Economical inverter with simple operation
Standard Specifications 1-/3-phase 200V class Model NES1- Output Ratings Input Rating Applicable motor size, 4-pole kW(HP) *1 200V 240V Rated output current (A) *2 Overload capacity(output current) Rated output voltage (V) Rated capacity Rated input current (A) Weight (kg) SB LB 3.1 1.8 SB LB 0.7 0.
Dimensions [Unit: mm(inch)] Inches for reference only NES1-002SB, 004SB, 002LB, 004LB, 007LB 68(2.68) 62(2.44) 118(4.65) 128(5.04) φ4.5(0.18) 4.5(0.18) 56(2.20) 62(2.44) D Model D 002LB, 002SB 76 (2.99) 007LB 115 (4.53) 004LB, 004SB 91 (3.58) *002 to 007LB/002,004SB:without cooling fan. NES1-007SB, 015SB, 022SB, 015LB, 022LB, 004HB, 007HB, 015HB, 022HB, 040HB 108(4.25) 96(3.78) 118(4.65) 128(5.04) φ4.5(0.18) 5(0.20) 96(3.78) D Model 007SB, 004HB, 007HB D 96 (3.
Operation and Programming NE-S1 Change and setting parameter by Keypad (NES1-OP).
Operation / Terminal Functions Terminal Description Terminal Symbol Terminal Symbol Terminal Arrangement Terminal Name L1,L2,N/L3 U/T1,V/T2,W/T3 Main power supply input terminals Inverter output terminals +1,+ ● R (L1) U (T1) DC reactor connection terminals Ground connection terminal Screw Diameter and Terminal Width Model 002-004SB 002-007LB ● Screw diameter (mm) Terminal width W (mm) M3.5 7.1 M4 9.
Function List The parameter tables in this chapter have a column titled "Run Mode Edit." An Ex mark x means the parameter cannot be edited; a Check mark means the parameter can be edited. The table example to the right contains two adjacent marks "x ". These two marks (that can also be ") correspond to low-access or high-access levels to Run Mode edits (note Lo and Hi in column heading).Parameter shown in "xx" or " case "b037" is "00" (Full display).
Function List [ X:: Allowed Not allowed ] A Group: Standard Functions Function Code V/f Characteristic A044 A244 A045 A245 A046 A246 A047 A247 DC braking Frequency Upper/Lower Limit and Jump Frequency PID Control AVR function Automatic Energy Saving Operation mode and acc./dec.
Function List [ X:: Allowed Not allowed ] b Group: Fine-tuning Functions Function Code Electronic thermal Overload restriction Lock b012 b212 b013 b213 b015 b016 Electronic thermal setting Electronic thermal setting, 2nd motor Electronic thermal characteristic Electronic thermal characteristic, 2nd motor Free setting, electronic thermal frequency (1) Free setting electronic thermal ~current1 b017 Free setting, electronic thermal frequency (2) b018 b019 b020 b021 b221 b022 Free setting electronic t
Function List [ X:: Allowed Not allowed ] C Group: Intelligent Terminal Functions Function Code Intelligent input terminal C001 Terminal [1] function C002 Terminal [2] function C003 Terminal [3] function C004 Terminal [4] function C005 Terminal [5] function C011- C015 Intelligent input terminal Serial communication Analog meter setting Others Name Range 00(FW:Forward), 01(RV:Reverse), 02-04(CF1-CF3:Multispeed command), 06(JG:Jogging), 07(DB:External DC braking), 08(SET:Second motor consta
Protective Functions Error Codes (Standard) Over Current Trip Over Voltage Trip (Lighting(1sec) & Blink) Under Voltage Trip (Same Blink(1sec)) (Alternate Blink(1sec)) RUN RUN RUN ALM ALM ALM Over Load Trip Major Failures *1 (Same Lighting) Other Failures (Light Out & Lighting) (Light Out & Blink(1sec)) RUN RUN RUN ALM ALM ALM *1 The Major fault: When a memory error, CPU error and Ground fault.
Connecting Diagram Source type logic NE-S1 series Power source <200V class> 1-/3-phase 200 to 240V+10%, -15% 50/60Hz ±5% <400V class> 3-phase 380 to 480V+10%, -15% 50/60Hz ±5% R(L1) (T1) U S(L2) (T2) V T/N(L3) DC24V Motor (T3) W P24 5 (+1)PD DC link choke (+)P 4 3 Intelligent input terminals (5 terminals) Source type 2 AL2 1 AL1 AL0 PLC Short bar Intelligent relay output contacts L DC 0~10V(8bit) FM DC10V H Frequency setting 1k ~2k Current input 0mA~20mA 11 O(Note3) CM2 OI(Note3
Connecting Diagram Sink type logic (default) NE-S1 series Power source <200V class> 1-/3-phase 200 to 240V+10%, -15% 50/60Hz ±5% <400V class> 3-phase 380 to 480V+10%, -15% 50/60Hz ±5% R(L1) (T1) U S(L2) (T2) V DC24V T/N(L3) Motor (T3) W P24 Short bar (+1)PD PLC 5 DC link choke (+)P 4 Intelligent input terminals (5 terminals) Sink type 3 AL2 2 Intelligent relay output contacts AL1 1 AL0 L DC 0~10V(8bit) FM DC10V H Frequency setting 1k ~2k Current input 0mA~20mA 11 O(Note3) CM2 OI(N
Wiring and Accessories Power Supply Input Voltage 1-phase 200V Motor Output (kW(HP) 0.2(1/4) NES1-002SB 0.75(1) NES1-007SB AWG14 0.4(1/2) 2.2(3) 0.2(1/4) 3-phase 200V 0.4(1/2) 0.75(1) 1.5(2) 2.2(3) 0.4 (1/2) 3-phase 400V Wiring Power Lines AWG AWG14 1.5(2) Fuse Model 0.75(1) 1.5(2) 2.2(3) 4.0(5) NES1-004SB NES1-015SB NES1-022SB NES1-002LB NES1-004LB NES1-007LB NES1-015LB NES1-022LB NES1-004HB NES1-007HB NES1-015HB NES1-022HB NES1-040HB AWG14 AWG10 AWG10 mm2 2.0 2.0 1.25 1.25 2.0 1.
Accessories ■Operator, Cable 4X-KITmini (For installation with OPE-SR mini) ●Operator Screw Model NES1-OP OPE-SR mini OPE-SBK OPE-SR WOP Potentiometer Remote Control ○ ○ ○ Copy function Panel External Gaske t ○ ○ ○ Fron t C over ○ ○ Internal Gaske t 1 Seal ●Cable Internal Gaske t 2 Cable Model ICS-1 ICS-3 L Cable Length 1m(3.3ft) 3m(9.8ft) Rear Cove r You can mount the keypad with the potentiometer for a NEMA1 rated installation.
Torque characteristics Torque characteristics Base frequency = 60Hz Base frequency = 50Hz Short time performance 150 130 130 Output torque (%) Output torque (%) Short time performance 150 Continuous performance 100 95 80 55 45 100 90 Continuous performance 75 55 45 35 35 1 6 20 60 Output frequency (Hz) 120 1 5 16.
For Correct Operation Application to Motors Application to general-purpose motors Operating frequency The overspeed endurance of a general-purpose motor is 120% of the rated speed for 2 minutes (JIS C4,004). For operation at higher than 60Hz, it is required to examine the allowable torque of the motor, useful life of bearings, noise, vibration, etc. In this case, be sure to consult the motor manufacturer as the maximum allowable rpm differs depending on the motor capacity, etc.
Installation location and operating environment Avoid installation in areas of high temperature, excessive humidity, or where moisture can easily collect, as well as areas that are dusty, subject to corrosive gasses, mist of liquid for grinding, or salt. Install the inverter away from direct sunlight in a well-ventilated room that is free of vibration. The inverter can be operated in the ambient temperature range from -10 to 50˚C.