L 300 IP Series Inverter Quick Reference Guide x Three-phase input 400V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No.: QRGL300IPV1 y Oct.
Caution: Be sure to read the L300IP Inverter Manual and follow its Cautions and Warnings for the initial product installation. This Quick Reference Guide is intended for reference use by experienced users in servicing existing installations.
Control Circuit Terminals Terminal Description name P24 +24V power for inputs CM1 +24V common PLC Common for logic inputs 1, 2, 3, 4, 5 Intelligent (programmable) discrete logic inputs FW Forward/stop command 11C-11A Intelligent 12C-12A (programmable) relay outputs TH Thermistor input FM PWM output Ratings and Notes 24VDC supply, 100 mA max. Common for 24V supply, FW, TH, inputs 1 to 5, and FM.
Terminal Name Description Ratings and Notes AM Voltage analog output 0 to 10VDC, 2 mA max. AMI Current analog output 4-20 mA, nominal load impedance 250Ω L Common for analog inputs Sum of OI, O, and H currents (return) OI Analog input, current 4 to 19.6 mA range, 20 mA nominal O Analog input, voltage 0 to 9.6 VDC range, 10VDC nominal, 12VDC max., input impedance 10 kΩ H +10V analog reference 10VDC nominal, 10 mA max.
Basic Wiring Diagram The following wiring diagram shows the power and motor connections for basic operation. The optional signal input wiring supports external Fwd and Rev Run command, and a speed potentiometer.
Inverter Keypad Operation Run/Stop LED Parameter Display Power LED Program/Monitor LED Alarm LED POWER HITACHI ALARM 5 0.
• Stop/Reset Key – Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm which has tripped. • Parameter Display – A 4-digit, 7-segment display for parameters and function codes. • Display Units: Hertz/Volts/Amperes/kW/% – These LEDs indicate the units associated with the parameter display. When the display is monitoring a parameter, the appropriate LED is ON. In the case of kW units, both Volts and Amperes LEDs will be ON.
Keypad Navigation Map Monitor Mode d002–d090 o.0 0 Program Mode FUNC. FUNC. 1 1 1 FUNC. 2 2 FUNC. 1 1 1 F o01 2 bo01 2 FUNC. 2 Edit FUNC. FUNC. PRG LED 1 2 3.4 2 b1 1 3 2 2 1 2 c o01 2 F 004 ho03 2 2 Increment/ decrement value 2 1 Po50 do01 h206 1 A––– 1 Uo01 1 c1 23 2 b– – – 1 FUNC. 2 1 C––– 1 2 FUNC. 2 Po01 2 H––– 1 2 1 P––– 1 Uo1 2 Po50 2 U––– PRG LED FUNC. do01 1 o.
Powerup Test The Powerup Test procedure uses minimal parameter settings to run the motor. The procedure describes two alternative methods for commanding the inverter: via the inverter keypad, or via the logic terminals. • Check power input and motor output wiring (see page 4 diagram). • If using logic terminals for testing, verify correct wiring on [FW], [CM1], [H], [O], and [L] per the diagram on page 4. • Reverse [RV] input wiring (defaults to terminal [8]) is optional.
Error Codes The L300P series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.
Error Code Name Probable Cause(s) E21 Inverter thermal trip • Inverter internal temperature is above the threshold E23 Gate array error • An internal inverter error has occurred (CPU / gate array IC) E24 Phase failure detection • One of three lines of the 3-phase power is missing E30 IGBT error • Instantaneous over-current on any IGBT (output transistor) device E35 Thermistor • Thermistor input, [TH] and [CM1], is over the temp.
Restoring Factory Default Settings Action Display Press the FUNC. , 1 or 2 keys as needed. Press the FUNC. Function/Parameter b- - - “b” Group selected b001 First “b” Group parameter key. Press/hold the 1 key until... Press the FUNC. key. If setting is correct, then skip next step. b085 Country code for initialization selected 02 00 = Japan 01 = Europe 02 = United States To change country code, press 1 or 2 key to set; Press the FUNC. STR to store. b085 Country code for key.
Parameter Tables “d” Group: Monitoring Functions Parameter Monitoring Func.
Trip History and Programming Error Monitoring Func.
Parameter tables for user-settable functions follow these conventions: • Some parameters have 2nd and 3rd motor equivalents, indicated by the x2xx and x3xx parameter codes in the left-most column. • Some parameters specify an option code. Where applicable, the options codes will be in a bulleted list in the Name/Description column. • The default values apply to all models unless otherwise noted for each parameter... –FE2 (Europe) / – FU2 (U.S.) / –FR (Japan).
“A” Group: Standard Functions Func.
Func. Code A021 to A035 Name / Description Default Value –FE2 / –FU2 / –FR Multi-speed frequency settings (for both motors) 0.00 A038 Jog frequency setting 1.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR A062/ Frequency lower limit setting A262 0.00 A063 A065 A067 Jump (center) frequency setting 0.00 A064 A066 A068 Jump (hysteresis) frequency width setting 0.50 A069 Acceleration pause frequency setting 0.00 A070 Acceleration pause time setting 0.0 A071 PID Enable • 00 PID operation OFF • 01 PID operation ON 00 A072 PID proportional gain 1.0 A073 PID integral time constant 1.0 A074 PID derivative time constant 0.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR A097 Acceleration curve selection • 00 Linear • 01 S-curve • 02 U-shape • 03 Reverse U-shape 00 A098 Deceleration curve selection • 00 Linear • 01 S-curve • 02 U-shape • 03 Reverse U-shape 00 A101 [OI]–[L] input active range start frequency 0.00 A102 [OI]–[L] input active range end frequency 0.00 / 60.00 / 0.00 A103 [OI]–[L] input active range start current 20. A104 [OI]–[L] input active range end current 100.
“b” Group: Fine-tuning Functions Func. Code Name / Description Default Value –FE2 / –FU2 / –FR b001 Selection of automatic restart mode • 00 Alarm output after trip, automatic restart disabled • 01 Restart at 0Hz • 02 Resume operation after frequency matching • 03 Resume previous freq. after freq. matching, then decelerate to stop and display trip info 00 b002 Allowable under-voltage power failure time 1.0 b003 Retry wait time before motor restart 1.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR b022 Overload restriction setting b023 Deceleration rate at overload restriction b024 Overload restriction operation mode (2) • 00 Disabled • 01 Enabled for accel and constant speed • 02 Enabled for constant speed only b025 Overload restriction setting (2) b026 Deceleration rate at overload restriction (2) 1.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR b085 Country code for initialization • 00 Japan version • 01 Europe version • 02 US version • 03 (reserved) b086 Frequency scaling conversion factor 1.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR b112 Free-setting V/f frequency (7) 0. b113 Free-setting V/f voltage (7) 0.0 Set Value “C” Group: Intelligent Terminal Functions Func.
Func. Code Name / Description Default Value –FE2 / –FU2 / –FR 01 C040 Overload signal output mode • 00 During accel/decel • 01 During constant speed C041 Overload level setting C042 Frequency arrival setting for accel 0.00 C043 Arrival frequency setting for decel 0.00 C044 PID deviation level setting 3.0 C061 Electronic thermal warning level 80.
Func. Code C091 Name / Description Debug mode enable • 00 Display Default Value –FE2 / –FU2 / –FR Set Value 00 • 01 No display C101 Up/Down memory mode selection • 00 Clear last frequency (return to F001) • 01 Keep last freq.
“P” Group: Expansion Card Functions Func.
“U” Group: User-selectable Menu Functions Func.
Intelligent Input Terminal Listing Symbol Code Input Terminal Name RV 01 Reverse Run/Stop CF1 02 Multi-speed select, Bit 0 (LSB) CF2 03 Multi-speed select, Bit 1 CF3 04 Multi-speed select, Bit 2 CF4 05 Multi-speed select, Bit 3 (LSB) JG 06 Jogging DB 07 External DC injection braking signal SET 08 Set (select) second motor data 2CH 09 2-stage accel and decel FRS 11 Free-run stop EXT 12 External trip USP 13 Unattended start protection CS 14 Commercial power source SFT
Intelligent Output Terminal Listing Symbol Code Input Terminal Name RUN 00 Run signal FA1 01 Freq. arrival type 1 – constant speed FA2 02 Freq. arrival type 2 – over-frequency OL 03 Overload advance notice signal OD 04 Output deviation for PID control AL 05 Alarm signal FA3 06 Freq.
Analog Input Configuration The following tables show the parameter settings required for various analog input signal types.
Analog Output Function Listing The following table shows all seven functions available for assignment to the three analog output terminals: • Terminal [FM], option set by C027 • Terminal [AM], option set by C028 • Terminal [AMI], option set by C029 Option Code Function Name Description Actual motor speed, represented by PWM signal Corresponding Signal Range 00 Output frequency 01 Output current Motor current (% of maximum rated output current), represented by PWM signal 0 to 200% 03 Digital output
Programming Error Codes The L300IP inverter operator keypad displays a special code (begins with the character) to indicate a programming error. Programming errors exist when one parameter conflicts with the meaningful range permitted by related parameter(s). Note that particular real-time frequency (speed) input levels can cause a conflict in some situations. After a conflict exists, the error code will appear on the display, or you can view it later with D090 in Monitor Mode.
Prg Error Code Function code of parameter out of bounds Boundary defined by...
Notes: 33