Product Overview

SPECIFICATION DATA
66-2027-04
SIL
3
Capable
7800 SERIES
RM7840E,G,L,M; EC7840L
Relay Module
APPLICATION
The Honeywell RM7840 is a microprocessor based integrated
burner control for automatically fired gas, oil or combination
fuel single burner applications. The RM7840 system consists
of a Relay Module, Subbase, Amplifier and Purge Card.
Options include Keyboard Display Module, Modbus Module™,
DATA CONTROLBUS MODULE™, Remote Display Mounting,
and First-Out Expanded Annunciator.
The RM7840 is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the RM7840 include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
RM7840G1022, RM7840L1075, RM7840L1091 and
EC7840L1014 offer Valve Proving Feature.
RM7840L1091 has a 4 second main flame establishing
period.
Using the S7800A1142 Keyboard Display (standard on
RM7800L1087) the following features can be set up:
Post Purge time—Up to 60 minutes—Device shipped
with 15 seconds Post purge.
Valve Proving features including:
VPS test time
When (Never, Before, After, Split or Both)
FEATURES
Safety features:
Interlock check.
Closed loop logic test.
Dynamic AMPLI-CHECK™.
Dynamic input check.
Dynamic safety relay test.
Dynamic self-check logic.
Expanded safe-start check.
High Fire Purge Switch test.
Internal hardware status monitoring.
Low Fire Start Switch test.
Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
0.8 or 3.0 second Flame Failure Response Time (FFRT),
depending on amplifier selected.
Communication interface capability using Modbus.
Dependable, long-term operation provided by
microcomputer technology .
First-out annunciation and system diagnostics are
provided by an optional 2 row by 20 column Vacuum
Fluorescent Display (VFD) located on the Keyboard
Display Module (optional).
First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
Five LEDs for sequence information. See Fig. 1.
Five function Run/Test Switch.
Interchangeable plug-in flame amplifiers.
Local or remote annunciation of RM7840 operation and
fault information (optional).
Nonvolatile memory RM7840 retains history files and
sequencing status after loss of power.
Remote reset (optional).