Install Instructions

X-XX UL
INSTALLATION INSTRUCTIONS
Copyright © 1997 Honeywell Inc. • All Rights Reserved
43191679-111/-
112
Auxiliary Potentiomet
ers
APPLICATION
The 43191679-111/-112 Auxiliary Potentiometers can be
used as feedback potentiometers and to provide remote
indication of the valve position. They are used with valve
actuators as shown in Table 1. Fig. 1 illustrates the parts
furnished with these potentiometers.
Table 1. Auxiliary Potentiometers.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could result in the equipment not operating
properly.
2. Check the part numbers in Table 1 to be sure that
the product is suitable for your application.
3. The installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check product operation.
CAUTION
Disconnect the power supply to the auxiliary
potentiometer and actuator before beginning
installation to prevent electrical shock or equipment
damage.
Mounting, Connecting, and Adjusting
1 Remove actuator cover.
2 Turn potentiometer shaft fully clockwise. See Fig. 2.
a
Over nominal stroke (3/4 in.), usable potentiometer range
is 135 ohms.
Fig. 1. Auxiliary Potentiometer Parts.
Actuator
Single 10K Ohm
Potentiometer
Single 220 Ohm
Potentiometer
a
ML6425A,B 43191679-111 43191679-112
ML7425A,B
C8372
T Y G
Fig. 2. Installing potentiometer, terminal label,
and connector block.
C8373
a
b
d
c
T Y G
63-2522