01/02
Vertical Applications:
Auger hole to required depth.
Insert electrode in center of hole.
Pour Ultrafill to proper depth. The
chart located to the right will help
determine how much Ultrafill will
be required.
Horizontal Applications:
Pour enough Ultrafill to cover
bottom of trench. Place the ground
electrode into trench. Pour in
additional Ultrafill to cover electrode
to the desired depth.
Pounds of Ultrafill Required Per Foot
Hole Size 5/8" Ground Rod 2" EGR
4" 6.3 4.8
6" 14.3 12.9
8" 25.7 24.2
10" 40.2 38.7
12" 57.9 56.5
Pounds of Ultrafill Required Per Foot
Trench Thickness of Ultrafill (Inches)
Width 123 4
4" 2 4.1 6.2 8.2
6" 3.1 6.2 9.2 12.1
8" 4.1 8.2 12.3 16.4
10" 5.2 10.4 15.6 20.8
12" 6.2 12.4 18.6 24.8
For example, placing a 5/8" x 10' ground rod in
a 4" hold would require 63 pounds of Ultrafill.
For example, using 2" of material in a 6" wide
by 10' long trench would require 62 pounds of
Ultrafill.
Liquid Mixing Instructions:
If mixing Ultrafill into a slurry form, use 3 to 3-1/2 gallons of water
per bag of Ultrafill. To facilitate ease of mixing, we recommend the
use of a standard cement mixer.
Installation Instructions
Ultrafill is a low resistance carbon based backfill material, which
dramatically lowers ground system resistance in difficult soil situations.
Ultrafill contains no bentonite or concrete components, which, in
very dry conditions, can cause shrinkage around the ground electrode,
thus rendering it ineffective.
Ultrafill is ideal for use in rocky soil, sand, gravel or any other high
resistance soil conditions. It is also the ideal backfill material for use
around enhanced ground rods and ground grid systems.
Ultrafill is easy to use, safe and effective. Unlike other backfill products, Ultrafill is relatively dust free and does
not require mixing in water prior to installation. (However, Ultrafill does mix readily with water if required).
Ultrafill may be either used in a horizontal trench or grid, or in vertical applications.