Product Overview
Table Of Contents
SPECIFICATION DATA
66-2027-04
SIL
3
Capable
7800 SERIES
RM7840E,G,L,M; EC7840L
Relay Module
APPLICATION
The Honeywell RM7840 is a microprocessor based integrated
burner control for automatically fired gas, oil or combination
fuel single burner applications. The RM7840 system consists
of a Relay Module, Subbase, Amplifier and Purge Card.
Options include Keyboard Display Module, Modbus Module™,
DATA CONTROLBUS MODULE™, Remote Display Mounting,
and First-Out Expanded Annunciator.
The RM7840 is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the RM7840 include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
RM7840G1022, RM7840L1075, RM7840L1091 and
EC7840L1014 offer Valve Proving Feature.
RM7840L1091 has a 4 second main flame establishing
period.
Using the S7800A1142 Keyboard Display (standard on
RM7800L1087) the following features can be set up:
• Post Purge time—Up to 60 minutes—Device shipped
with 15 seconds Post purge.
• Valve Proving features including:
— VPS test time
— When (Never, Before, After, Split or Both)
FEATURES
• Safety features:
— Interlock check.
— Closed loop logic test.
— Dynamic AMPLI-CHECK™.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— High Fire Purge Switch test.
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
• Access for external electrical voltage checks.
• Application flexibility.
• 0.8 or 3.0 second Flame Failure Response Time (FFRT),
depending on amplifier selected.
• Communication interface capability using Modbus.
• Dependable, long-term operation provided by
microcomputer technology .
• First-out annunciation and system diagnostics are
provided by an optional 2 row by 20 column Vacuum
Fluorescent Display (VFD) located on the Keyboard
Display Module (optional).
• First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
• Five LEDs for sequence information. See Fig. 1.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of RM7840 operation and
fault information (optional).
• Nonvolatile memory RM7840 retains history files and
sequencing status after loss of power.
• Remote reset (optional).