Installation Guide

NXT-WI Wiegand-Only Reader Interface Module
Installation Guide
Page 1 of 3 P/N: 02509-001 Rev. B
1.0 Wiring and Layout Diagrams
1.1 Reader Interface Module (RIM)
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
P/N: 02509-002 Rev. B
NXT-WI Wiegand-Only RIM Installation Drawing
J2
1 2
3
4
5 6 7 8
Reader LED Configuration
Wiegand Reader - D5
Reader Type
D10 - 12VDC
Reader Power
Selected
12VDC
5VDC
J2 Jumper Settings
for Reader Power
RS-485 Comm - D8
1
2
3
4
5
6
7
8
n/a
Beeper
LED
n/a
+ 12 VDC
Ground
Data0
Data1
n/a
Blue
Brown
n/a
Red
Black & Shield
Green
White
n/a
Beeper
Red LED
Green LED
+ 12 VDC
Ground
Data0
Data1
n/a
Blue
Brown
Orange
Red
Black & Shield
Green
White
Single-Line LED Dual-Line LED
Wiegand Reader
* Farpointe
Wire Color
* Farpointe
Wire Color
ConnectionConnectionPin #
* Please refer to the reader
manufacturers documentation
for other Wiegand reader types.
D1 - Single-line, three color LED
(firmware default)
D2 - Dual-line, three color LED
(downloadable firmware)
D3 - Single-line, two color LED
(not supported at this time)