Installation guide

Installation Instructions
HOOD EXHAUST
NOTE: Read these next two pages only if you plml to vent your exhaust to the
outside. If you plan to recirculate the air back into the room, proceed to page 6.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
The following chart describes an example ot one possible
ductwork installation.
DUCT PIECES
EQUIVALENT NUMBER
LENGTH x USED
RoofCap 24 Ft. x
12Ft.StraightDuct 12Ft. x
(6" Round)
Rectangular-to-Round 5Ft. x
TransitionAdaptor*
Equivalentlengthsof duct piecesare basedon actualtests and
reflect requirementsfor goodventingperformancewith anyventhood.
(1)
(1)
(1)
Total Length
EQUIVALENT
LENGTH
24 Ft.
12Ft.
5Ft.
41 Ft.
* IMPORTANT: If a rectangula>to-round transition adaptor is used, the bottom cornei_ of the damper
will haxe to be cut to fit, using the tin snips, in order to allow free moxement of the damper.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart describes an example ot one possible
ductwork installation.
EQUIVALENT
DUCT PIECES LENGTH* x
Wall Cap 40Ft.
3 Ft.StraightDuct 3 Ft. x
3W' x 10" Rectangular)
(_ 90° Elbow 10Ft. x
NUMBER EQUIVALENT
USED = LENGTH
x (1) = 40Ft.
(1) = 3 Ft.
(2) = 20R.
Equivalent lengths of duct pieces are based on actual tests and
reflect requirements for good venting performance with any vent hood.
Total Length = 63 Ft.
NOTE: For back exhaust, care should be taken to align exhaust with space between studs, or wall should be prepared
at the time it is const_ ucted by leaving enough space between the wall studs to accommodate exhaust.
4