REV DESCRIPTION DATE G REVISED PER ECO E6030-13 APPROVED NOTE: Cover sheet is for Revision Control only, and is not to be sent with document. REV SHEET 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 59 50 51 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 REV STATUS G G G G G G G G G G G OF SHEETS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 REV SHEET TOLERANCES APPROVALS DATE HID CORPORATION .XX = +/- .03” DWN G.
Installation Manual – 6030-900 Rev G ProxPro Plus Wiegand/Clock and Data Reader 6030/8A _____________________________________________________________________________________________________ HID Corporation 9292 Jeronimo Road Irvine, CA 92618-1905 USA TEL (714) 598-1600 (800) 237-7769 FAX (714) 598-1690 Web page, E-mail - www.hidcorp.
Table of Contents ProxPro Plus System Overview.............................................................................................3 Operation ...............................................................................................................................3 Product Configuration/Ordering Options .............................................................................3 Installation Notes................................................................................................
ProxPro Plus System Overview The ProxPro Plus reader is a self contained proximity reader. This product is derived from the popular ProxPro Reader with added features that include a side cable exit for glass mount locations, and a longer read range. The two piece polycarbonate enclosure has a cable grommet that seals the cable for the side exit option and a feed through strain relief connector for the rear exit option. A bi-color LED and beeper enhance user feedback.
Installation Notes Near Metal - The typical read distance specification (9.5 inches) refers to operation without metal in the vicinity of the Reader. Use the metal compensation Jumper, P1, if mounting within 2” of a metal surface. Place the jumper on P1 between pins 1 and 2 when mounting to a metallic surface or to a junction box with a metal cover plate. Otherwise, the jumper should be between pins 2 and 3, the default position (see figure 1).
Installation Procedure Cable Installation Preparation - Determine the desired mounting location for the reader. The reader can be mounted directly to a glass panel using tape (Glass Mount), to the mullion of a glass panel using a side mount bracket (Side Mount), or to an electrical gang box (Wall Mount). Install Cable - Route the interface cable from the mounting location to the power supply and/or the Host. Refer to “Cable Notes” to determine the best cable to use.
Switch Configuration FIGURE 2 Switch description and default settings: SW1-1 Hardware Identity When set in the “ON” position the unit is configured for “Wiegand” Interface. The “OFF” position configures the unit for “Clock and Data” Interface. SW1-2 Beeper Control - On The Beeper may be enabled or disabled to sound when an access card is read. When enabled, the audible tone is sounded when the a card is successfully read.
Glass Mount Installation Parts List 1) 2) 3) 4) ProxPro Plus Reader, Side Cable Exit This Installation Manual Adhesive Foam Tape 5 conductor Alpha 1295 C or equivalent. See cable notes. 5) Power Supply Requirements " " " qty 1 ea. (included) qty 1 ea. (included) qty 3 ft (included) User supplied As required, up to 500’ User supplied Linear, 10-28.5VDC, 120mA Replace cover of reader ensuring that the LED is lined up with the LED lens on the cover.
Side Mount Installation Parts List 1) 2) 3) 4) 5) 6) 7) ProxPro Plus Reader, Side Cable Exit This Installation Manual Mounting Bracket Screw, self tapping, 8-18 x .750, flat head 100° Screw, machine, 6-32 x .750, pan head, blk Washer, flat #6, black 5 conductor Alpha 1295 C or equivalent. See cable notes. 8) Power Supply Requirements " " " qty 1 ea. (included) qty 1 ea. (included) qty 1 ea. (included) qty 2 ea. (included) qty 2 ea. (included) qty 2 ea.
Wall Mount Installationarts List 1) 2) 3) 4) 5) 6) ProxPro Plus Reader, Rear Cable Exit This Installation Manual Screw, self tapping, 6-32 x 1.00, pan head Screw, machine, 8-32 x .875, flat head 82°, black Nut, clinch, black 5 conductor Alpha 1295 C or equivalent. See cable notes. 7) Power Supply Requirements qty 1 ea (included) qty 1 ea (included) qty 2 ea (included) qty 4 ea (included) qty 4 ea (included) User supplied As required, up to 500’ User supplied Linear, 10-28.
Radio Frequency Interference Motors and electronic devices generate RF noise that may interfere with the reception of the signal from a access card. The effect of RF noise is typically a reduction of read range. The Glass Mount ProxPro is susceptible to RF interference as are all devices that receive RF signals. Examples are radios, televisions, and cellular phones. The read range is affected by the amount of interference (noise) in the area.