx.03 Note: The PC and the ATS must be on the same subnet. Note: A crossover cable can be used to connect the PC to the ATS controller through the Ethernet port. Figure 4-6 Remote Network (Ethernet) Connection Ethernet Network Modbusr TCP/IP PC IP xx.xx.xx.
4.3 Accessory Modules (Option Boards) 4.3.1 Accessory Module Mounting Mount the accessory modules on the module mounting plate. Starting at the end of the module mounting assembly nearest the cable connection, install any I/O modules first, then install the alarm board, if used. The external battery module, if used, must be the last module. See Figure 4-9. The alarm board has a fixed Modbus address = 5. DANGER Hazardous voltage. Will cause severe injury or death.
4.3.2 Input/Output (I/O) Modules 1 2 Two types of input/output modules are available. The standard I/O Module has two inputs and six outputs. The high-power I/O module has two inputs and three outputs. See Figure 4-10 through Figure 4-13 for I/O module illustrations and specifications. 3 1 2 3 4 1. 2. 3. 4. Input LEDs 1 and 2 Input connector (see Figure 4-14) Output connector Output LEDs 3--5 for outputs 1, 2, and 3 Figure 4-12 4 1. 2. 3. 4.
Use 14-24 AWG cable to connect to inputs and outputs. See Figure 4-14. 4.3.3 LEDs on the module circuit board light to indicate that each input or output is active. The external battery supply module kit allows connection to the generator set engine start battery(ies) or other batteries to provide 12 VDC power to the ATS controller. The EBSM is also referred to as the battery option board (BOB). Note: Each I/O module must have a unique address.
The EBSM/BOB produces 2 amps at 12 VDC with 9--36 VDC input. The EBSM/BOB input is reverse-polarity protected. The EBSM/BOB outputs a low battery voltage signal when the external battery voltage falls below 11 VDC for a 12-volt system or 22 VDC for a 24-volt system. A module mounting kit is required for installation of the external battery supply module. See Section 4.3.1.
Alarm Board DIP Switches Alarm Operation, Chicago Alarm Mode There are four DIP switches on the alarm module board. Some of the switches are not used. See Figure 4-19. To enable the preferred source selection, set DIP switch 1 to ON. If the supervised transfer switch is installed on the ATS, set DIP switch 2 to ON. Chicago Alarm mode requires the horn to sound and a lamp or LED to light when the switch is in the emergency (non-preferred) position.
4.4 Heater DANGER 1 Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure. Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers.
4.5 Other Accessories Refer to the following documentation for instructions to install, connect, and operate optional accessories. HYGROSTAT D Transfer switch wiring diagrams. D Installation instructions accessory kits. CIRCUIT BREAKER provided with loose D Controller Operation Manual. See List of Related materials in the Introduction section of this manual for document numbers.
Notes 42 Section 4 Communication and Accessory Connections TP-6946 3/16
Section 5 Functional Tests 5.1 Introduction Be sure to perform all of the functional tests described in this section before putting the transfer switch into operation. Note: Perform these checks in the order presented to avoid damaging the ATS. Read all instructions on the labels affixed to the automatic transfer switch before proceeding. To complete the installation, follow the instructions in this section to: D Set the time, date, and exercise schedule on the controller.
5.5 Voltage Check The voltage, frequency, and phasing of the transfer switch and the power sources must be the same to avoid damage to loads and the transfer switch. Compare the voltage and frequency ratings of the utility source, transfer switch, and generator set, and verify that the ratings are all the same.
instructions to adjust the generator set. The automatic transfer switch will only function with the rated system voltage and frequency specified on the nameplate. 5.8 System Setup Set the controller’s current time and date. See the controller Operation Manual for instructions. 4. Use a phase rotation meter to check the phase rotation at the source terminals. Rewire the transfer switch source terminals to obtain the correct phase sequence if necessary.
Notes 46 Section 5 Functional Tests TP-6946 3/16
Section 6 Operation 6.1 6.1.1 Transfer Switch Operation Normal Operation Under normal conditions, the load is energized from the utility supply through the closed utility transfer power switching device. If the utility power fails, the generator will start and the load will be reenergized via the closed generator transfer power switching device. Refer to the controller operation manual for the sequence of operation. In the normal operating mode, the service disconnect switch must be in the AUTO position.
Original Transformer Assemblies (Service Disconnect to EMERGENCY only) Revised Transformer Assemblies (Service Disconnect to OFF [) TR* * * * GM69797-KA1 (MCCB) GM94796-AA1 (MCCB) * * * GM69797-KA2 (ICCB) GM94796-AA2 (ICCB) * Asterisk indicates differences that can be used to identify original or revised transformer assemblies.
6.2.3 Transformer Assemblies Service disconnect to OFF units are equipped with revised transformer assemblies and controller firmware version 1.10. See Figure 6-2 for illustrations of original and revised transformer assemblies. Orignal Transformer Assemblies Transfer switches equipped with an original transformer assembly GM69797-KA1 or GM69797-KA2 must use the Service Disconnect to Emergency position only. The transformer kit number is not printed on the nameplate.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first.
6.3.1 Service Disconnect Procedure, Service Disconnect to Emergency The service disconnect switch has two positions: AUTO and SERVICE DISCONNECT. Follow the procedures in this section carefully and observe the safety precautions when performing a service disconnect before maintenance or service. Watch the LED indicators on the ATS controller to check the ATS position and source status during the procedures. 1.
Service reconnect procedure when Normal source is NOT available Manually operate the ATS to the Normal position before returning the generator set to service, as described in the procedure below. 1. Verify that the generator set master switch is in the OFF position. 2. Open the ATS enclosure and manually transfer the ATS to utility. (Open the emergency breaker and close the utility breaker. See Section 2.7 for instructions, if necessary.) Then close and secure the enclosure door. 3.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first.
6.4.1 Service Disconnect Procedure, Service Disconnect to OFF The service disconnect switch has two positions: AUTO and SERVICE DISCONNECT. Follow the procedures in this section carefully and observe the safety precautions when performing a service disconnect before maintenance or service. Watch the LED indicators on the ATS controller to check the ATS position and source status during the procedures.
Transfer Switch in EMERGENCY Use this procedure if the transfer switch is in the Emergency position. 6.4.2 Service Reconnect Procedure, Service Disconnect to OFF DANGER 1. Move the service disconnect control switch located on the door of the transfer switch to the SERVICE DISCONNECT position. 2. The engine start signal is maintained briefly to allow the emergency breaker to open. The engine start signal is then removed. 3. Wait for the generator set to shut down.
6.5 Control Circuit Isolation Switch The two-position control circuit isolation switch removes utility power from the ATS controller assembly. Perform the service disconnect procedure explained in Section 6.3 or 6.4 before operating the control circuit isolation switch. Review the notes and precautions in Section 6.3 or 6.4 before proceeding. See Figure 6-7 for switch positions. The control circuit isolation switch is mounted on the transformer assembly. See Figure 6-8.
6.5.1 Control Circuit Isolation and Reconnection for Service Disconnect to Emergency Units Control Circuit Reconnect Procedure (with normal source available) DANGER Note: This section describes control circuit isolation and reconnection procedures for transfer switches that use the Service Disconnect to Emergency position. Go to Section 6.5.2 for transfer switches that use the Service Disconnect to OFF position. Hazardous voltage. Will cause severe injury or death.
Control Circuit Reconnect Procedure (when normal source is NOT available) DANGER 6.5.2 Control Circuit Isolation and Reconnect for Service Disconnect to OFF Units Hazardous voltage. Will cause severe injury or death. Note: This section describes control circuit isolation and reconnection procedures for transfer switches that use the Service Disconnect to OFF position. Go to Section 6.5.1 for transfer switches that use the Service Disconnect to Emergency position.
Control Circuit Reconnect Procedure (with normal source available) DANGER Control Circuit Reconnect Procedure (when normal source is NOT available) DANGER Hazardous voltage. Will cause severe injury or death. Hazardous voltage. Will cause severe injury or death. Only authorized personnel should open the enclosure. Only authorized personnel should open the enclosure. Note: Review the precautions and notes in Section 6.4 before proceeding.
Notes 60 Section 6 Operation TP-6946 3/16
Section 7 Changing the Service Disconnect Position 7.1 Introduction Orignal Transformer Assemblies The service disconnect operation for Model KEP service entrance rated automatic transfer switches equipped with the Decision-Makerr MPAC 1500 controller has changed. When the transfer switch is put into service disconnect mode: Transfer switches equipped with an original transformer assembly GM69797-KA1 or GM69797-KA2 must use the Service Disconnect to Emergency position only.
Original Transformer Assemblies (Service Disconnect to EMERGENCY only) : Revised Transformer Assemblies (Service Disconnect to OFF [ ): TR* * * * GM69797-KA1 (MCCB) GM94796-AA1 (MCCB) * * * GM69797-KA2 (ICCB) GM94796-AA2 (ICCB) * Asterisk indicates differences that can be used to identify original or revised transformer assemblies.
7.2 Changing the Service Disconnect Position In some applications, it may be necessary to change the service disconnect position on the transfer switch. Example 1: If you update the controller firmware or replace the controller on a unit that is equipped with an original transformer assembly, GM69797-KA1 or GM69797-KA2, you will need to change the service disconnect position setting on the controller back to Emergency.
7.2.1 Procedure to Change the Service Disconnect Position Setting on the Controller 1 1. Use a USB cable to connect your laptop PC to the MPAC controller. See Figure 7-3. 2. Start SiteTecht and wait for it to connect to the MPAC controller. 3. Click on Set Mpac Password and enter the distributor password. Obtain the password from the Kohler Power Systems Generator Service Department. 4. Find the Service Disconnect Position setting in the ATS Connection Configuration group. See Figure 7-4. GM85888 1.
7.2.2 Procedure to Disconnect the Engine Start Bypass Circuit Transfer switches using the new transformer assemblies include an engine start bypass circuit that prevents the ATS from sending an engine start signal to the generator when it is placed in the Service Disconnect position. If it is necessary to configure the ATS to operate in the Service Disconnect to Emergency position, this bypass circuit must be disconnected from the controller’s input connection.
6. Use cable ties to secure the leads out of the way. 7. Reconnect power to the control circuit. Follow the instructions in Section 6.5. 8. Use Kohlerr SiteTecht software to change the service disconnect position setting to Emergency. See the procedure in Section 7.2.1. 7.2.
1 GM95677 1. Disconnect and tape off lead USD at QCON1.
Procedure for ICCB Models 1. At the generator (emergency) circuit breaker inside the transfer switch, find lead G-22, which is connected to terminal 22 on the circuit breaker auxiliary contact terminal block. See Figure 7-8. Disconnect lead G-22 and reconnect it to terminal 24. 2. At the utility (normal) circuit breaker, disconnect leads G-21 and U-21 from the circuit breaker auxiliary contact terminal block. Crimp leads G-21 and U-21 together. DETAIL A 1 1 TO P3 2 1.
7.2.4 Final Steps 1. On the enclosure door, change the service disconnect switch decal to show that the ATS now uses the Service Disconnect to Emergency position. Use a permanent marker or apply a new label over the existing decal that says: Service Disconnect transfers to EMERGENCY source and starts the generator set. 2. Return the generator set to service and place in AUTO. 3. Test the system operation.
Notes 70 Section 7 Changing the Service Disconnect Position TP-6946 3/16
Section 8 Performance Test Form Conduct the performance tests outlined in Sections 5.3 and 5.4, and record the results on the following form. This form must be retained by those in charge of the Date Personnel building’s electrical installation in order to be available to the authority having jurisdiction.
Notes 72 Section 8 Performance Test Form TP-6946 3/16
Appendix A Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ABDC AC A/D ADC adj. ADV Ah AHWT AISI ALOP alt. Al ANSI AO APDC API approx. AQMD AR AS ASE ASME assy. ASTM ATDC ATS auto. aux. avg. AVR AWG AWM bat. BBDC BC BCA BCI BDC BHP blk. blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CAN CARB CB cc CCA ccw. CEC cert.
k K kA KB KBus kg kg/cm2 kilo (1000) kelvin kiloampere kilobyte (210 bytes) Kohler communication protocol kilogram kilograms per square centimeter kgm kilogram-meter kilograms per cubic meter kg/m3 kHz kilohertz kJ kilojoule km kilometer kOhm, k kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com TP-6946 3/16b E 2014, 2016 by Kohler Co. All rights reserved.