Install Instructions

INSTALLATION INSTRUCTIONS
Put Bar Code Here
66-1161-04
SIL
3
Capable
RM7898A
7800 SERIES Valve Proving Primary
Relay Modules
APPLICATION
The RM7898 is a microprocessor-based integrated burner
control for automatically fired gas, oil or combination fuel single
burner applications. The RM7898 system consist of a relay
module, subbase, amplifier, and purge card. Options include
Keyboard Display Module (KDM), Personal Computer Interface,
Data ControlBus™ Module, remote display mounting, Expanded
Annunciator and Combustion System Manager® Software.
Functions provided by the RM7898 include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
The RM7898 provides unique functions to a standard primary
control.
As received, the RM7898 offers the following features:
Interrupted pilot with 10 second pilot flame establishing period.
Main valve operation with 10 second MFEP.
Pre-Ignition Interlock (POC) input.
Shutter-driven output when appropriate amplifier is
selected (R7861A, R7886A, R7851C).
Blinking Fault Code Power LED on safety shutdown.
RM7898A1018 offers early spark shutoff when flame is sensed.
Available features when appropriate terminals are energized:
Intermittent pilot T8 (Terminal 19).
Direct spark feature for Valve Proving System (VPS)
(Terminal 18).
Valve Proving System function (Terminal 17).
See “Appendix b - ignition options” on page 23 for
examples of 24 single or dual fuel system combinations
with or without using the Valve Proving feature.
Programmable features using the S7800A1142 Keyboard
Display Module (KDM) (not included):
Postpurge time—(up to 60 minutes).
Valve Prove System features, including:
VPS test time
When in burner sequence to conduct VPS time
(Never, Before, After, Both or Split):
NOTE: The S7800A1142 Series 5 or higher can be programmed
for ModBus Communication. (See 65-0288 Spec Sheet.)
At commissioning time, the Valve Proving System may be
scheduled to occur at one of five different times:
1. Never—Device default as received; valve proving does
not occur. (Demand wired to Terminal 6.)
2. Before—Valve proving after standby and safe start
check, prior to ignition trials, concurrent with Pre-Purge.
3. After—Valve proving occurs after the Run state before
the device goes to Standby, concurrent with postpurge.
4. Both—Valve proving occurs at both times Before and
After noted above.
5.
Split—The Main Valve 2 (MV2) (high pressure) seat test is
performed at the Before time and the Main Valve 1 (MV1)
(low pressure) seat test is performed during the After time.
To perform Valve Proving, it must be commissioned and
Demand Input (Terminal 17) must be used.
The following assumptions apply when using the RM7898
Valve Proving testing.
Fig. 1. Valve Proving System—simplified diagram.
MV1—Wired to terminal 9. It is located at the most upstream
position of the main gas valve train.
VPS—Valve Proving Switch (Rated 1/2 of main valve inlet pressure).
MV2—Wired to terminal 21. It is the main valve located
closest to the burner.
The Pre-Ignition Interlock switch or Proof of Closure for
Terminal 20 can be installed on MV1, MV2, or as a series
connection through both valves.
MV1
MV2
VP
SW.
M24161
OUTLET
INLET
1
CAUTION: VALVE ENERGIZING TIMING IS BASED ON HONEYWELL VALVE
OPENING TIMES OF 13 SECONDS MAXIMUM.
− FOR VALVES WITH TIMINGS GREATER THAN 13
SECONDS OR THOSE THAT DO NOT OPEN THE ACTIVE
VALVE WITHIN THE ENERGIZED TIME, A BYPASS
SOLENOID VALVE (1/4”, 120 VAC) IS REQUIRED TO
OBTAIN THE PROPER TEST PRESSURES.
− THE BYPASS VALVE WILL BE WIRED IN PARALLEL TO THE
VALVE IT IS BYPASSING (TERMINAL 9 FOR MV1 OR
TERMINAL 21 FOR MV2).
1

Summary of content (28 pages)