Install Instructions

INSTALLATION INSTRUCTIONS
Put Bar Code Here
95C-10206-02
V4043 and V4044 Motorized Valves
FEATURES
These valves consist of an actuator motor and valve assembly
for controlling the flow of hot or cold water.
The V4043 provides 2-position, straight through control of
supply water.
The V4044 provides 2-position, diverting control of supply
water.
Compact construction for easy installation.
Manual opener for valve operation on power failure. Valve
returns to automatic position when power is restored.
Motor actuator may be replaced without removing the valve
body or draining the system.
Complete powerhead may be removed without breaking
the line connections.
Sweat fit models may be installed without disassembling
the valve.
Fits under the cover of most baseboards.
SPECIFICATIONS
Models:
V4043 - line voltage, straight-through valves.
V4044 - line voltage, 2-position diverting valves.
Electrical Ratings:
Maximum Temperature Rating:
Minimum Temperature Rating:
Ambient: 40° F (4° C).
Liquid: 40° F (4° C).
Humidity Rating: 5-95% RH (non-condensing)
Atmosphere: non-corrosive, non-explosive
For Models with End Switch: End Switch Rating: 2.2 A @
220/240 Vac 50 Hz.
Timing:
V4043 opens or closes in 15 seconds.
V4044 diverts flow in 30 seconds.
Manual Opener: Manual opener opens the valve in case of
power failure. Valve returns to automatic position when
power is restored.
Powerhead Replacement: Includes motor housing, rubber
plug, O-ring, 2 mounting screws, and 1 sheetmetal screw.
Flow Ratings:
a
Static Pressure Ratings: Both 125 psi (860 kPa) and 300 psi (2070
kPa) models available.
Voltage Amperes
110 .084
120 .080
220 .042
Class A Motor Class F Motor
Ambient
(F)
77 125 140 125 170 190 200
Liquid (F) 175 165 155 250 220 210 200
Ambient
(C)
25 52 60 52 77 88 93
Liquid (C) 80 75 68 120 105 100 95
Valve Family Capacity Rating
Maximum Closeoff
Pressure
a
V4043 Cv kV PSI kPa
1.0 0.9 50 345
2.5 2.0 30 207
3.5 3.0 20 138
8.0 7.0 8 55
V4044 4.0 3.5 10 69
7.0 6.0 10 69
V4043
V4044

Summary of content (8 pages)