ES 2100 / ES 2200 / IS 3200 / BR 4200 Installation Manual 800-356-2671 | Accutech | www.accutech-ics.com Version 2.37 July 2008 DOC.
Installation Manual Preface i IMPORTANT FCC & DOC INFORMATION Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
ii Preface Installation Manual IMPORTANT: Keep all Televisions, Computers, X-ray equipment, etc. at least 10 feet away from the ES Receiver. This includes equipment located on the other side of walls and doors. Picture the area around the monitored zone as a big globe with the receive antenna as the center. Keep all sources of interference outside this globe. IMPORTANT NOTICE: Do not store ES Sensor(s) within 3 feet of ANY of the sources of electrical noise listed on this page.
Installation Manual UL Addendum (UL 294, BP9480) iii FOR UL LISTED SYSTEMS: MODEL VOLTAGE, V FREQUENCY CURRENT ESI, ESR, ES 120 V 50-60 HZ 1A ESRI, ESRR 12 DC 50 mA TW 24 DC (RMS) 150 mA FPI, FPIB 12 DC 120 mA SAP 12 DC 300 mA GDP 12 DC 500 mA ED 12 DC 100 mA ADD 12 DC 100 mA PS51, PS68 PRI – 120 V SEC – 12 V PRI – 60 HZ SEC - DC PS51 = 5.1 A PS68 = 6.8 A MX, MXB 12 DC 500 mA LT, SB, BR, CB 3.0 DC Standby off = 1.5 uA Standby on = 5 uA Transmit (BR) = 1.
iv UL Addendum (UL 294, BP9480) LT, SB, BR, CB TAD, PTAD CL-8A Installation Manual Long Term (LT), Slotted Back (SB), Band Removal (BR), Cut Band (CB) Tags, small wristwatch sized device, activated Tag sends signal via receiver to the Controller. Tag activator/deactivator, also checks Tag’s battery and assists in finding lost Tags. PTAD is identical to TAD except it does not activate/deactivate tags. Testing with TAD shall be conducted before use daily. Keypad, used to disable audible device.
Installation Manual UL Addendum (UL 294, BP9480) v 9. The magnetic switch shall be UL Listed as a connector and switches. 10. Wiring of FPI must be wired to fail-safe in an alarm or loss of power condition. 11. The Passive Infrared Detector for use with this system is not intended to be used as an intrusion detector. It is for monitoring use only. 12.
vi Installation Manual ICS/ACCUTECH LIMITED WARRANTY Innovative Control Systems, Inc. (ICS) warrants its Accutech™ equipment (Product) against defect in materials and workmanship under normal use for one (1) year from the date of product shipment. Defective equipment will be either repaired or replaced at ICS’ discretion, free of charge to the Customer during the warranty period.
Installation Manual Contents Preface UL Addendum i iii Chapter 1: The Accutech Systems 1-1 Chapter 2: Wire and Cables 2-1 Chapter 3: The Controller 3-1 Chapter 4: The Tx wand antenna 4-1 Chapter 5: The Receiver 5-1 Chapter 6: The Tag 6-1 Chapter 7: The Keypad 7-1 Chapter 8: The Push Button Override (PBO) 8-1 Chapter 9: The Magnetic Switch 9-1 Chapter 10: The Passive Infrared Reader (PIR) 10-1 Chapter 11: Magnetic Locks 11-1 Chapter 12: Fire Panel Interface (FPI) 12-1 C
Installation Manual Chapter 1: The Accutech Systems IMPORTANT: No Security System can replace human vigilance. Creating a safe environment requires the combined efforts of personnel, physicians, security, and patients. Global policies, procedures, and processes on patient care should be discussed and disseminated. Education, communication, and coordination are key. No level of security can replace an informed and knowledgeable staff.
Installation Manual The Accutech Systems ES 2200 System IS 3200 System BR 4200 System Cut Band System How Accutech Systems Work System Components Typical System Configurations Throughout this manual, when referring to the various applications of the system, the term “Tag” is used to represent all possible applications of the system (i.e., a resident, a patient, an infant, pediatrics, or an asset, etc.) Furthermore, the terms “ingress” and “egress” will be encountered.
1-2 The Accutech Systems IS 3200 System The IS 3200 System is the ES 2200 System plus a computer with the Accutech Software installed, a TAD, a Tag Test Station, a Multiplexer, a Power Supply. The IS 3200 System uses IS 3200 System Tags (LT/SB32) that are placed on the monitored resident or asset. Once assigned, the computer associates a name, room number and any other pertinent information about the resident/asset with that Tag.
Installation Manual An optional Loiter function is available to alert staff personnel if a Tag is in a monitored zone (even if the door or elevator is closed) for too long. The time setting is adjustable (10-110 seconds) and is factory set for 15 seconds. An optional Door Ajar function is also available to alert staff personnel if the door in a monitored zone has been held open for too long. The time range can be set for immediate or from 10 to 110 seconds and is factory set for approximately 15 seconds.
1-4 The Accutech Systems closed and a Keypad Reset (or AutoReset jumper in place) to clear. A Loiter alarm occurs when a Tag lingers in the Tx Activation Field. Remove all Tags from the Field and then enter a Keypad Reset (or AutoReset jumper in place) to clear this alarm. A Supervisor alarm occurs when the performance of the system has been altered due to tampering or inadvertent acts such as cut wires, antenna damage or interference, etc. The alarm will reset when the condition is corrected.
Installation Manual The Accutech Systems 1-5 The ES 2200 System Tag The ES 2200 System Tag (Figure 1.1) is a small wristwatch-sized device that is worn by a resident or attached to an asset. LT22 Two models are available: LT = Long Term resident care SB = Slotted Back; to be used on small infants and assets When an ES 2200 System Tag enters a Tx Activation Field (near a monitored zone), the ES 2200 System Tag activates and responds by sending a signal via the Receiver to the Controller.
1-6 The Accutech Systems Installation Manual The BR 4200 System Tag In addition to the functionality of an IS 3200 System Tag, the BR 4200 System Tag (Figure 1.3) will alarm if the band is removed or tampered with in any way. BR 4200 System Tags are attached to infants with a conductive fiber striped-cloth band, are activated/deactivated using a TAD unit, and contain a visual pulse LED. Figure 1.
Installation Manual The Accutech Systems 1-7 Tag barcodes Visual Pulse LED Tag barcodes (Figure 1.7) contain a Tag’s manufacturing history. The Visual Pulse LED indicates the Tag’s current mode (see Table 1.1) Table 1.1 Visual Pulse LED status LED Light Pattern off on Tag LED Status LT, SB Tags None Tag is off. Active, not in zone Active, in zone Figure 1.7 Tag barcode example The coding scheme is as follows: BR, CB Tags None Tag is off.
1-8 The Accutech Systems Installation Manual The Tag Activator/Deactivator (TAD) The Tag Activator/Deactivator (TAD) (Figure 1.8) turns IS 3200 System and BR 4200 System Tags on and off. In addition, the TAD checks a Tag’s battery and assists in finding lost Tags. Figure 1.8 The Tag Activator/Deactivator (TAD) The Tag Test Station (TTS) The Tag Test Station (TTS) (Figure 1.9) is used for Tag assignments. Figure 1.9 Tag Test Station (TTS) The Accutech Software The Accutech Software (Figure 1.
Installation Manual The Accutech Systems 1-9 The Transmit (Tx) wand antenna The Transmit (Tx) wand antenna (Figure 1.12) generates a Tagactivating signal near a monitored zone. This signal is referred to as the “Tx Activation Field.” Figure 1.12 Transmit (Tx) wand antenna (shown without cover) The Receiver Figure 1.13 Receiver (remote shown) The Receiver (Figure 1.13) picks up the signal from an activated tag and relays it to the Controller and the Multiplexer.
1-10 The Accutech Systems Installation Manual The Magnetic Switch The Magnetic Switch (Figure 1.16) is used on a door when alarm activation is not desired unless the door is open when a monitored resident is near that door. Figure 1.16 Magnetic Switch The Passive Infrared Reader (PIR) A Passive Infrared Reader (PIR) (Figure 1.17) is a device that uses a infrared sensor to monitor doors, hallways, corridors and passageways. Figure 1.
Installation Manual The Accutech Systems 1-11 The Multiplexer The Multiplexer (Figure 1.21) relays event information from the Controller to Graphic Display Panels (GDPs) and to a PC with the Accutech Software. Figure 1.21 Multiplexer Power Supply Some installations of Accutech System peripherals require more power than the Controller can provide. In these cases, a Power Supply (Figure 1.22) is added to the system to meet the additional power requirements. Figure 1.
1-12 The Accutech Systems Installation Manual Magnetic Locks Magnetic Locks (Figure 1.25) prevent unescorted egress.
Installation Manual The Accutech Systems 1-13 Typical System Configurations Single Door Example Remote Single Door Example Double Door Example 6 to 8 foot Elevator Example The following are lists of the components used in each of the more typical zones encountered. They are accompanied by graphics that are intended merely as suggestions as to where the components should be placed in relationship to the opening being covered.
1-14 The Accutech Systems Installation Manual Double Door Example (Figure 1.31) (Controller mounted at door, above drop ceiling) 1-Accutech Controller/Receiver (Ch. 3; Ch 5) 2-Accutech Tx wand antennas (Ch. 4) 2-Magnetic Switches (Ch. 9) 1-Keypad (Ch. 7) 1-Local Alarm (Ch. 13) 1-Cable Kit (Ch. 2) Figure 1.31 Double Door Example 6 to 8 Foot Elevator Example (Figure 1.32) (Controller mounted at elevator, above drop ceiling) 1-Accutech Controller/Receiver (Ch. 3; Ch 5) 2-Accutech Tx wand antennas (Ch.
Installation Manual Chapter 2: Wire and Cables
Installation Manual Wire and Cables 2-1 Wire and Cables Cable Door Kit Cable Door Kit SAP and GDP Cable Specifications Fire Panel Cable Specifications Composite Cable Wire Gauge Table Accutech’s Cable Door Kit (see Table 2.1) is the building block for the installation of any type of zone. As options are added additional wire or cables will be required. Each component in the Accutech Systems has its own wiring requirements.
2-2 Wire and Cables Fire Panel Cable Specifications The addition of a Lock requires an interface to the Fire Panel. If future expansion of the system is a possibility, it is recommended that you use a Fire Panel Interface (FPI) unit. If expansion is not possible and there are only one or two zones, a Fire Panel Relay (with 3 sets of dry contacts) can be used instead. If a FPI unit is used, you will need to run a separate 2-conductor cable from one of the zone Controllers to the FPI unit to provide power.
Installation Manual Wire and Cables 2-3 Technical Specifications The technical specifications for the Accutech Composite Cable (Part # 200371) are: A four-element Plenum-rated composite cable Element 1: 18 gauge 4 conductor shielded Mid-Cap (Color code: orange, yellow, white, green) Element 2: 18 gauge 4 conductor non-shielded (Color code: red, black, blue, brown) Element 3: 24 gauge 2 conductor shielded (Color code: gray, violet) Element 4: 25 gauge 14 conductor non-shielded (Color code: white, green, be
2-4 Wire and Cables Installation Manual Table 2.2 Wire Gauge Table - For common system devices The following table indicates the recommended minimum wire gauge for a given length of cable. This table reflects the fact that there are two conductors, power and ground, running to each device. Note: 1000 feet of cable means the supply current travels a total of 2000 feet. Supply Voltage (DC) V Min.
Installation Manual Chapter 3: The Controller
Installation Manual The Controller Controller Specifications Mounting the Controller at the zone Remote Mounting the Controller Hard Wiring Power The System Supervisor Tamper Switch The Controller coordinates and controls all of the devices and functions of the Accutech Systems. Controller Specifications Power Requirements Temperature Weight Location Power Requirements 120V AC, 1.0 amp A dedicated 120V AC, 15-amp circuit with emergency backup is recommended.
3-2 The Controller Mounting the Controller at the zone To mount the Controller, refer to Figure 3.1 and use the following instructions: 1. Mark-out and drill 4 mounting holes in the wall corresponding to the mounting holes of the Controller. 2. Using appropriate hardware for the mounting surface, install the four anchors, then the upper two screws leaving about a 1/8th of an inch exposed. NOTE: The hole spacing on the Controller is 16” on centers, which is typical wall stud spacing. 3.
Installation Manual Figure 3.
3-4 The Controller Remote Mounting of the Controller To mount the Controller remotely, follow the same instructions as you would to mount the Controller locally. However, remote mounting of the Controller requires that a Remote Receiver be positioned at the zone. The Receiver, normally mounted inside of the Controller, requires a different mounting plate and a 4”x4”x2” electrical box.
Installation Manual Figure 3.
3-6 The Controller 5. Punch out the ½” conduit fitting knock-out and install a proper conduit fitting for the connection you are making. 6. After your conduit runs are complete and tight, fish solid 14gauge conductor from the power source through to the power terminal strip. Be sure to leave yourself 4-6” of excess wire to work with. 7. Replace the Power Supply Cover. 8. Turn on the power to test the connections. NOTE: The Red wires from the secondary of the transformer carry approximately 15V AC.
Installation Manual NOTE: JP5 Positions 1 and 2 are only for testing and demonstration purposes; they should not be used during normal operation. If desired, the System Supervisor can also be wired to trigger an external alarm (e.g. Local Alarm) A common System Supervisor condition is that a large metal object (such as a food cart) has been placed very near the Tx wand antenna and has diminished the Tx Activation Field.
3-8 The Controller Installation Manual Tamper Switch UL 294 requirements call for the installation of a “tamper switch” that engages the lid, and is wired so as to cause an alarm if the lid is removed. When the tamper switch is installed and the lid is removed, a Tx Supervise alarm will be generated and LED14 will illuminate red. To remedy the alarm, replace the lid. The switch is mounted with #4-40, ½” machine screws, star washer, and nut to the Controller case (Figure 3.4).
Installation Manual Figure 3.
Installation Manual Chapter 4: The Tx wand antenna
Installation Manual The Tx wand antenna 4-1 The Tx wand antenna Tx wand antenna Specifications Single Door Applications Double Door Applications Spacing Tx wand antennas at the Same Zone Mounting a Tx wand antenna Connecting a Tx wand antenna to the zone Controller Stagger Tuning Why Re-tune the Tx wand antenna? Tuning a Tx wand antenna Alternate Tuning Method Adjusting the Tx Activation Field A Tx wand antenna (Figure 4.1 and 4.
4-2 The Tx wand antenna the floor and at least 3 inches away from any metal doorframe (Figure 4.3). A 3-inch wood or plastic spacer may be used to keep the antenna away from a metal door frame. In some circumstances due to a building’s construction, it may be necessary to mount the antenna on the hinge side of the door. Furthermore, never mount any metal electrical box or run conduit right behind the “ferrite” bar portion of the antenna (Figure 4.1).
Installation Manual The Tx wand antenna 4-3 cable thus negatively affecting the system’s performance. NOTE: When using multiple antennas, it is necessary to install jumper JP4 on the Controller board. Install in position 2-3 for two antennas, or position 1-2 for three antennas. For more information on jumper JP4, see Appendix B-1.
4-4 The Tx wand antenna Connecting a Tx wand antenna to the zone Controller To connect a Tx wand to the zone Controller, refer to Figure 4.5 (and if applicable, Figures 4.6 and 4.7) and use the following instructions: 1. Using the RED wire, connect the “UNREG” on the antenna (pin P1-2) to “UNREG” on the zone Controller (pin P1-5). NOTE: When multiple antennas are being used, each subsequent antenna should have its RED wire connected to one of the two “UNREG” positions on the zone Controller (P1-1 or P1-5).
Installation Manual Figure 4.5 Connecting a Tx wand antenna to the zone Controller Figure 4.6 Connecting two Tx wand antennas to the zone Controller Figure 4.
4-6 The Tx wand antenna Installation Manual Stagger Tuning Implementing Stagger Tuning Stagger Tuning allows monitored zones to be located closer than the normal minimum 70 feet distance by using different Tx operating frequencies for adjacent zones so that Tags activated in one zone do not create events (locks, alarms, etc.) in another zone. Implementing Stagger Tuning The Controller comes from the factory with 3 different crystals, Y1 (130 KHZ), Y2 (131.072 KHZ) and Y3 (132 KHZ).
Installation Manual The Tx wand antenna 4-7 Why Re-tune a Tx wand Antenna? Before you start Tx wand antennas come from the factory set to Y2 (131.072 KHZ). Under most circumstances, they will not need to be adjusted. However, there are 3 possible reasons to re-tune: For either tuning method, before you start note the number of antennas in the zone and complete the following steps to establish a good starting point: On the Controller: a.
4-8 The Tx wand antenna One-antenna zone To tune a one-antenna zone, refer to Figure 4.10 and use the following instructions: Installation Manual 5. After you have finished adjusting, on the antenna, turn pot R1 completely counterclockwise so that LED1 is dim. 6. On the Controller, return switch S3 to the left position. 1. Using the spanner key provided or a spanner screwdriver, remove the antenna cover by removing the spanner screws. 7. Replace the antenna cover and secure it with the spanner screws.
Installation Manual Two-antenna zone To tune a two-antenna zone, refer to Figure 4.10 and use the following instructions: 1. Using the spanner key provided or a spanner screwdriver, remove both antenna covers by removing the spanner screws on each. 2. Remove the Controller cover. 3. A “steady” and a “flashing” green bar should be illuminating on LED13. The “steady” green bar is the Tx Output Level and should be above the “flashing” bar but not off the top of the scale.
4-10 The Tx wand antenna has been adjusted properly. Therefore, if you try to see a change with LED1 set too bright you may miss that change and be slightly off tune. If this is the case, on the antenna, turn pot R1 (LED brightness adjust) counterclockwise until the yellow LED1 dims then adjust C1 again. 11. After you have finished adjusting, on the “Y” antenna, turn R1 counterclockwise so that LED1 is dim. 12. On the Controller, place jumper JP6 (Scan Rate) into position 1-2. 13.
Installation Manual (LED brightness adjust) counterclockwise until the yellow LED1 dims then adjust C1 again. 7. After you have finished adjusting, on the “X” antenna, turn pot R1 completely counterclockwise so that LED1 is dim. 8. Replace jumper JP6. 9. On the Controller, quickly remove jumper JP6 (Scan Rate) so that only LED2 (the “Y” antenna output indicator) is illuminating. This may take a few attempts. You will not leave the jumper in place while tuning. 10.
4-12 The Tx wand antenna NOTE: Make sure that all connections have been made as outlined in the previous section and you have competed the steps in the “Before you start” section on page 4-7. To tune a Tx wand antenna, refer to Figures 4.11, and use the following instructions: 1. Using the spanner key provided or a spanner screwdriver, take off all antenna covers by removing the spanner screws on each.
Installation Manual counterclockwise until the yellow LED1 dims then adjust C1 again. 6. Turn off power to the system. 7. If you have not been working with antenna "Z", go to Step 9, otherwise, loosen the terminal screw for position X and remove the Z wire from position X on the Controller's P1 connector. Return it to its normal Z position and tighten it. Go to Step 4.d. 8.
Installation Manual Chapter 5: The Receiver
Installation Manual the Receiver 5-1 The Receiver Receiver Specifications Internal vs. External Receivers Receiver Mounting Options Receiver Positioning/Stagger Tuning BR 4200 Auxiliary Receivers Receiver Jumpers Connecting the Receiver Adjusting the Receiver The Receiver (Figures 5.1-5.2) located at the monitored zone, picks up the signal from an activated Tag and relays it to the Controller. Zone Receivers can be internally or externally mounted near a monitored zone.
5-2 the Receiver Installation Manual Internal vs. External Receivers Receiver Positioning/Stagger Tuning When the Controller is positioned near the monitored door, the Receiver is mounted internally in the Controller housing. Position the Receiver within approximately 6 feet of the center of the monitored zone or door opening. It is permissible to mount it beyond 6 feet, but do not exceed 15 feet from the center of the zone or door opening.
Installation Manual the Receiver 5-3 BR 4200 Auxiliary Receivers BR 4200 Zone Receivers monitor both zone events and Band Removal events. BR 4200 Auxiliary Receivers only monitor Band Removal events. Depending upon your facility’s physical layout, Zone Receivers may be enough to ensure full Band Removal coverage. However, to determine where Auxiliary Receivers may be needed, a test BR42 Tag should be used to check every potential location in the area being covered.
5-4 the Receiver Receiver Jumpers Jumper Definitions IS 3200 Zone Receiver jumper settings BR 4200 Zone Receiver jumper settings BR 4200 Auxiliary Receiver jumper settings The following tables (Tables 5.1 – 5.4) contain the Receiver jumper definitions and default positions for each system. Refer to Figure 5.6 for the locations of the Receiver jumpers. Table 5.
Installation Manual Figure 5.
5-6 the Receiver Adjusting the Receiver The Receiver is factory set for optimum performance, and as such, it should NOT be necessary for you to make any adjustments to it. NOTE: If you are trying to eliminate crosstalk (activated Tags from one zone being detected in another zone), implement Stagger Tuning (page 4-6). However, there are a couple of exceptions: When protecting a wide hallway or passageway, it may be necessary to increase Receiver sensitivity to assure optimum detection.
Installation Manual Chapter 6: The Tag
6-2 The Tag BR 4200 System Tags In addition to the functionality of an IS 3200 System Tag, BR 4200 System Tags (Figure 6.3) will alarm if the band is removed or tampered with in any way. Installation Manual Tag between applications and is waterresistant during use. BR 4200 System Tags also contain a visual pulse LED. Tags are activated/deactivated with a TAD unit. BR 4200 System Tags are attached to infants with a conductive-fiber-striped cloth band. Figure 6.4 Cut Band Tag Figure 6.
Installation Manual The Tag 6-3 Tag barcodes Visual Pulse LED Tag barcodes (Figure 6.7) contain a Tag’s manufacturing history. The Visual Pulse LED indicates the Tag’s current mode (see table 6.1) Table 6.1 Visual Pulse LED status LED Light Pattern off on Tag LED Status LT, SB Tags None Tag is off. Active, not in zone Active, in zone Figure 6.7 Tag barcode example BR, CB Tags None Tag is off.
6-4 The Tag Installation Manual LED Tag Verifying Proper Zone Coverage Identifying Foreign Tag-Activating Sources DISCLAIMER: Due to each facility’s unique environment, an LED Tag cannot give an exact measurement of zone coverage; it can only give an estimation of zone coverage. Verifying Proper Zone Coverage An LED Tag (Figure 3.8) is used to verify proper zone coverage during installation, adjustment, or testing of a monitored zone.
Installation Manual The Tag 6-5 3. If you find that a zone’s coverage is at unacceptable levels (too small, too big, extends too far in one direction), look for factors that may be affecting the zone (food carts, medical equipment, and/or building construction). 4. If you cannot locate any immediate causes, contact your system maintenance technician for further assistance. 5. When finished, deactivate the LED Tag using a TAD.
6-6 The Tag Testing Tags For maximum protection of residents or assets, Accutech recommends that Tags be tested on a weekly basis. There are 6 ways that you can test Tags: Enter a monitored zone (Software will report.) With a TAD With a PTAD The Keypad’s Auxiliary LED (Yellow) will light when a Tag is detected (Optional; additional wire required).
Installation Manual Storing Tags To preserve battery life, Tags must be turned off with a TAD during storage or periods of non-use. CB and BR Tags must be deactivated to prevent alarms when not use. However, if you do not have a TAD or your Tags are always activated, Tags should be stored away from sources of electrical noise (see below) and stored in a metal container with lid.
6-8 The Tag The S-TAD Powering the S-TAD On/Off Unlocking the S-TAD Activating/Deactivating Tags The S-TAD (Secure Tag Activator/Deactivator) is used to check the functionality of an Accutech Tag. Accutech Tags operate by internal battery. Over the course of normal operation, Tags eventually lose battery power and the Tags will need to be replaced. The S-TAD is used to determine if a Tag has sufficient battery power to respond to an activating signal. The S-TAD requires a 9-volt battery to operate.
Installation Manual Activating/Deactivating Tags The S-TAD can activate and deactivate Tags preserving Tag battery life and preventing nuisance alarms. ACTIVATING 1. Unlock the S-TAD. 2. Place the inactive Tag in the correct orientation within the Tag receptacle. The Tag’s graphic’s LED is silent (just like the physical Tag’s LED is silent). 3. Press the Enter button (green LED lit). The Wait LED will illuminate (red) for 2 seconds.
Installation Manual Chapter 7: The Keypad
Installation Manual The Keypad Keypad Specifications Positioning the Keypad Surface Mounting the Keypad Flush Mounting the Keypad Connecting the Keypad to the Controller Programming the Keypad The Keypad is used to escort residents through a monitored zone and to reset zone equipment once an alarm has occurred. The Keypad provided by Accutech (Visonic CL8A) is intended as an indoor Keypad only. If you require an outdoor Keypad, contact your Accutech Representative.
7-2 The Keypad Installation Manual Positioning the Keypad Surface Mounting the Keypad The Keypad should be located within 3 to 5 feet of the monitored door or elevator. In hallway applications, mount the Keypad just outside of the zone to avoid alarm activation when escorting a monitored resident. The Keypad is designed to be surface mounted using the white back box provided.
Installation Manual Figure 7.3 Connecting the Keypad to the Controller Figure 7.
Installation Manual The Keypad 7-3 Flush Mounting the Keypad If flush mounting is required, use a plastic single gang electrical switch box, instead of the original white back box (see Figure 7.2). A flush mount box can be obtained from your local building supply outlet. CAUTION: The Keypad manual shows the use of a standard single gang, metal electrical switch box. Accutech does not recommend the use of this type of box for two reasons: 1. The fit is very, very tight.
7-4 The Keypad Connecting the Keypad to the Controller Installation Manual connect pin 4 of the Keypad to P8-pin5 (Tag Detect) of the Controller. You will need 22-gauge 4-conductor plenumrated cable for installation. If you are using composite cable, see Chapter 2 for color code. 9. Place a jumper connecting the Keypad pins 2, 4 and 6. NOTE: If using Tag Detect option, only jumper Keypad pins 2 and 6.
7-6 The Keypad Programming the Keypad Keypad Operation Programming user codes Deleting user codes Resetting the master code Adjusting the Keypad Escort Time Installation Manual Keypad Operation The Keypad has three LED indicators. See Table 5.1 for their functions during normal operation. Table 7.1 Keypad LED Indicators LED Status Function entered 3 times or more incorrectly, the Keypad will lockout for 90 seconds; this lockout mode is indicated by a green blinking LED.
Installation Manual Programming user codes Remember that user code No. 01 will become the new master code as soon at it is programmed, and therefore should be assigned to the person in charge of security. It is recommended that the master code be composed of at least 8 digits. To program user codes, use the following instructions: 1. Prepare a list of user codes you want to program and record them. 2. Invoke the programming menu by entering **, [master code], **.
7-8 The Keypad If you make an error while programming, press [*] and you will be instantly returned to the programming menu. To quit programming, ensure that the green LED is flashing slowly, then press [#]. This will restore the Keypad to normal operation. Deleting user codes To delete user codes, use the following instructions: 1. Access the programming menu by entering **, [master code], **. With the programming menu active, the green LED will flash slowly. 2.
Installation Manual 6. To quit programming at this stage, press # while the green LED is flashing slowly. Adjusting the Keypad Escort Time To adjust the Keypad Escort Time, use the following instructions: 1. Access the programming menu by entering **, [master code], **. With the programming menu active, the green LED will flash slowly. 2. Enter “2” to select the relay timer function. The green LED will respond by flashing rapidly, indicating that the Keypad is ready to receive data. 3.