Installation Guide

M200-502-00 I56-4428-000
DOP-IOD085
EN54-17: 2005
EN54-18: 2005
0786
22
0786
Honeywell Morley-IAS
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
E N G L I S H
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
-20°C
60°C
Fig./Abb. 3
Fig./Abb. 2
MI-D240CMOE
MI-D240CMOE
M200E-SMB
Lift
Sollevare
Levantar
Anheben
Push down
Premere
Precionar
hacia abajo
Runterdrücken
Rotate / Ruotare
Girar /
Drehen
Rotate
Ruotare
Girar
Drehen
Clip / Agganciare
Acoplar /
Einrasten
Plug
Inserire
Conectar
Einhaken
2
3
1
13
2
1:2 DIN
1:1 M200E-SMB
Fig./Abb. 1
This manual is intended as a quick reference installation guide. Please
refer to the control panel manufacturers installation manual for detailed
system information.
The installation must be carried out by expert personnel, that is, a person
with education or experience to identify hazards and take appropriate
actions to reduce the risk of injury to themselves and others.
GENERAL INFORMATION
The Morley series of modules are a family of microprocessor controlled
interface devices permitting the monitoring and/or control of auxiliary
devices. The MI-D240CMOE is an output module, providing 250VAC
5A rated voltage free contacts, both normally open and normally closed.
SPECIFICATIONS
Operating Voltage Range: see S00-7100
LED Cuto󰀨 Voltage: 16.5 VDC
Maximum Standby Current (µA): 75µA - No Communication
Fault Current: 5.5 mA (Yellow LED illuminated)
Coil Activation/Deactivation Current: 76mA Maximum for 12ms
Relay Contact Rating: 5A at 30VDC, 5A at 250VAC
Isolator Features: see S00-7100
Operating Temperature: -20°C to 60°C
Humidity: 5% to 95% Relative Humidity
Maximum Wire Gauge 2.5 mm²
CAUTION
Disconnect loop power before installing modules or sensors.
High voltages may be present on terminals 7 to 12.
INSTALLATION
Note: This module must only be connected to control panels using
compatible proprietary analogue addressable communication protocols for
monitoring and control.
Morley series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low prole surface-mounting box. The SMB
Base is a󰀩xed to mounting surface, and then the module and cover
are screwed onto the base using the two screws supplied. Box
dimensions: 132 mm (H) x 137 mm (W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5
mm "Top Hat" DIN rail inside a control panel or other suitable enclosure.
Install and remove as shown in Figure 1:2.
Wiring to all series Morley modules is via plug in type terminals capable
of supporting conductors up to 2.5 mm²
WARNING
Ensure that the correct terminals are used for the loop and
switched voltage as damage may result from incorrect usage.
The module address is selected by means of rotary decade address
switches (see gure 3), accessed at the front of the module. A screwdriver
should be used to rotate the wheels to select the desired address. (Note:
The number of addresses available will be dependent on panel capability,
check the panel documentation for information on this).
Short Circuit Isolators
All Morley series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired
out of the loop to facilitate the use of the modules on high current loaded
loops, for example if sounders are used. To achieve this, the loop out
positive should be wired to terminal 4 rather than terminal 2.
MI-D240CMOE
INSTALLATION INSTRUCTIONS FOR MAINS
SWITCHING OUTPUT MODULE
Note:
In order to meet the requirements of European Safety Standards, ensure
that all cables carrying voltages in excess of 48V are suitably fused.