Table of Contents Glossary 3 Earth Ground 4 Device Handling and Cleaning 5 IXM Install Kit for MYCRO, SENSE 2 and TOUCH 2 6 IXM Install Kit for MERGE 7 MYCRO 8 SENSE 2 10 TOUCH 2 12 MERGE 14 MERGE CR 16 I/O Cable: Top Connector Pin Out for MYCRO, SENSE 2 and TOUCH 2 18 I/O Cable: Bottom Connector Pin Out for MYCRO, SENSE 2 and TOUCH 2 19 I/O Cable: Connector Pin Out for MERGE 20 Hardware Tools Required For Installation 21 Hardware Installation Steps 22 Connections for Power 26
Glossary ACP Access Control Panel COM Common DAC Door Access Control DOS Door Open Schedule DSP Door Strike Power EGND Earth Ground ESD Electrostatic Discharge GND Ground IXM INVIXIUM LED Light Emitting Diode NC Normally Closed NO Normally Open OTG On-the-Go RLY Relay RX Receive SGND Signal Ground SPI Specific Purpose Input SPO Specific Purpose Output TX Transmit USB Universal Serial Bus WDATA Wiegand Data WGND Wiegand Ground VDC Volts Direct Current VIN+ Power
Earth Ground For protection against ESD, which may cause damage or malfunction to the IXM device, Invixium recommends the use of the ground connections between each IXM device and a high quality Earth Ground available at the install site. Please note that installation of any IXM device should be performed by licensed electricians. An Earth Ground wire with lug is provided in the IXM Install Kit. The lug of the Earth Ground wire should be fastened with a screw to the front of the mounting plate.
Device Handling Do's Handle with care, ensure not to drop or step on the device. Perform occassional cleaning to eliminate a build-up of dust, dirt, oil and residual grime. Device Handling Don'ts Do not install in areas with direct sunlight, high levels of humidity, extreme dust or flammable vapours. Do not allow magnetic objects to come in close contact to any device. Do not install near any heating elements or equipment.
The IXM Install Kit for MYCRO, SENSE, TOUCH, SENSE 2 and TOUCH 2 includes: DO LP HI N IXM INSTALL KIT PHIN DO LP DOL DOL PHIN HI N HIN DOLP DOL HIN LP PHIN DO LP HI N DO HI N DO LP DOLPHI LP HI N Micro USB-On-the-Go Cable DO DO LP HIN DO DOL PHIN LPH IN N INVIXIUM Dolphin Crimps (qty 24) Wall Mounting Screws (qty 4) Metal Mounting Plate Screw (qty 1) INVIXium - Hex Key Earth Ground Wire INVIXIUM Copyright Metal Mounting Plate Wired Back Cover Micro USB Extension C
The IXM Install Kit for MERGE includes: DO N HI DO LP LP HIN DO DO HIN DOL P LPH IN DOLPHI LP N HI N IXM INSTALL KIT Metal Mounting Plate Screw (qty 1) Wall Mounting Screws (qty 4) Dolphin Crimps (qty 10) Wired Back Cover INVIXium - Hex Key Metal Mounting Plate Micro USB Extension Cable (4 ft/1.
MYCRO Rugged Front Shell Industrial Grade Connectors Multi-color LEDs Sensor Solid Metal Back Plate Surge Protection as per EN55024 8
Front View Side View 46.3 30 Front View Side View Angled Front View INVIXIUM recommends printing this page in Actual Size MYCRO Product & Mounting Plate Actual Dimensions in mm 110 82.1 162 168 48 38.5 41.70 4.20 8.
SENSE 2 Proximity Sensor Rugged Front Shell Industrial Grade Connectors Multi-color LEDs Solid Metal Back Plate Lumidigm Sensor Multispectral Imaging Fingerprint Sensor Surge Protection as per EN55024 10
Front View Side View 30 Front View Side View Angled Front View INVIXIUM recommends printing this page in Actual Size SENSE 2 Product & Mounting Plate Actual Dimensions in mm 110 46.08 82.1 194.9 199.7 49 45.20 5.40 51.
Proximity Sensor TOUCH 2 Rugged Front Shell 5 MP Camera Super Strong Protective Glass Industrial Grade Connectors Multi-color LEDs Optically Bonded Cap Touch Screen Sensor Solid Metal Back Plate Surge Protection as per EN55024 12
Front View Side View 51.85 30 Front View INVIXIUM recommends printing this page in Actual Size TOUCH 2 Product & Mounting Plate Actual Dimensions in mm Side View 110 46.08 82.1 194.9 199.7 49 45.20 5.
MERGE Super Strong Protective Glass NEXT Sensor Active Thermal Sensor Optically Bonded Cap Touch Screen Multi-color LEDs Industrial Grade Connectors 14
Front View 47 Side View 37 Front View Side View Angled Front View 110 INVIXIUM recommends printing this page in Actual Size MERGE Product & Mounting Plate Actual Dimensions in mm 82.10 172.14 178 11 42.50 3.20 30 7.
MERGE CR Multi-color LEDs Industrial Grade Connectors 16
Front View 47.19 Side View Front View Side View 30 Angled Front View 110 INVIXIUM recommends printing this page in Actual Size MERGE CR Product & Mounting Plate Actual Dimensions in mm 82.10 135.89 142.94 142.94 17.49 40.50 3.20 7.65 26.81 34.
I/O Cable: Top Connector Pin Out for MYCRO, SENSE, TOUCH, SENSE 2 and TOUCH 2 Wired Back Cover RLY_NO RLY_COM RLY_NC ACP_LED1 ACP_LED2 ACP_LED_GND DAC_IN1 DAC_IN2 DAC_IN3 DAC_GND DSP DAC_OUT SPI_GND SPI_3 SPI_2 SPI_1 SPO_1 SPO_2 SPO_3 SPO_GND Front View Wire Color Back View Application Label 2 SPO Line 1 SPO_1 RLY_COM 4 SPO Line 2 SPO_2 Relay NO RLY_NO 6 SPO Line 3 SPO_3 7 ACP LED 1 Feedback ACP_LED1 8 Ground for SPOs SPO_GND 9 ACP LED 2 Feedback ACP_LED2 10 SPI Line 1 SPI_1
I/O Cable: Bottom Connector Pin Out for MYCRO, SENSE, TOUCH, SENSE 2 and TOUCH 2 Wired Back Cover EGND VINVIN+ RS-485_T TCP/IP RJ45 Receptacle WGND WDATA_OUT1 WDATA_OUT0 WDATA_IN1 WDATA_IN0 RS232_RX RS232_TX SGND RS-485+ (B) RS-485- (A) Front View Back View Pin Application Label Pin 1 Power (+12-24 VDC) VIN+ 3 Power Ground 5 7 Wire Color Application Label 2 RS-232 Data Receive RS-232_RX VIN- 4 RS-232 Data Transmit RS-232_TX Earth Ground EGND 6 Signal Ground SGND RS-485 Termina
I/O Cable: Connector Pin Out for MERGE EGND VINVIN+ Wired Back Cover DGND WDATA_OUT1 DAC_IN2 DAC_IN3 TAMPER RLY_NO SGND RLY_NC RLY_COM WDATA_IN1 WDATA_IN0 Front View Back View DAC_IN1 RS485- (A) RS485+(B) DAC_OUT SPO_1 WDATA_OUT0 Application Label Pin Application Label 1 Power (+12-24 VDC) VIN+ 2 RS-485 Inverting Line RS485- (A) 3 Power Ground VIN- 4 RS-485 Non-Inverting Line RS485+(B) 5 Earth Ground EGND 6 Door Access Control Output DAC_OUT 7 Ground for Wiegand DGND 8 Spec
Hardware Tools Required For Installation Hammer* Battery powered Screwdriver Power Drill* Measuring Tape Ratchet-style Crimping tool Pencil Manual Screwdriver Installation of any IXM device should be performed by licensed electricians. *Depending on the mounting surface, the Power Drill and Hammer may not be required.
1 Ensure Power is Off 2 IXM Install Kit This protects the device being installed. Remove the following items from the kit: N DO LP HI DOLP DOLP DOLP HIN DOLP HIN HIN DO LP HIN ON HIN LP HIN DO LP HIN DO LP HIN DO LP HIN DO DOLPH DO LP HIN DO DOLP HIN LPH IN IN OFF INVIXIUM recommends the use of the 4 circular holes for mounting.
5 Get Wires 6 Insert Screws Get access to the installation wires either from behind the wall of from the wiring conduit. Feed wires through the square hole of the mounting plate. Align the holes of the mounting plate with the wall anchors and attach the mounting plate with the screws provided in the IXM Install Kit. INVIXIUM recommends the use of an electric or battery-powered screwdriver for this step.
8A Make the Connections Connect the required wires using the Dolphin® crimps provided in the IXM Install Kit (or any similar crimps) and a ratchet style crimping tool. Insert two wires (no stripping required) into the open end of the crimp and then using the crimping tool, clamp down on the middle of the crimp. DO HIN LP Earth Ground Wire Lug 8B Connect Earth Ground Connect the lug of the Earth Ground wire directly to the front of the mounting plate using one of the Wall mounting screws.
9 Attach the Device 10 Secure the Device Take the IXM device and unscrew the Temporary Back Cover, keeping the screws handy. Connect the Wired Back Cover to the back of the device by lining up the connectors. Secure the Wired Back Cover with the same screws. Next, hang the IXM device onto the mounting plate as shown in the series of diagrams below. Finally, secure the device on the bottom to the mounting plate with the Metal Mounting Plate screw provided in the IXM Install Kit.
Connections for Power MYCRO UPS DC Power Supply VIN+ VIN- EGND INVIXIUM recommends: • 12-24 VDC regulated power supply (Safety tested and FCC/IC/CE certified) • Dedicated Power Supply for each IXM device (minimum 1A) • Dedicated Power Supply for each IXM device powering door strike (minimum 1.5A) • Use of a battery back-up or UPS with built-in surge protection • If sharing power supplies, ensure that each device is supplied with minimum 1A per device (i.e.
Connections for Power Over Ethernet (PoE) Available on MERGE, SENSE, TOUCH X, SENSE 2 and TOUCH 2 SENSE 2 TOUCH 2 INVIXIUM recommends: • A centralized Power Sourcing Equipment (PSE) for full PoE deployments (not included) • Use of a battery back-up or UPS with built-in surge protection Ethernet/PoE Connections TX+ TXRJ45_PIN4 Both IEEE 802.3af power transmission modes (A and B) are supported.
Ethernet and Wi-Fi Communication IXM WEB Ethernet: • Switch/Router required • CAT 5 cabling or better WiFi: • Wireless router to LAN/WAN • 802.
RS-485 Network Communication INVIXIUM recommends: • Daisy chain configuration • Maximum 31 devices in the network • Both RS-485 converter and the last device in the chain should be terminated (not included, refer to NOTE below for correct Resistor vaues) • • Connect the IXM device to PC via RS-485-to-Serial (RS-232 or USB) Converter Maximum cable length of 1200m (4000 ft.
Serial Communication IXM WEB 4 5 3 1 TOUCH 2 2 RS SG N 23 D 2_ RX RS 23 2_ TX USB-to-Serial B-to-Serial Converter RS-232: • Connect IXM device directly to the DB9 Serial port of the PC (if available) • DB9 connectors and cables are not included RS-232 Connections RS-232_RX MYCRO, SENSE 2 and TOUCH 2 only RS-232_TX SGND NOTE INVIXIUM Copyright 2019 30
USB Communication ommunication SENSE 2 Host PC Micro USB Cable USB: • Connect ect a Flash Drive via Micro USB OTG cable and perform functions like upgrading firmware and downloading transaction logs • USB port can also be used to connect to a PC running IXM WEB via Micro USB cable • Driver installation is required and will automatically initiate once the device is connected INVIXIUM Copyright 2019 31
Access Control Panel Connections for MERGE MERGE WDATA_OUT0 WDATA_OUT1 DGND Wiegand Connections ACP: • Wiegand connections available for ACP operation • INVIXIUM recommends the use of Wiegand Output Data 0, 1 and GND connection WDATA_OUT0 WDATA_OUT1 DGND INVIXIUM Copyright 2019 32
Access Control Panel Connections for MYCRO, SENSE, TOUCH, SENSE 2 and TOUCH 2 TOUCH 2 3 ACP_LED1 3 ACP_LED2 ACP_LED_GND WDATA_OUT0 WDATA_OUT1 WGND ACP: • LED and Wiegand connections available for ACP operation • INVIXIUM recommends the use of Wiegand Output Data 0, 1 and GND connection NOTE ACP_LED signals can be used if available on the Access Control Panel. IXM devices support up to 2 wires + GND for LED status.
Door Access Control Connections for MYCRO, MERGE, SENSE, TOUCH, SENSE 2 and TOUCH 2 TOUCH 2 RLY_NO Door Strike Snubber Diode RLY_COM Door Strike Power Supply DAC_IN1 Door Contact DAC_OUT DAC_OUT Request to exit DAC_IN2 *Max Relay Rating = 1 Amp @ 24 VDC DAC: • INVIXIUM recommends a separate power supply for Door Strike (not included) for this configuration • Snubber Diode required for Door Strike (not included) • Example above shows use of RLY_NO, but RLY_NC may be used instead if required by the D
DAC Connections for Device Powers Door Strike (SENSE 2 and TOUCH 2 only) TOUCH 2 RLY_NO Door Strike Snubber Diode RLY_COM - + DAC_GND DAC_DSP DAC_IN1 Door Contact DAC_OUT • DAC_OUT Request to exit DAC_IN2 *Max Relay Rating = 2 Amp @ 24 VDC DAC Connections DAC: • The IXM device powers the door strike in this configuration. Only applicable to SENSE 2 and TOUCH 2.
Software Installation System Requirements To successfully install and run IXM WEB, the system must meet the following minimum requirements: PC Workstation: • • • • • ® ® 2 GHz Intel Pentium 4 or equivalent (2.4 GHz or higher recommended) 4 GB RAM (6 GB or higher recommended) 2 GB Free Hard Disk Space 850 MB Hard Disk Space for x86 systems or 2 GB Hard Disk Space for x64 systems Microsoft ®.NET Version 4.
Software Installation Steps Step 1 Go to ixmweb.invixium.com. Click Get IXM WEB. Provide the required details and Click “Submit”. An email with the latest IXM WEB Package will be sent to the email ID provided. (Contact Support if using a customized solution). Step 2 Download and Extract the package. Run IXM WEB.exe file. Step 3 There are two installation options: Install or Advanced. INVIXIUM recommends selecting INSTALL option for rapid installation.
Step 4 During the installation process, the status of the install will be shown. Step 5 When the installation is complete, click EXIT. IXM WEB icon is now on the desktop. Step 6 Run IXM WEB to launch the application in the default web browser to setup the Database and Admin credentials.
FCC Information to Users (English) This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference. 2. This device must accept any interference received, including interference that may cause undesired operation. NOTICE NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
NOTIFICATION NOTE Cet équipement a été testé et s'est avéré conforme aux limites pour un appareil numérique de Classe B, conformément à la partie 15 des règles de la FCC. Ces limites sont conçues pour fournir une protection raisonnable contre les interférences nuisibles dans une installation résidentielle.
CE Information to Users (English) All INVIXIUM devices have the CE mark for conformance with EMC Directive 89/336/EEC, and Low Voltage Safety Directive 73/23/EEC. Device with RFID components are compliant with R&TTE Directive 1999/5/EC, and are Class 1 Devices. Informations de la CE aux Utilisateurs (en Français) Tous les dispositifs de INVIXIUM ont le marquage CE de conformité à la directive CEM 89/336/CEE et basse tension de sécurité Directive 73/23/CEE.
Warning to Users (English) WARNING Changes or modifications not expressly approved by INVIXIUM could void the user's authority to operate the equipment. Avertissement aux Utilisateurs (en Français) WARNING Les changements ou modifications non expressément approuvés par INVIXIUM pourraient annuler l'autorité de l'utilisateur à utiliser l'équipement.
For Technical or Customer Support issues, please contact your Local Authorized Reseller. For all other inquiries, please contact us at support@invixium.com For detailed information, please visit our website: invixium.com Enjoy the Experience. Some features may vary based on device models. Copyright © 2018, INVIXIUM. All rights reserved. P/N XAD-00E-119-05G INSTALLATION GUIDE INGUIDE INVIXIUM.COM © 2018 Google Inc. All rights reserved. Chrome™ browser is a trademark of Google Inc.