Install Instructions

INSTALLATION INSTRUCTIONS
62-0220-03
C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP
Series 2000 Electronic Temperature Sensors
C7031G, C7041F, T775-SENS-OAT OUTDOOR; STRAP-ON, C7041B,
C DUCT; C7031D, C7041D IMMERSION
SENSOR APPLICATIONS
Table 1. Electronic Sensor Application Guide
C7031D,
C7041D
C7031G, C7041F,
T775-SENS-OAT
C7041B,C
Strap-on
Model Application Output Element Insertion Length
C7031D Immersion 1097 ohms @ 77 F 5 in. (127 mm)
C7031G Outdoor 3484 ohms @ 77 F
C7041B Duct 20 K ohm NTC @ 77 F 6 in. (152) or 12 in. (305 mm)
C7041C Duct 20 K ohm NTC @ 77 F 18 in. (457 mm)
C7041D Immersion 20 K ohm NTC @ 77 F 5 in. (127 mm)
C7041F Outdoor 20 K ohm NTC @ 77 F
C7041K Strap-On 20 K ohm NTC @ 77 F
T775-SENS-OAT Outdoor 1097 ohms @ 77 F
T775-SENS-STRAP Strap-On 1097 ohms @ 77 F
C7041B,C
Duct
C7031D,
C7041D
Immersion
C7031G, C7041F,
T775-SENS-OAT
Outdoor
Be sure to take advantage of the entire line of quality Honeywell Sensors
C7041P
Button
Probe
Strap-on
C7041R
Duct
Rigid
Copper
C7031J,
C7041J
Duct
Cable
Averaging