User's Manual

MOUNTING
WIRING DIAGRAM
ON-LRD-509
DIM
L N
Neutral
Line
DIM
DIM
N
L
Gray
Violet
Red
White
Black
BALLAST
LED DRIVER
DIM
DIM
N
L
BALLAST
LED DRIVER
1
2
This device can be integrated with a luminaire or
mounted on the ceiling in various formats via specific
mounting bracket. Please refer to the mounting
instruction sheet separately attached for more details
about mounting options available.
OPERATION
The ON-LRD-509 employs a digital PIR sensor together
with an ALS to detect occupancy status and ambient
light level. The sensor not only controls the connected
lighting as programmed when it detects the presence of
an occupant/vehicle, but also broadcasts an OCC
signal to other devices of the group to activate the
respective controls. Each sensor can be assigned to be
member of maximum 4 groups for coordinated control.
Non-dimmable Lighting (ON-OFF Switching only)
0-10V Dimmable Lighting
ON-LRD-509
DIM
L N
Load
Line
Neutral
White
Red
Black
NOTE:
Use 0/1-10V dimmable driver/ballast to enable
dimming control.
Ensure to connect the LINE and NEUTRAL wires
correctly. Reverse connection may damage the
sensor permanently.
Ensure TOTAL isolation between DIM+/DIM- and
GROUND of line voltage to avoid damaging the
sensor.
Always conduct factory test with GROUND connected.
1.
2.
3.
4.
OVERVIEW
The ON-LRD-509 series is a fundamental device of OS-NET wireless mesh network solution packed with multiple functionalities including occupancy/vacancy
sensing, daylight harvesting, bi-level StepDIM or continuous SmartDIM, and wireless network communication for top-notch intelligent lighting control.
Numerous design innovations allow this device to be flexibly integrated with an OEM luminaire, or mounted on the ceiling in a variety of options. Interchangeable lenses allow the
sensor to be mounted at various heights with different detection patterns for all applications. All functionalities can be easily and intuitively configured by a 2-way remote
programmer from the floor. With ON-LRD-509, you can effortlessly achieve energy efficient, code-compliant smart lighting control through a state-of-the-art wireless mesh network
synchronously established while installing the OS-NET enabled lighting.
APPLICATION NOTESSPECIFICATIONS
The sensor is more sensitive to the movements
“crossing” the detection zones than “toward” or
“away” the sensor unit. To obtain better sensitivity,
avoid placing the sensor in line with occupant path.
The closer the movement is to the sensor, the more
sensitive the sensor is. The higher the sensor is
installed, the larger movement is required to be
detected.
Ensure to place the sensor at least at 1.5m (5 ft.) away
from air supply ducts as rapid air flow may cause false
activations.
The sensor cannot “see” the movements behind
obstacles, such as tall furniture, shelf, glass or
partitions. Avoid placing the sensor where
obstructions may block the sensor’s line of sight.
The partition of workstation could block the sensor
view to occupant movements, it is best to place the
sensor over the intersection of workstation. For large
open office, place multiple sensors so that there is
overlap coverage with each adjacent sensor.
To obtain optimal wireless communication range,
avoid enveloping the sensor with a metallic enclosure.
1.
2.
3.
4.
5.
6.
P/N: 058-50906-001 Printed in Taiwanwww.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
Line Voltage OS-NET Sensor
ON-LRD-509 series
INSTALLATION INSTRUCTIONS
Risk of Electric Shock - Disconnect power supply before servicing.
Do NOT touch the square window of infrared sensor under the lens
assembly.
Open Type Photoelectric Switches.
WARNING & CAUTION
Risque de choc électrique - Débranchez l'alimentation
avant l'entretien.
Ne PAS toucher la fenêtre carrée de capteur infrarouge
sous l'ensemble de l'objectif.
Ouvrir Type commutateurs optoélectroniques.
AVERTISSEMENT & PRUDENCE
w/Lens A/B/C w/Lens D
w/Lens Gw/Lens F
*More lens options are available for this sensor.
Please refer to the Lens Datasheet for more details.
Power supply
Infrared sensor
Dim control
HIC protection
Wireless protocol
Radio frequency
Number of Channel
Radio range
Radio Power Output
Detectable speed
Mounting height
Detection range
Remote range
Op. humidity
Op. temperature
Dimensions
120/230/277VAC, 50/60Hz
Digital quad-element pyroelectric sensor
0-10V, isolated, max 25mA
Max. 80A for 16.7msec.
Modified Zigbee Light Link (ZLL)
2405~2480Mhz
16ch
15/90 m @indoor/outdoor, open space
6.98dBm
0.15 ~ 3 m/sec. (0.5~10 ft./sec.)
Subject to the lens applied
As per lens applied and mounting height
Typ. 10 m (33 ft), indoor with no backlight
Max. 95% RH
-40°C~70°C (-40°F~158°F)
Ø60 x H37mm (Ø2.36”x H1.45”)
Maximum Load
-Incandescent/Halogen
-Fluorescent Ballast/CFL
-Ballast Electronic (LED)
120VAC
800/*500W(VA)
800/*500W(VA)
540/*500VA
5A
5A
5A
230VAC
1200/*750W(VA)
1200/*750W(VA)
1200/*750VA
277VAC
*Max load for operating temperature at 55°C~70°C(131°F~158°F)
Federal Communication Commission Interference Statement FCC ID: NRIRS350900
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: Any changes or modifications not expressly approved by the
party responsible for compliance could void the user's authority to operate
this equipment.
This transmitter must not be co-located or operating in conjunction with
any other antenna or transmitter.
Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and
operated with minimum distance 20cm between the radiator & your body.
Install the sensor at least 1ft. away from any occupant.
Dim voltage tolerance is ±5%