SmartVFD HVAC2 PRODUCT DATA • Fire Mode feature • Integrated RFI-filters • Models available with or without Class C2 EMC filter • Wide input and output connection possibilities • Configurable inputs and outputs • 30 second Start-Up Wizard • Easy “keypad to remote” change with 1 button • Parameter upload/download even without main power to the drive with HVFDCABLE accessory • Quiet motor operation with 4 kHz switching frequency • Overtemperature ride-through • Motor pre-heat • Power ride-through GENERAL •
SMARTVFD HVAC2 Motor Connection Output voltage: 0 - Uin Output current: Continuous rated current IN at ambient temperature max. +50 ºC (dependson the unit size), overload: 1.5 x IN max 1 min / 10 min Starting current/torque: Current 2 x IN for 2 sec in every 20 sec period. Torque depends on motor. Output frequency: 0…320 Hz Frequency resolution: 0.01 Hz Altitude: 100% load capacity (no derating) up to 3281 ft. (1000 m). 1% derating for each 328 ft. (100 m) above 3281 ft. (1000 m); max. 6562 ft.
SMARTVFD HVAC2 MODELS Mains voltage 208-240 V Table 1. Mains voltage 208-240 V, 50/60 Hz, 1~ series. Motor shaft power Rated loadability 100% contin. current IN [A] Part number 150% overload current [A] P [HP] Nominal input current P [KW] [A] Mechanical size Weight (lbs) HVFD2D1B0003E2 1.7 2.6 0.33 0.25 4.2 MI1 1.21 HVFD2D1B0005E2 2.4 3.6 0.5 0.37 5.7 MI1 1.21 HVFD2D1B0007E2 2.8 4.2 0.75 0.55 6.6 MI1 1.21 HVFD2D1B0010E2 3.7 5.6 1 0.75 8.3 MI2 1.54 HVFD2D1B0015E2 4.
SMARTVFD HVAC2 Mains voltage 115 V Table 3. Mains voltage 115 V, 50/60 Hz, 1~ series. Motor shaft power Rated loadability Part number 100% contin. current IN [A] 150% overload current [A] P [HP] Nominal input current P [KW] Mechanical size [A] Weight (lbs) HVFD2D1A0003 1.7 2.6 0.33 0.25 9.2 MI2 1.54 HVFD2D1A0005 2.4 3.6 0.5 0.37 11.6 MI2 1.54 HVFD2D1A0007 2.8 4.2 0.75 0.55 12.4 MI2 1.54 HVFD2D1A0010 3.7 5.6 1 0.75 15 MI2 1.54 HVFD2D1A0015 4.8 7.2 1.5 1.1 16.
SMARTVFD HVAC2 PRODUCT IDENTIFICATION CODE HVFD2D 3 C 0000 E2 EMC Filter E2 = EMC Filter (Blank) = No EMC Filter Nominal Horsepower 0003 = .33 HP 0040 0005 = .5 HP 0050 0007 = .75 HP 0075 0010 = 1 HP 0100 0015 = 1.5 HP 0150 0020 = 2 HP 0200 0030 = 3 HP 0250 = = = = = = = 4 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP Nominal Voltage A = 105 V - 120 V B = 208 V - 240 V C = 380 V - 480 V F = 520 V - 600 V Phases 1 = Single Phase 3 = 3-Phase Product Family HVFD2D = Honeywell SmartVFD HVAC2 MCR36499A Fig. 1.
SMARTVFD HVAC2 MECHANICAL MOUNTING There are two possible ways to mount SmartVFD HVAC2 in the wall. For MI1-MI3, either screw or DIN-rail mounting; For MI4-MI5, screw or flange mounting. MI3 =M5 MI2 MI1 =M5 LOC REM BACK RESET OK =M4 M36503 LOC REM BACK RESET LOC REM BACK RESET Fig. 5. Flange mounting, MI4 - MI5 OK OK OK LOC REM BACK RESET 14-1/2 (370) Ø 1/4 (7) DRIVE OUTLINE 13/64 (6) M36500 OPENING OUTLINE Fig. 2.
SMARTVFD HVAC2 DIMENSIONS W2 D D2 W3 A H2 H (H1) H3 LOC REM BACK RESET OK D (D1) W (W1) M36508 Fig. 9. SmartVFD HVAC2 dimensions, MI1 - MI3. W2 M36510 W3 H (H1) H3 H2 Frame Dimensions in inches (mm) MI2 MI3 A .7 (17) .9 (22.3) B 1.7 (44) 4 (102) Fig. 11. SmartVFD HVAC2 dimensions, MI2 - 3 Display Location. B L1 L2 L3 DC+R+ R- DC- U/T1 V/T2 W/T3 W (W1) D (D1) M36509 A Fig. 10. SmartVFD HVAC2 dimensions, MI4 - MI5. Table 6. SmartVFD HVAC2 dimensions in inches (mm).
SMARTVFD HVAC2 COOLING Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below. If several units are mounted above each other the required free space equals C + D. Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit. The amount of cooling air required is indicated below.
SMARTVFD HVAC2 CABLING AND FUSES Use cables with heat resistance of at least 158 °F (70 °C). The cables and the fuses must be dimensioned according to the tables below. The fuses function also as cable overload protection. These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. In any other case, ask the factory for more information. Table 9. Cable types required to meet standards. EMC category cat. C2 cat.
SMARTVFD HVAC2 Table 13. Cable and fuse sizes for SmartVFD HVAC2, 208 - 240 V, 3~. Terminal cable size (min/max) Frame Fuse [A] Horsepower 6 Mains cable Cu [AWG] 3*16+16 Motor cable Cu [AWG] 3*16+16 Main terminal [AWG] 16-12 Earth terminal [AWG] 16-12 Control terminal [AWG] 20-16 Relay terminal [AWG] MI1 .33-.75HP 20-16 MI2 1-2HP 10 3*16+16 3*16+16 16-12 16-12 20-16 20-16 MI3 3HP 20 3*14+14 3*14+14 16-10 16-10 20-16 20-16 MI4 4-7.
SMARTVFD HVAC2 3~ (380, 480V) MAINS 3~ (380, 480V) MOTOR OUT BRAKE RESISTOR MOTOR (NOT USED) MAINS MOTOR OUT MOTOR BRAKE RESISTOR (NOT USED) M36557 M36556 Fig. 16. SmartVFD HVAC2 power connections, MI4. Fig. 17. SmartVFD HVAC2 power connections, MI5. Control cabling ATTACH THE SUPPORT AFTER INSTALLING ATTACH THE SUPPORT AFTER INSTALLING THE POWER CABLES ATTACH THIS PLATE BEFORE INSTALLING THE POWER CABLES ATTACH THIS PLATE BEFORE INSTALLING THE POWER CABLES M36559 Fig. 19.
SMARTVFD HVAC2 CONTROL CABLE TIGHTENING TORQUE: 0.4 NM STRIP THE PLASTIC CABLE COATING FOR 360° EARTHING M36560 M36562 Fig. 20. Open the lid, MI1 - MI3. Fig. 22. Install the control cables. MI1 - MI3. M36561 Fig. 21. Open the lid, MI4 - MI5. M36563 Fig. 23. Install the control cables. MI4 - MI5. AI2 GND DO- DI4 DI5 DI6 AO DO+ 4 5 1 13 2 14 3 15 6 16 7 18 8 22 20 9 RO1 RO1 NO CM 23 26 25 10 +10VAI1 GND 24V DI-C DI1 DI2 DI3 RO2 NO * A B 24 RO2 RO2 CM NC Fig. 24.
SMARTVFD HVAC2 The table below shows the SmartVFD HVAC2 control connections with the terminal numbers. Table 16. SmartVFD HVAC2 General purpose application default I / O configuration and connections for control board P = Programmable function. 1–10 kΩ Terminal Signal Factory preset Description 1 +10 Vref Ref. voltage out Maximum load 10 mA 2 AI1 Analog signal in 1 3 GND I / O signal ground 6 24 Vout 24 V output for DI's ±20%, max.
SMARTVFD HVAC2 FEATURES / FUNCTIONS Easy to set-up features Table 17. Feature Functions Benefit 30 second Start-up wizard Quick wizard allows you to set up basic parameters upon first power up of drive. Speeds up drive set-up for basic parameters. Includes fire mode set-up if needed. “Keypad – Remote” Operation Push the Local/Remote button. Single button operation to change the control to manual (keypad) and back.
SMARTVFD HVAC2 VFD and motor control features Table 20. Feature Functions Benefit Flying start Ability to get an already spinning fan under speed control Improved performance Ease of application Inbuilt PID controller Capability to make a standalone system with sensor connected directly to the inverter for complete PI- control. Cost saving OPTIONAL ACCESSORIES Table 21.
SMARTVFD HVAC2 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you. Home and Building Technologies In the U.S.
SmartVFD HVAC2 DONNÉES DU PRODUIT INFORMATIONS D'ORDRE GÉNÉRAL Les variateurs de fréquence SmartVFD HVAC2 permettent un contrôle de vitesse continu pour diverses applications : • Pompes • Ventilateurs • Compresseurs CARACTÉRISTIQUES • Format compact : fait gagner de la place dans l'armoire de votre équipement • Modèles disponibles jusqu'à 25 HP • Support de moteur à aimants permanents • Fonctionnalité d'optimisation énergétique • Données de processus FB (Fieldbus) programmable • Supervisions des limites r
SMARTVFD HVAC2 Raccordement du moteur Particules mécaniques : IEC 721-3-3, unité en service, classe 3S2 Tension de sortie : 0 - Uin Courant de sortie : Courant nominal continu IN à une température ambiante maximale de +50 °C (selon la taille de l'unité), surcharge : 1,5 x IN max 1 min / 10 min Courant/couple de démarrage : Courant 2 x IN pendant 2 s toutes les 20 s. Le couple dépend du moteur. Fréquence de sortie : 0...
SMARTVFD HVAC2 MODÈLES Tension secteur 208-240 V Tableau 1. Tension secteur 208-240 V, 50/60 Hz, série monophasée. Puissance de l'arbre du moteur Capacité de charge nominale Courant continu à 100 % IN [A] Numéro de pièce HVFD2D1B0003E2 1.7 Courant de surintensité à 150 % [A] P [HP] Courant d'entrée nominal P [KW] 2.6 0.33 0.25 HVFD2D1B0005E2 2.4 3.6 0.5 0.37 HVFD2D1B0007E2 2.8 4.2 0.75 0.55 HVFD2D1B0010E2 3.7 5.6 1 0.75 HVFD2D1B0015E2 4.8 7.2 1.5 1.1 HVFD2D1B0020E2 7 10.5 2 1.
SMARTVFD HVAC2 Tension secteur 115 V Tableau 3. Tension secteur 115 V, 50/60 Hz, série monophasée. Puissance de Courant d'entrée l'arbre du moteur nominal Capacité de charge nominale Numéro de pièce Courant continu à 100 % IN [A] Courant de surintensité à 150 % [A] P [HP] P [KW] Dimensions Poids mécaniques (lb) [A] HVFD2D1A0003 1.7 2.6 0.33 0.25 9.2 MI2 1.54 HVFD2D1A0005 2.4 3.6 0.5 0.37 11.6 MI2 1.54 HVFD2D1A0007 2.8 4.2 0.75 0.55 12.4 MI2 1.54 HVFD2D1A0010 3.7 5.
SMARTVFD HVAC2 CODE D'IDENTIFICATION DES PRODUITS HVFD2D 3 C 0000 E2 Filtre CEM E2 = Filtre CEM (Vide) = Pas de filtre CEM Puissance nominale 0003 = 0,33 HP 0040 0005 = 0,5 HP 0050 0007 = 0,75 HP 0075 0010 = 1 HP 0100 0015 = 1,5 HP 0150 0020 = 2 HP 0200 0030 = 3 HP 0250 = = = = = = = 4 HP 5 HP 7,5 HP 10 HP 15 HP 20 HP 25 HP Tension nominale A = 105 V - 120 V B = 208 V - 240 V C = 380 V - 480 V F = 520 V - 600 V Phases 1 = monophasé 3 = triphasé Gamme de produits HVFD2D = Honeywell SmartVFD HVAC2 MFCR
SMARTVFD HVAC2 MONTAGE MÉCANIQUE Il existe deux possibilités d'installation du SmartVFD HVAC2 au mur. Pour MI1-MI3, montage à vis ou sur rail DIN; pour MI4-MI5, montage à vis ou sur bride. MI3 =M5 MI2 MI1 LOC REM BACK RESET OK =M5 =M4 M36503 LOC REM BACK RESET LOC REM BACK RESET Fig. 5. Montage sur bride, MI4 - MI5 LOC REM BACK RESET OK OK OK 14-1/2 (370) Ø 1/4 (7) SCHÉMA DU VARIATEUR 13/64 (6) SCHÉMA D'OUVERTURE M36500 6 HAUT (153) Fig. 2.
SMARTVFD HVAC2 DIMENSIONS W2 D D2 W3 A H2 H (H1) H3 LOC REM BACK RESET OK D (D1) W (W1) M36508 Fig. 9. Dimensions du SmartVFD HVAC2, MI1 - MI3. W2 M36510 W3 H (H1) H2 Châssis Dimensions en pouces (mm) H3 MI2 MI3 A .7 (17) .9 (22.3) B 1.7 (44) 4 (102) Fig. 11. Dimensions du SmartVFD HVAC2, MI2 - 3 Emplacement de l'affichage. B L1 L2 L3 DC+R+ R- DC- U/T1 V/T2 W/T3 W (W1) D (D1) M36509 A Fig. 10. Dimensions du SmartVFD HVAC2, MI4 - MI5. Tableau 6.
SMARTVFD HVAC2 REFROIDISSEMENT Il convient de laisser suffisamment d'espace libre au-dessus et en dessous du variateur de fréquence pour garantir une circulation de l'air et un refroidissement suffisants. Vous trouverez les dimensions requises pour l'espace libre dans le tableau ci-dessous. Si plusieurs appareils sont installés l'un au-dessus de l'autre, l'espace libre requis équivaut à C + D.
SMARTVFD HVAC2 CÂBLAGE ET FUSIBLES Utilisez des câbles dotés d'une résistance à la chaleur d'au moins 158 °F (70 °C). Les câbles et les fusibles doivent posséder les dimensions indiquées dans les tableaux ci-dessous. Les fusibles jouent également le rôle de protection contre la surcharge des câbles. Les présentes instructions s'appliquent uniquement aux cas possédant un moteur et un raccordement de câble reliant le variateur de fréquence au moteur.
SMARTVFD HVAC2 Tableau 13. Tailles de câbles et de fusibles pour le SmartVFD HVAC2, 208 - 240 V, triphasé. Taille du câble de la borne (min./max.
SMARTVFD HVAC2 Triphasé (380 V, 480 V) Triphasé (380 V, 480 V) SORTIE MOTEUR SECTEUR RÉSISTANCE SECTEUR DE FREINAGE MOTEUR (NON UTILISÉE) SORTIE MOTEUR RÉSISTANCE MOTEUR DE FREINAGE (NON UTILISÉE) MF36557 MF36556 Fig. 16. Raccordements électriques du SmartVFD HVAC2, MI4. Fig. 17. Raccordements électriques du SmartVFD HVAC2, MI5.
SMARTVFD HVAC2 COUPLE DE SERRAGE DU CÂBLE DE COMMANDE : 0,4 NM ENLEVEZ LE REVÊTEMENT EN PLASTIQUE DU CÂBLE POUR UNE MISE À LA MASSE À 360° M36560 MF36562 Fig. 20. Ouverture du couvercle, MI1 - MI3. Fig. 22. Installation des câbles de commande. MI1 MI3. M36561 Fig. 21. Ouverture du couvercle, MI4 - MI5. M36563 Fig. 23. Installation des câbles de commande. MI4 MI5.
SMARTVFD HVAC2 Le tableau ci-dessous indique les raccordements de commande du SmartVFD HVAC2 avec les numéros de bornes. Tableau 16. Configuration et raccordements par défaut des E/S pour la carte de commande avec l'application généraliste du SmartVFD HVAC2 P = Fonction programmable. 1–10 kΩ Borne Signal 1 +10 Vref Tension réf. en sortie Préréglage usine Description Charge maximale 10 mA 2 AI1 Signal analogique en 1 3 GND Terre du signal d'E/S Réf.
SMARTVFD HVAC2 CARACTÉRISTIQUES/FONCTIONS Fonctionnalités de configuration facile Tableau 17. Caractéristique Fonctions Avantage Assistant de démarrage L'assistant de démarrage rapide vous permet de configurer les en 30 secondes paramètres de base dès la première mise sous tension du variateur. Accélère la configuration des paramètres de base. Comporte une configuration du mode de déclenchement si besoin.
SMARTVFD HVAC2 Fonctions du fonctionnement sans coupure Tableau 19.
SMARTVFD HVAC2 Par l'utilisation de la présente documentation Honeywell, vous consentez à ce qu'Honeywell ne possède aucune responsabilité pour tous dommages résultant de votre utilisation ou modification de la dite documentation. Vous défendrez et indemniserez Honeywell, ses sociétés affiliées, filiales pour et contre toute responsabilité, frais ou dommages, y compris les honoraires d'avocats, résultant de quelque manière, ou survenant en connexion avec toute modification à la documentation de votre part.