Install Instructions

PP901A & B Pressure Reducing Valves
DESCRIPTION
The PP901A & B Pressure Reducing Valves regulate the
pressure of air delivered to pneumatic control system
devices. The PP901A operates in a single pressure
system and delivers a regulated air pressure. The PP901B
operates in a two-pressure system and delivers two
independent regulated air pressures.
The PP901A & B include a safety relief valve that protects
the downstream line from excessive main line pressure
surges. A gage connection accommodates a 305915
0-30 psi Gage (“Gage”) for measurement of the regulated
pressure.
BEFORE INSTALLING NOTE
A coalescing filter is required upstream of the
PP901A & B.
Also, if no Gage is used, PP901 installation requires a
CCT1705T 1/8-inch Pipe Plug.
INSTALLATION INSTRUCTIONS
INSTALLATION
Mounting
Refer to job drawings and Fig. 1. Mount PP901A or B in
one of the following ways:
Wall- or panel-mounted using provided Bracket.
Bracket includes mounting slots for two 1/4-20x5/
8 inch screws (provided).
Directly supported on system piping
Piping
Connect PP901A & B INLET and OUTLET piping
(Fig. 1).
Mount Gage or CCT1705T Pipe Plug in
1/8-inch NPT gage connection on PP901A & B.
®U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. All Rights Reserved
95-2558