Product Overview
Table Of Contents
SPECIFICATION DATA
66-2031-3
® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc.
All Rights Reserved
7800 SERIES
EC7823/RM7823 Relay Module
APPLICATION
The Honeywell EC7823/RM7823 is a microprocessor based
Flame Detector Relay that can be fitted with any 7800
SERIES amplifier to provide relay action from one relay with
2 single poles, double throw (spdt) circuits when flame is
present or not present. The EC7823/RM7823 Relay Module,
Q7800 Wiring Subbase and Amplifier are required to complete
the system. Options include Keyboard Display Module,
Personal Computer Interface, DATA CONTROLBUS
MODULE™, Remote Display Module, First-Out Expanded
Annunciator and COMBUSTION SYSTEM MANAGER™
Software.
Functions provided by the EC7823/RM7823 include flame
monitoring, system status indication, system or self-
diagnostics and troubleshooting.
The EC7823/RM7823 is a flame detector relay only. Suitable
primary control must be used to provide safe-start check,
safety lockout, load switching and other required in flame
safeguard systems.
FEATURES
• Safety features:
— Dynamic AMPLI-CHECK™.
— Dynamic self-check logic.
— Tamper resistant logic.
• Access for external electrical voltage checks.
• Application flexibility with interchangeable plug-in
flame amplifiers.
• Communication interface capability.
• Dependable, long-term operation provided by
microcomputer technology.
• System and device diagnostics are provided by an
optional 2 row by 20 column Vacuum Fluorescent
Display (VFD) located on the optional Keyboard
Display Module.
• Three (LEDs) for status information. See Fig. 1.
• EC7823/RM7823 provide either 0.8 or 3.0 second FFRT,
depending on amplifier selected.
• Local or remote annunciation of EC7823/RM7823
operation and fault information (optional).
• Nonvolatile memory; EC7823/RM7823 retains history
files after loss of power.
• Remote reset (optional).
• Report generation (optional).
• Shutter drive output.
• Burner controller data (optional):
— Flame signal strength.
— Total hours of operation.
— Total cycles of operation.
— Fault history providing the six most recent faults:
• Cycles of operation at the time of the fault.
• Fault message and code.
• Hours of operation at the time of the fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• Software revision and version of EC7823/RM7823
and optional Keyboard Display Module.