Install Instructions

1 65-0100—2
B.M./L.Z. • Rev. 2-95 • ©Honeywell Inc. 1995
CAUTION
1. Installer must be a trained, experienced, flame safeguard control service technician.
2. Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More
than one power supply disconnect may be involved.
3. All wiring must comply with applicable local electrical codes, ordinances, and regulations.
4. All line voltage terminal wiring shall be no. 14, 16 or 18 copper conductor TTW (60C) or THW (75C) or THHN
(90C), 600 volt insulation wire. A maximum of two conductors can be wired to each Q7800 Subbase terminal.
5. Voltage and frequency of the power supply and flame detector(s) connected to this control must agree with those
marked on the device.
6. Loads connected to the control terminals must not exceed ratings listed in Specification sheets 65-0087 or 65-0117,
or on the RM7800/RM7840 label.
7. All external timers must be listed or component recognized by authorities having jurisdiction for the specific
purpose for which they are used.
8. Perform all required checkout tests after installation is complete.
Conversion Wiring Diagrams for
RM7800/RM7840
These diagrams and instructions are for converting the following model programmers to RM7800/RM7840 microprocessor
based integrated burner control.
TABLE OF CONTENTS
Page
Section I ............................................................................................................................................................................... 6
BC7000
Section II ........................................................................................................................................................................... 12
Honeywell R4140, R4150
Section III .......................................................................................................................................................................... 31
Honeywell R4126, R4127, R4181
Section IV .......................................................................................................................................................................... 44
Fireye C, D, and E Series
Section V ........................................................................................................................................................................... 50
Fireye P Series
Section VI .......................................................................................................................................................................... 59
Eclipse 5602
WARNING
Improper configuration jumper selection could cause a fire or explosion hazard that could lead to property
damage, severe injury or death.
65-0100-2

Summary of content (60 pages)