All-Purpose Temperature Controller ITC-1000F User Manual Version 1.0s Inkbird Tech. Co., Ltd. Copyright Copyright© 2016 Inkbird Tech. Co., Ltd. All rights reserved. No part of this document may be reproduced without prior written permission. Disclaimer Inkbird has made every effort to ensure that the information contained in this document is accurate and complete; however, the contents of this document are subject to revision without notice. Inkbird to ensure you have the latest version of this document.
ITC-1000 User Manual Contents 1. Safety Precautions ................................................................................................ 3 2. Specification ........................................................................................................ 4 Main features .....................................................................................................4 Mounting dimension ............................................................................................4 3.
ITC-1000 User Manual 1. Safety Precautions Ensure the product using within the specification. Do not touch the terminals at least while power is being supplied. Doing so may occasionally result in injury due to electric shock. Do not allow pieces of metal, wire clippings, or fine metallic shaving or filings from installation to enter the product. Doing so may occasionally result in electric shock, fire, or malfunction. Do not use the product where subject to flammable or explosive gas.
ITC-1000 User Manual 2. Specification Main features Fahrenheit and Celsius Display Can Be Choose; More User-friendly Operating; Switch Between Cooling and Heating Modes; Control the Temperature by Setting the Temperature Set Value and the Difference Value; Temperature Calibrating; Refrigerating Control Output Delay Protection; Alarm When Temperature Exceeds the Limit or When Sensor Error; Mounting dimension: Front Panel Size: 75(L)*34.
ITC-1000 User Manual 3. Wiring Diagram 3.1 ITC-1000F-110V Note: Strictly distinguish interface of relay,sensor and power Strictly distinguish connection of sensor and power Sensor down-lead and power wire should be kept a proper distance 3.2 ITC-1000F-220V Note: Strictly distinguish interface of relay,sensor and power Strictly distinguish connection of sensor and power Sensor down-lead and power wire should be kept a proper distance 3.
ITC-1000 User Manual 4. Keys Instruction 5. Key Operation Instruction 5.1 Check Parameter: In normal working status, press “ value; press “ ” key once, it will display the setting temperature ” key once, it will display the difference value; 5.2 Parameter Setting: In normal working status, keep pressing “ ” for more than 3s to enter set mode, set indicator lamp is on, screen displays the first menu code “TS”. Press “ ” key or “ ” key to move up or down the menu item and display the menu code.
ITC-1000 User Manual If no operating within 10s, it will exit the menu automatically and return to normal temperature display status, and does not save the parameter of this modification. 5.3 Operating instruction: In normal working status, press and hold “ controller; in Power-off Status, press and hold “ ” key for more than 3s to turn off the ” key for more than 1s to turn on the controller.
ITC-1000 User Manual 6. Menu Instruction 6.1 When the set temperature is degrees Celsius (FCC) Code Function Set range Default TS Temperature Set Value -50~99.9 oC 10.0 oC DS Difference Set Value 0.3~15 oC 1.0 oC PT Compressor Delay 0~10 minutes 3munites CA Temperature Calibration Value -15 oC~15 oC 0 oC CF Fahrenheit or Celsius Setting Note C 6.
ITC-1000 User Manual 7. Error Description Sensor Error Alarm: When the temperature sensor circuit is short circuit or open circuit, the controller starts sensor error mode and closes all running status, the buzzer alarm sounds, screen displays ER. Press any keys can cancel buzzer alarm, the system returns to the normal working status after error is cleared.
ITC-1000 User Manual 8. Technical Assistance and Warranty 8.1 Technical Assistance If you have any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. If you require assistance, please write us to cs@ink-bird.com. We will reply your emails in 24 hours from Monday through Saturday. You can also visit our web site www.ink-bird.com to find the answers of the common technical questions. 8.2 Warranty INKBIRD TECH. C.L.