HZ432 TrueZONE Zone Panel Professional Installation Guide 69-2070-01
Installation Guide Table of Contents Specifications..................................................................................................................................1 Accessories.....................................................................................................................................2 Mounting..........................................................................................................................................3 Wiring............................
HZ432 TrueZONE Specifications Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more. Temperature Ratings: Shipping: -20° to 150°F (-29° to 66°C) Operating: -40° to 165°F (-40° to 74°C) Current Draw: Zone Panel: 10 VA max. All VA specifications at 24 VAC. Dimensions: See below. Emissions: Complies with FCC Class B, part 15 requirements. Wiring: 18-gauge solid (not stranded) wire. Humidity Ratings: 5% to 90% RH non-condensing. 13.42 (341) 8 (203) 1.
Installation Guide Accessories Table 1. Recommended Thermostats. System NonProgrammable Programmable Single- TH5110D, TH3110D, TH8110U, TH6110D, Stage T87N TH4110D MultiTH5220D TH8320U, TH8321U, Stage TH6220D, YTH9421C HeatTH5220D (2H/1C TH8320U (Up to 3H/2C) Pump only) TH8321U (Up to 3H/2C) TH3210D (2H/1C TH6320U* (Up to 3H/2C) only) TH6220D (2H/1C only) TH5320U* (Up to TH4210D (2H/1C only) 3H/2C) YTH9421C* ** Note: These thermostat models all have different fourdigit suffixes.
HZ432 TrueZONE Mounting 1 Mount the HZ432 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or coldair return. NOTE: The HZ432 TrueZONE panel can be mounted in any orientation; level it for appearance only.
Installation Guide Wiring CAUTION: Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Wire entire panel before applying transformer power. Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional systems, refer to this page. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9. 3 Install thermostats using instructions provided with thermostats.
HZ432 TrueZONE 5 SENSOR Wiring Connect DATS as shown. DATS DATS M24804 C7735A1000 6 Connect equipment as shown. The DS/BK terminal is used with a variable-speed fan. Connect the DS, BK, ODD, or DHUM terminal on the HVAC equipment to this terminal. When 1 zone is calling (or 25% on systems with more than 4 zones) this terminal will be de-energized of 24 VAC. This reduces blower speed on most variable speed blowers. HVAC 24 VOLT TRANS.
Installation Guide Heat Pump Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat. NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump system. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED M1 COMMON M4 OPEN 2 THERMOSTAT ZONE 4 DAMPER AIR HANDLER G O/B L 24 VOLT TRANS.
HZ432 TrueZONE Heat Pump Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat. ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED THERMOSTAT ZONE 4 DAMPER AIR 2 HANDLER Rc R C E AUX Y Y2 G O/B L 24 VOLT TRANS. C R EM. HEAT M6 CLOSED M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L RH RC W1/E W2 W3 Y1 Y2 G O B DS/BK M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L E AUX.
Installation Guide Dual Fuel Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.
HZ432 TrueZONE dual Fuel Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.
Installation Guide Configuration To enter Configuration: 1 Press the Mode button (the Config LED will light up). BACK HOME CONFIG CHECK OUT MODE ADJUST SETTING NEXT BACK HOME CONFIG CHECK OUT MODE ADJUST SETTING NEXT M24799 2 M24810 Use the Back and Next buttons to navigate through the configuration menus. Pressing Next enters the selected option for that menu item and advances to the next menu. Adjust settings up or down by pressing the Adjust Setting button.
HZ432 TrueZONE Operation The HZ432 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information. Much of this information, as well as configuration information, is listed on the label on the inside of the HZ432 cover. For users who prefer French or Spanish labels, they are provided in the 69-2070FS document. Cut them out and attach them to the inside of the HZ432 cover.
Installation Guide Advanced Configuration Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 10 for instructions on using these buttons. Table 6. Advanced Configuration.
HZ432 TrueZONE Checkout To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on page 10 for instructions on using these buttons. Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation. Steps 11–14 verify thermostat operation and correct wiring.
Warranty Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPRO , FocusPRO®, PRO 4000, PRO 3000, LineVolt PRO, Digital Round , and Modern Round (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of installation.