Product Overview

SPECIFICATION DATA
66-2028-04
SIL
3
Capable
7800 SERIES
RM7800E,G,L,M Relay Module
APPLICATION
The Honeywell RM7800 is a microprocessor based integrated
burner control for automatically fired gas, oil or combination
fuel single burner applications. The RM7800 system consists
of a Relay Module, Keyboard Display Module, Subbase,
Amplifier, and Purge Card. Options include Modbus™ Module,
DATA CONTROLBUS MODULE™, Remote Display Mounting,
and First-Out Expanded Annunciator.
The RM7800 is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the RM7800 include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
The RM7800L1087 offers the following setup features:
Post Purge time adjustable up to 60 minutes, shipped with
15 second post purge.
Valve Proving features including:
VPS Test Time
When (Before, After, Split, or Both)
FEATURES
Safety features:
Interlock check.
Closed loop logic test.
Dynamic AMPLI-CHECK™.
Dynamic input check.
Dynamic safety relay test.
Dynamic self-check logic.
Expanded safe-start check.
High Fire Purge Switch test.
Internal hardware status monitoring.
Low Fire Start Switch test.
Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
Provides 0.8 to 3.0 second Flame Failure Response
Time (FFRT), depending on amplifier selected.
Communication interface capability through
Modbus™.
Dependable, long-term operation provided by
microcomputer technology.
First-out annunciation and system diagnostics
provided by 2 row by 20 column Vacuum Fluorescent
Display (VFD) located in the Keyboard Display Module.
First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
Five sequence information LEDs, see Fig. 1.
Five function Run/Test Switch.
Interchangeable plug-in flame amplifiers.
Local or remote annunciation of operation and fault
information through the Keyboard Display.
Nonvolatile memory for retaining history files and
sequencing status after loss of power.
Remote reset (optional).
Burner controller data:
Sequence status.
Sequence time.
Hold status.
Lockout/alarm status.
Flame signal strength.
Expanded annunciator status.
Total cycles of operation.
Total hours of operation.
Fault history of six most recent faults:
• Cycles of operation at time of fault.
• Expanded annunciator data at time of fault.
• Fault message and code.
• Hours of operation at time of fault.
• Sequence status at time of fault.
• Sequence time at time of fault.
Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of RM7800 and
Keyboard Display Module.
• Status of configuration jumpers.
• Status of Run/Test Switch.