Install Instructions

RP971A
Pneumatic Ratio (Sequencing) Relay
INSTALLATION INSTRUCTIONS
DESCRIPTION
The RP971A Ratio Relay is a nonbleed, pneumatic relay
that produces a modulating pressure output in proportion
to pilot pressure input changes, and is suitable for use in
all types of pneumatic control systems. In a typical
application, two or three relays are used to control
pneumatic valve or damper actuators in sequence from a
single signal source.
Fig. 1 shows approximate dimensions in inches (millimeters).
2
(51)
2
1
4
1
2
4
2-5/8
(67)
C7459
PORT
3
Fig. 1. RP971A Dimensions,
INSTALLATION
Mounting
Suspend on tubing or mount on a surface (see Fig. 2).
WALL OR
PANEL
PART NO. 801629T
NO. 10 X 1/2 IN.
SHEET METAL SCREW
(OBTAIN LOCALLY)
RP971 RELAY
MOUNTED HERE
C8248
NOTE: INSIDE DIAMETER OF CLAMP 2IN. (51MM).
MOUNTING SCREW WHOLE DIAMETER IS
.20 IN. (5MM).
Fig. 2. Typical Surface Mounting.
Piping
Fig. 3 shows adaptation piping. Port 1 (Main, Supply)
sharp barb for 1/4-in. (6 mm) O.D. tubing. Ports 2, 3, and 4
(Branch, Output; Pilot, Input; and Exhaust, respectively),
sharp barb for 5/32-in (4 mm) O.D. tubing.
CAUTION
To prevent damage to the sharp barb connections,
do not attempt to cut or pull tubing. To remove the
tubing from the barb connections, cut tubing a few
inches from the control device . Use a coupling to
reconnect tubing.
NOTE: If the system is other than copper or polyethylene
tubing, adapt as shown in Fig. 3. Some models
provide parts for adapting.
Copyright © 1996 Honeywell Inc. All Rights Reserved
95-7234

Summary of content (4 pages)