Manual

MAN0885-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 1 of 6 #1037
1 Specifications
Specifications
Digital DC Inputs
Inputs per Module
12 including 4 configurable
HSC inputs
Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance
10 k
Input Current Positive Logic Negative Logic
Upper Threshold 0.8 mA -1.6 mA
Lower Threshold 0.3 mA -2.1 mA
Max Upper Threshold 8 VDC
Min Lower Threshold 3 VDC
OFF to ON Response 1 ms
ON to OFF Response 1 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse,
Edges
5 kHz Frequency/Pulse,
Width
2.5 kHz Quadrature
Digital Relay Outputs
Outputs per Module 6 relay
Commons per Module 6
Max. Output Current per Relay 3 A at 250 VAC, resistive
Max. Total Output Current 5 A continuous
Max. Output Voltage 275 VAC , 30 VDC
Max. Switched Power 1250 VA, 150 W
Contact Isolation to XL6
ground
1000 VAC
Max. Voltage Drop at Rated
Current
0.5 V
Expected Life
(See Derating section for
chart.)
No load: 5,000,000
Rated load: 100,000
Max. Switching Rate
300 CPM at no load
20 CPM at rated load
Type Mechanical Contact
Response Time
One update per ladder scan
plus 10 ms
Analog Inputs, Medium Resolution
Number of Channels 4
Input Ranges
0 - 10 VDC
0 – 20 mA
4 – 20 mA
Safe input voltage range -0.5 V to +12V
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
Current
Mode:
100
Voltage
Mode:
500 k
Nominal Resolution 10 Bits
%AI full scale 32,000 counts
Max. Over-Current 35 mA
Conversion Speed
All channels converted once
per ladder scan
Max. Error at 25°C
(excluding zero)
*can be made tighter (~0.25%)
by adjusting the digital filter
setting to 3.
4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 1.50%*
Additional error for
temperatures other than 25°C
TBD
Filtering
160 Hz hash (noise) filter
1-128 scan digital running
average filter
General Specifications
Required Power
(Steady State)
500 mA @ 24 VDC
Required Power
(Inrush)
30 A for 1 ms @ 24 VDC – DC Switched
2.5 A for 4 ms @ 24 VDC - AC Switched
Primary Power Range 10 – 30 VDC
Relative Humidity 5 to 95% Non-condensing
Clock Accuracy
+/- 35 ppm maximum at 25° C
(+/- 1.53 Minutes per Month)
Operating Temperature
-10°C to +60°C
Terminal Type Screw Type, 5 mm Removable
Weight 26.5 oz. (.751 kg)
CE
UL
USA: http://www.heapg.com/Pages/TechSupport/ProductCert.html
Europe: http://www.horner-apg.com/en/support/certification.aspx
Display Type 5.7” QVGA TFT
Display Size 5.7”
Display Screen
Dimension
320 x 240
Display Memory 2.75 MB
Display Life Minimum 40000 hours (50% brightness, 25 deg C)
User Keys 5 user-defined Function keys and a System Key
Screens supported 1023
Colors 32768/ 16 shade Grey scale (XL6M models only)
Connectivity
Serial Ports 2 Serial Ports – RS232 & RS485
Ethernet 10/100-Mbps (XL6e models only)
USB
USB Networking Port for communication with PCs, flash device connectivity
and programming Port
Removable Media
Removable Media for upto 2 GB of storage for programs, data logging or
screen capture
Smartstix Remote IO modules communicating on CAN
HE-XL102 / HE-XL1E2 / HE-XL1M2
XL6/XL6M/XL6e OCS Models
HE-XL102 / HE-XL1M2 / HEXT350C112 / HEXT280C112
HE-XL1E2 / HEXT351C112
12 Digital DC Inputs
4 Analog Inputs (Medium Resolution)
6 Digital Relay Outputs
Note: Highest usable frequency for PWM output is 65 KHz