Service Instructions ANX, SSX, ASX, GSX, DSX Condensing Units, ANZ, SSZ, ASZ, GSZ, DSZ, VSX, VSZ Split System Heat Pumps with R-410A Refrigerant Blowers, Coils, & Accessories RS6200006r97 December 2019 This manual is to be used by qualified, professionally trained HVAC technicians only. The manufacturer does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
IMPORTANT INFORMATION Table of Contents IMPORTANT INFORMATION.............................2 PRODUCT IDENTIFICATION - MODEL TREE..4 COILS.................................................................6 BLOWERS..........................................................8 AIR HANDLERS.................................................9 LIGHT COMMERCIAL......................................11 PRODUCT IDENTIFICATION - CHARTS........12 LIGHT COMMERCIAL......................................
IMPORTANT INFORMATION SAFE REFRIGERANT HANDLING While these items will not cover every conceivable situation, they should serve as a useful guide. REFRIGERANTS ARE HEAVIER THAN AIR. THEY CAN “PUSH OUT” THE OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE. TO AVOID POSSIBLE DIFFICULTY IN BREATHING OR DEATH: • NEVER PURGE REFRIGERANT INTO AN ENCLOSED ROOM OR SPACE. BY LAW, ALL REFRIGERANTS MUST BE RECLAIMED. • IF AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE ARA BEFORE BEGINNING WORK .
PRODUCT IDENTIFICATION - MODEL TREES PRODUCT IDENTIFICATION A N Z 13 1 2 3 4,5 018 1 AA 6,7,8 9 10,11 Brand Engineering A - Amana® brand Major/Minor Revisions Type N Voltage 1 - 208/230V Single-Phase 60 Hz Deluxe Split System 2 - 220/240V Single-Phase 50 Hz Type 3 - 208/230V Three-Phase 60 Hz X: Condenser R-410A 4 - 460V Three-Phase 60 Hz Z: Heat Pump R-410A 5 - 380/415V Three-Phase 50 Hz SEER 11 - 11 SEER 13 - 13 SEER Nominal Capacity 14 - 14 SEER 18 = 24 = 30 = 36 = 16 - 16 S
PRODUCT IDENTIFICATION S S Z 14 1 2 3 0 6 4,5 36 7,8 1 AA 9 10,11 Brand G Goodman® brand (Standard Feature Set) S Goodman® brand (High Feature Set) A Amana® brand Deluxe D Goodman® brand Deluxe V Value Line Engineering Major/Minor Revisions Voltage Type S 1 - 208/230V Single-Phase 60 Hz Split System 2 - 220/240V Single-Phase 50 Hz Type 3 - 208/230V Three-Phase 60 Hz X: Condenser R-410A 4 - 460V Three-Phase 60 Hz Z: Heat Pump R-410A 5 - 380/415V Three-Phase 50 Hz SEER 13 - 13
COILS PRODUCT IDENTIFICATION C A P F 1 2 3 4 1824 5,6,7,8 A 6 AA 9 10 11,12 Brand C Engineering* Indoor Coil Major/Minor Revisions Refrigerant Charge Unit Application A Upflow/Downflow Coil 4 = R-410A H Horizontal A-Coil 6 = R-410A or R-22 S Horizontal Slab Coil T Coated Coils 2 = R-22 Nominal Width for Gas Furnace A = Fits 14" Furnace Cabinet B = Fits 17-1/2" Furnace Cabinet C = Fits 21" Furnace Cabinet D = Fits 24-1/2" Furnace Cabinet N = Does Not Apply (Horizontal Slab Coils U Unp
COILS PRODUCT IDENTIFICATION 7
BLOWERS PRODUCT IDENTIFICATION MB R 8 1,2 3 4 00 A A 1 5,6 7 8 9 Electrical Brand MB - Modular Blower 1: 208-230V/60Hz/1 PH Design Series Type Constant R - Speed E - Variable Speed A: First Series Circuit Breaker Airflow 8: 800 CFM A: No Circuit Breaker B: Circuit Breaker 12: 1200 CFM 16: 1500 CFM Factory Heat 20: 2000 CFM 00 No Heat 8
AIR HANDLERS PRODUCT IDENTIFICATION AR 1234 UF 18 5,67 B1 81 4A 01 A 1,12 Brand A - Single-piece Air Handler Engineering * Major/ Minor Revisions * Not used for order or inventory management.
PRODUCT IDENTIFICATION 10
PRODUCT IDENTIFICATION A R U F 18 B 1 4 AA 1 2 3 4 5,6 7 8 9 10,11 Brand A Engineering* Single-Piece Major/Minor Revisions Airhandler Unit Application Refrigerant Charge C Ceiling Mount PSC Motor R Multi Position PSC Motor S Multi Position EEM Motor 4 = R-410a Electrical W Wall Mount PSC/EEM Motor 1 208/240V, 1 Phase, 60 Hz Cabinet Finish Cabinet Width U Unpainted B = 17- 1/2" Wide P C = 21" Wide Painted N Uncased D = 24 -1/2" Wide Expansion Device F Flowrator 18 = 1-1/2
LIGHT COMMERCIAL PRODUCT IDENTIFICATION LIGHT COMMERCIAL G S X 11 1 2 3 090 1 4,5 6,7,8 9 AA 10,11 Brand Engineering G - Goodman brand Major/Minor Revisions A - Amana brand Type S Voltage 1 - 208/230V Single-Phase 60 Hz Split System 2 - 220/240V Single-Phase 50 Hz Type 3 - 208/230V Three-Phase 60 Hz X: Condenser R-410A 4 - 460V Three-Phase 60 Hz Z: Heat Pump R-410A 5 - 380/415V Three-Phase 50 Hz SEER 11 - 11 SEER 13 - 13 SEER Nominal Capacity 14 - 14 SEER 16 - 16 SEER 036 - 3 Tons
LIGHT COMMERICAL LIGHT COMMERCIAL PRODUCT IDENTIFICATION - CHARTS PRODUCT IDENTIFICATION GSX11 LIGHT COMMERCIAL GOODMAN® BRAND SPLIT X-R410A CONDENSERS 11 SEER Model/Rev Description GSX11090*AA GSX11120*AA Introduction of Goodman Light Commercial 11 SEER, R-410A Condensers. GSX111203AB GSX110903AB GSX111204AB GSX110904AB 208-230V and 460V 3 Phase condensing units with new ball valve/brackets, suction tube/assembly and panel w/offset.
PRODUCT IDENTIFICATION Split System Heat Pumps ASZ13 AMANA® BRAND SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description ASZ130**1AA Initial release of Amana® Brand 13 SEER Heat Pump R410A. ASZ130**1AB Introduces new revisions with improved circuiting for effective defrost. ASZ130[18, 36-60]1AB ASZ130[24-30]1AC Introduces models containing crankcase heater, CCH switch and upgraded defrost control.
PRODUCT IDENTIFICATION Split System Heat Pumps ASZ14 AMANA® BRAND SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description ASZ140**1AA Initial release of Amana® Brand 14 SEER Heat Pump R410A with sound blankets and Coresense control. ASZ140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. ASZ140**1AC Horizontal style louvers. ASZ140[18, 42-48]1AD ASZ140[24-36, 60]1AE New steel muffler, and suction tubes w/shock loop.
PRODUCT IDENTIFICATION Split System Heat Pumps ASZ14 AMANA® BRAND SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description ASZ140381AA 35" chassis with 6-channel flowrator and ZP29K5 compressor. ASZ140[18-30]1BA Updated ratings and agency information. ASZ140[18-60]1KA Introduction of ready 15, 14 SEER heat pumps to meet the 2015 energy efficiency requirement. ASZ140[42,49]1KB Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap.
PRODUCT IDENTIFICATION Split System Heat Pumps ASZ16 AMANA® BRAND SPLITS Z-R410A HEAT PUMP 16 SEER Description Model/Rev ASZ160**1AA Initial release of Amana® Brand 16 SEER Heat Pump R410A. ASZ160**1AC Introduces models with screw locations moved in the top panel, base pans, louvers, and control box covers. Horizontal style louvers. ASZ160**1AD Muffler and standardized TXV, Compensator using the ASZ18 Seer weldment.
PRODUCT IDENTIFICATION Split System Heat Pumps ANZ13 AMANA® BRAND SPLIT SYSTEM N-BASE Z-R410A HEAT PUMP 13 SEER Model/Rev Description ANZ130[18-60]1AA Initial release of Amana® Brand Split System Base Heat Pump, 13 Seer R-410A units.
PRODUCT IDENTIFICATION Split System Heat Pumps DSZ16 DELUXE SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description DSZ160**1AA Initial release of Deluxe Goodman 2-stage 16 SEER heat pumps with R-410A. DSZ160241AC DSZ16036, 48, 60]1AB Sanhua (RANCO) reversing valves. DSZ18 DELUXE SPLIT Z-R410A HEAT PUMP 18 SEER Model/Rev Description DSZ180**1AA Initial release of Deluxe Goodman 2-stage 18 SEER heat pumps with R-410A. DSZ180[36, 48, 60]1AB Sanhua (RANCO) reversing valves.
PRODUCT IDENTIFICATION Split System Heat Pumps VSZ13 VALUE SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description VSZ13**1AA Initial release of Value Line 13 SEER heat pumps with R-410A. VSZ130[24 & 30]1AB Improved circuiting for effective defrost. VSZ130[24 & 36]1BA Initial release of models with 5mm Smart Coil™. VSZ130[18, 42, 48]1AB VSZ130241BB VSZ130301AC Models containing crankcase heater, CCH switch and upgraded defrost control.
PRODUCT IDENTIFICATION Split System Heat Pumps VSZ14 VALUE SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description VSZ14[018-060]1AA Introduction of ready 15, 14 SEER heat pumps to meet the 2015 efficiency requirement. VSZ140(18-30)1AB Energy guide update. PCBDM160 with new software. VSZ140421AB VSZ140491AB Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap. VSZ140[18,30]1AC VSZ140[36,48,60]1AB Refrigerant charge reduction.
PRODUCT IDENTIFICATION Split System Heat Pumps GSZ13 GOODMAN SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description GSZ13**1AA Initial release with Regal Beloit motor. GSZ13**1AB GSZ13**3AA GSZ13**4AA Initial release with Broad Ocean motor. GSZ130[24 & 30]1AC Release of minor revision with improved circuiting for effective defrost. GSZ130[24 & 36]1BA Initial release of models with 5mm Smart Coil™. GSZ130241CA Release of 2 Ton models with a compressor change from ZP21K5EPFV130 to ZP20K5EPFV130.
PRODUCT IDENTIFICATION Split System Heat Pumps GSZ13 GOODMAN SPLIT Z-R410A HEAT PUMP 13 SEER Model/Rev Description GSZ130[19,31]1AD GSZ130241BE GSZ130251AC Create new Motor & Replace 0131M00294 with 0131M00800 GSZ130601AE Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807 GSZ130181AH GSZ130301AJ Replaced motor 0131M000266 with 0131M00811 GSZ130361BF GSZ130371AD GSZ130421AJ GSZ130481AH Replaced motor 0131M00018P with 0131M00813 GSZ130421AK GSZ130421AL Change from copper wound compr
PRODUCT IDENTIFICATION Split System Heat Pumps GSZ16 GOODMAN SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description GSZ160[18-48]1BA Initial release of Goodman 16 SEER, 13 EER Heat Pumps with 9.0+ HSPF GSZ1160601BA Initial release of Goodman 5 Ton 16 SEER, 13 EER Heat Pumps GSZ160241BB GSZ160301BB Motor change on 3 & 3.5T 14 SEER & 2 & 2.5T 16 SEER. Increase blade gap. GSZ160181BB 16 SEER 1.
PRODUCT IDENTIFICATION Split System Heat Pumps SSZ14 SPECIAL HIGH FEATURE SPLIT Z-R410A HEAT PUMP 14 SEER Model/Rev Description SSZ140**1AA Initial release of Goodman 14 SEER Heat Pump R410A. SSZ140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. SSZ140**1AC Broad Ocean Motors. SSZ140181AC SSZ140241AF SSZ140301AD Discharge line mufflers added. SSZ140361AF SSZ140[42-60]1AD Added discharge line mufflers.
PRODUCT IDENTIFICATION Split System Heat Pumps SSZ16 SPECIAL HIGH FEATURE SPLIT Z-R410A HEAT PUMP 16 SEER Model/Rev Description SSZ160**1AA Initial release of Goodman 16 SEER Heat Pump R410A. SSZ160**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. SSZ160**1AC Broad Ocean Motor. Updated muffler and standardized TXV. Compensator using ASZ18 SEER weldment to the SSZ160601AC. SSZ16[024-48]1AC SSZ160601AD Discharge line mufflers added.
PRODUCT IDENTIFICATION Split System Condensers GSX13 GOODMAN BRAND SPLIT X-R410A CONDENSERS 13 SEER Model/Rev Description GSX130**1AA Initial release of Goodman 13 SEER R-410A Condensers with Regal Beloit motors GSX13061[1/3/4]AA Introduction of Goodman 13 SEER R-410A Condensers that supplement our current 5 ton models.
PRODUCT IDENTIFICATION Split System Condensers GSX13 GOODMAN BRAND SPLIT X-R410A CONDENSERS 13 SEER Mode l/ Re v De scripti on GSX130611AC Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807 GSX130241ED GSX130[30,60]1BG GSX130361EE GSX130[42,48]1BF Factory Refrigerant Charge Optimization GSX130181EH Changing Flat BOM structure to Indented BOM structure GSX130181EG Switching 3-legged and 4-legged compressors in 13SEER and 14SEER condensers to those with improved overload protection (O
PRODUCT IDENTIFICATION Split System Condensers GSX14 GOODMAN BRAND SPLIT X-R410A CONDENSERS 14 SEER Mode l/Re v De scription GSX14**1AA Int roduc tion of Goodman 14 SEE R R-410A models . GSX140[18-19]1KA GSX140[24-25]1KA GSX140[30-31]1KA GSX140[36-37]1KA GSX140[42, 48, 60]1KA Goodman Split X 14 Seer Condensing units. Introducing the Goodman 14 SEER standard condenser 5mm architecture with updated scroll compressors. GSX140241KB Replaced 1/12hp fan motor with 1/8hp fan motor.
PRODUCT IDENTIFICATION Split System Condensers GSX16 GOODMAN BRAND SPLIT X-R410A CONDENSERS 15 AND 16 SEER Model/Rev Description GSX160**1FA Initial release of the Goodman 16 SEER R410A Condensers. GSX160611FA New high capacity 5 ton model that will supplement the current GSX160601 models. GSX160[18-61]1FB Minor revision for GSX16s to include ball valves 0151R00045 and 0151R00046. GSX160601GA 7mm coils.
PRODUCT IDENTIFICATION Split System Condensers SSX14 SPECIAL HIGH FEATURE SPLIT X-R410A CONDENSERS 14 SEER Model/Rev SSX140**1AA Description SSX14018, 241AC Initial release of Goodman 14 SEER AC 410A. Revisions have screw locations moved in the top panel, base pans, louvers, and control box covers. Revised condenser coils by removing [1] haripin.
PRODUCT IDENTIFICATION Split System Condensers SSX16 SPECIAL HIGH FEATURE SPLIT X-R410A CONDENSER 16 SEER Model/Rev Description SSX160**1AA Introduces Goodman 16 SEER AC 410A SSX160**1AB New revisions have screw locations moved in the top panel, base pans, louvers, and control box covers. SSX160**1AB SSX160591AA New revisions have screw locations moved in the top panel, base pans, louvers, and control box covers. SSX160[24, 36, 48]1BA SSX160[30 & 42]1AA SmartCoil® coils.
PRODUCT IDENTIFICATION Split System Condensers VSX13 VALUE SPLIT X-R410A CONDENSER 13 SEER Model/Rev Description VSX130[18-48]1AA Introduces Value Line 13 SEER condensing units with R-410A. VSX130611AA Supplements the 5 ton model GSX130611 to enhance performance. VSX130301AB Replaced fan motor to -294 and fan blade to -18 on the VSX130301AA.
PRODUCT IDENTIFICATION Split System Condensers VSX13 VALUE SPLIT X-R410A CONDENSER 13 SEER Mode l /Re v De scription VSX130611AC Create new Motor 0131M00807 & Replace 0131M00061 with 0131M00807 VSX13[241,361]EE VSX130301AG VSX130[421,481]AF VSX130601BE Factory Refrigerant Charge Optimization VSX130181EH Changing Flat BOM structure to Indented BOM structure VSX130181EG Switching 3-legged and 4-legged compressors in 13SEER and 14SEER condensers to those with improved overload protection (OLP).
PRODUCT IDENTIFICATION Split System Condensers VSX14 VALUE SPLIT X-R410A CONDENSER 13 SEER Mode l /Re v De scription VSX140[18-19]1AA VSX140[24-25]1AA VSX140[30-31]1AA VSX140[36-37]1AA VSX140[42, 48, 60]1AA Introducing the 14 SEER standard condenser 5mm architecture with updated scroll compressors. VSX140241AB Replaced 1/12hp fan motor with 1/8hp fan motor.
PRODUCT IDENTIFICATION Split System Condensers ANX13 AMANA® BRAND SPLIT SYSTEM N-BASE X-R410A CONDENSERS 13 SEER Description Model/Rev ANX130[18-24]1AA Launch of the Tier 1.5T & 2.0T models. Launched with 26" chasis to accommodate horizontal style louvers. ANX130[30-61]1AA Initial release. ANX130241BA Convert ANX13/14 1.5 and 2 ton models to Rechi compressors.
PRODUCT IDENTIFICATION Split System Condensers ANX14 AMANA® BRAND SPLIT SYSTEM N-BASE X-R410A CONDENSERS 14 SEER Model/Rev Description ® ANX140[18-60]1AA Introducing the Amana Brand 14 SEER standard condenser 5mm architecture with updated scroll compressors. ANX140241AB Replaces 1/12hp fan motor with 1/8hp fan motor. ANX140431AA Introduction of ready 15, 12.2 EER air conditioning units.
PRODUCT IDENTIFICATION Split System Condensers ASX13 AMANA® BRAND SPLIT X-CONDENSERS 13 SEER Model/Rev Description ASX130**1AA Initial release new models of Amana® Brand Deluxe 13 SEER AC R410A conditioners. ASX130611AA Initial release of new models of Amana® Brand Deluxe 13 SEER AC R410A conditioners; replaced ASX130601* models. ASX130611AA Introduction of Amana® brand 13 SEER R-410A Condensers that supplement our current 5 ton models.
PRODUCT IDENTIFICATION Split System Condensers ASX14 AMANA® BRAND SPLIT X-CONDENSERS 14 SEER Model/Rev Description ASX140**1AA Initial release of models of Amana® Brand Deluxe 14 SEER AC R410A conditioners. ASX140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. ASX140**1AC Horizontal style louvers. ASX14018-361AD Revised condenser coils by removing (1) hairpin. R410A quantity reduced by 6 ounces.
PRODUCT IDENTIFICATION Split System Condensers ASX14 AMANA® BRAND SPLIT X-CONDENSERS 14 SEER Model/Rev Description ASX140191KB Remove HS Kit from Control Panels of condenser units with updated ZP14K6E scroll compressors. ASX140241LA Change compressor from K6 to K5 on ASX140241 and DX14SA0241 ASX 140[30,43]1KB Change from copper wound motor to aluminum wound motor.
PRODUCT IDENTIFICATION Split System Condensers ASX16 AMANA® BRAND SPLIT X-CONDENSERS 16 SEER Model/Rev Description ASX160**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers. ASX160**1AC Horizontal style louvers. ASX160**1FA Single speed outdoor fan. ASX160611FA High capacity 5 ton models that supplement the current ASX160601 models. ASX160611GA 7mm coils. ASX160[24-60]1BA Wiring diagram updated with notes.
PRODUCT IDENTIFICATION Air Handlers ACNF A-SINGLE PIECE AIR HANDLER CEILING MOUNT N-UNCASED FLOWATER Model/Rev Description ACNF****1AA Release of all models of 13 SEER Dayton uncased air handlers. ACNF****16AA Release of all models of 13 SEER Dayton uncased air handlers suitable for use with R-22 & R-410A. ACNF****1AB Drain pan material change.
PRODUCT IDENTIFICATION Air Handlers AEPF A-SINGLE PIECE E-MULTI-POSITION VARIABLE SPEED PAINTED FLOWATER Model/Rev Description AEPF****16AA Introducation of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A. AEPF****16BA Introduction of new models adding lower kW hit kits on the S&R plate. AEPF****16BB Replacement of the current spot welded blower housing with the same cinched or crimped design used on the 80% furnace line.
PRODUCT IDENTIFICATION Air Handlers ARUF A-SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR UNPAINTED FLOWRATOR Model/Rev ARUF172916AA A24-00-2RCA Description Introduction of new Air Handler Models with all aluminum evaporator coils. Conversion includes coils, manifold, hairpin, flowrators, 3/8" return bend to 5/16" aluminum return bends.
PRODUCT IDENTIFICATION Air Handlers ARPT - R410A ONLY A-SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR PAINTED FLOWRATER TXV Model/Rev Description ARPT***14AA Initial release of the new air handlers. ARPT***14AB Initial release of the air handlers manufactured at the Houston furnace facility. ARPT[18-36]B14AC ARPT[36-60]D14AC Serial plate changes.
PRODUCT IDENTIFICATION Air Handlers ASPT A-SINGLE PIECE AIR HANDLER S-MULTI-POSITION EEM MOTOR PAINTED TXV Model/Rev Description ASPT[24/36/48/60]*14 Introduction of new generation ASPT air handlers. ASPT36C 14AB ASPT[48/60]D14AB ASPT48D 14AC 9mm return bend coil changes to new generation of ASPT air handlers. ASPT24B 14AC ASPT30C 14AB ASPT36C 14AC Programmed Broad Ocean Motor. The supplier can program the motor instead of furnace plant, thus eliminating any programming installing issues.
PRODUCT IDENTIFICATION Air Handlers MBR MODULAR BLOWER AIR HANDLER R-MULTI-POSITION PSC MOTOR Model/Rev Description MBR****AA-1AA Initial release of a module blower with PSC blower motor. MBR****AA-1AB A quality improvement to use 0.75" Quiet Flex Insulation. MBR****AA-1AC Release of MBR/MBVC Models(Minor Revisions) for 11th St Plant.
PRODUCT IDENTIFICATION Air Handlers AWUF A SINGLE PIECE AIR HANDLER WALL MOUNT PSC MOTOR UNPAINTED FLOWRATOR Model/Rev Description AWUF****1AA Initial release of 13 SEER Dayton wall mount air handlers. AWUF****16AA Initial release 13 SEER Dayton wall mount air handlers suitable for use with R-22 and R410A refrigerant. AWUF3005-101AA Introduces 13 SEER Dayton wall mount air handlers using a Burr Oak Louvered Fin coil. AWUF****1BA Replaced wave fin design with new louvered fin design.
PRODUCT IDENTIFICATION Air Handlers AWUF A SINGLE PIECE AIR HANDLER WALL MOUNT PSC MOTOR UNPAINTED FLOWRATOR Model/Rev Description AWUF180[316,516,816]BC AWUF190[316,516,816]AB AWUF240[316,516,816]BC AWUF241016BC AWUF250[316,516,816]AB AWUF251016AB AWUF300[516,816]BD AWUF301016BD AWUF310[516,816]AC AWUF321016AC AWUF360[516,816]BD AWUF361016BD AWUF370[516,816]BC AWUF371016BC Release gasket and caps to seal leak. With this modification we will be able to meet 2% at 1 inch static leak and 1.
PRODUCT IDENTIFICATION Coils CAPF C-INDOOR COIL A-UPFLOW/DOWNFLOW PAINTED FLOWRATOR Model/Rev Description CAPF*****6AA Initial release of CAPF Dayton Upflow/Downflow coils. CAPF*****6BA Burr Oak Louvered Fin released in place of the Wavy Fin. CAPF36***CA Redesigned for performance improvement from 2 row to 3 row. CAPF*****6DA Replaced existing copper coils and other associated parts with aluminum components. CAPF*****6DB Drain pan material changed.
PRODUCT IDENTIFICATION Coils CAPF C-INDOOR COIL A-UPFLOW/DOWNFLOW PAINTED FLOWRATOR Model/Rev Description CAPFA1714A6AA CAPFA1714B6AA CAPFA1818C6BA Initial release of 7mm AL CAPFA Upflow/Downflow Coils. CAPFA2318A6AA CAPFA2318B6AA CAPFA2318C6AA CAPFA2422A6AA CAPFA3022A6AA Initial release of 7mm AL CAPFA Upflow/Downflow Coils. CAPFA2922A6AA CAPFA2922B6AA CAPFA2922C6AA Initial release of 7mm AL CAPFA Upflow/Downflow Coils.
PRODUCT IDENTIFICATION Coils CAPT C-INDOOR COIL A-UPFLOW/DOWNFLOW PAINTED CASED FLOWRATOR W/TXV Model/Rev Description CAPT3131B4BA CAPT3131C4BA Initial release of coils with factory-installed, non-adjustable TXV. Single stage AHRI ratings for CAPT3131 NTC combinations. CAPT3743C4AA CAPT3743D4AA Initial release of single stage AHRI ratings for CAPT3743 NTC combinations. CAPT4961C4AA CAPT4961D4AA Initial release of single stage AHRI ratings for CAPT4961C4 NTC combinations.
PRODUCT IDENTIFICATION Coils CAPF C-INDOOR COIL A-UPFLOW/DOWNFLOW UNCASED FLOWRATOR Model/Rev Description CAUF*****6AA Initial release of CAUF Dayton Upflow/Downflow coils. CAUF*****6BA Burr Oak Louvered Fin released in place of the Wavy Fin. CAUF****6*DA Replaced existing copper coils and other associated parts with aluminum components. CAUF*****6DB Drain pan material changed.
PRODUCT IDENTIFICATION Coils CSCF C-INDOOR COIL S-HORIZONTAL SLAB COIL UNPAINTED FLOWRATOR Model/Rev Description CSCF*****6AA Release 13 SEER CSCF slab horizontal coil. CSCF*****6BA Burr Oak Louvered Fin released in place of the Wavy Fin. The rows change by one, (i.e. 4 row to 3 row; 3 row to 2 row) where applicable. CSCF1824N6BB CSCF3036N6BB CSCF3642N6CB CSCF4860N6CB Drain pan material change. CSCF3642N6CA CSCF4860N6CA Release 13 SEER CSCF slab horizontal coil. Louvered fin project.
ACCESSORIES - LIGHT COMMERCIAL ACCESSORIES LIGHT COMMERCIAL GSX11 Model Description GSX110903 GSX110904 GSX111203 GSX111204 FSK01A* Freeze Protection Kit x x x x ASC01 Anti Short Cycle Kit x x x x LAKT-01 Low Ambient Kit x x x x LSK03* Liquid Line Solenoid Kit x x x x GSZ110903 GSZ110904 GSZ111203 GSZ111204 GSZ11 Model Description FSK01A* Freeze Protection Kit x x x x ASC01 Anti Short Cycle Kit x x x x --- --- --- --- x x x x x x x x OT-EHR18-6
ACCESSORIES MODELS TO KITS MATCHUP ASX13 Model 1 Description ASX13 018* ASX13 024* ASX13 030* ASX13 036* ASX13 042* ASX13 048* ASX13 060*/061* Anchor Bracket Kit X X X X X X X ASC01 Anti-Short Cycle Kit X X X X X X X CSR-U-1 Hard-start Kit X X X X CSR-U-2 Hard-start Kit CSR-U-3 Hard-start Kit X X ABK-20 2 X X FSK01A Freeze Protection Kit X X X X X X X LSK02* Liquid Line Solenoid Kit X X X X X X X TX2N4A³ TXV Kit X X X X X X X TX3N4 3 TXV
ACCESSORIES ASX14 Model Description ABK-201 ASC01 CSR-U-1 CSR-U-2 CSR-U-3 FSK01A² LSK02* TX2N4A³ TX3N4³ TX5N4³ Anchor Bracket Kit Anti-Short Cycle Kit Hard-start Kit Hard-start Kit Hard-Start Kit Freeze Protection Kit Liquid Line Solenoid Kit TXV Kit TXV Kit TXV Kit GSX14 Model Description ABK-201 Anchor Bracket Kit ABK-21⁴ Anchor Bracket Kit CSR-U-1 Hard-start Kit CSR-U-2 Hard-start Kit CSR-U-3 Hard-Start Kit FSK01A² Freeze Protection Kit LSK02* Liquid Line Solenoid Kit TX2N4A³ TXV Kit TX3N4³ TXV Kit
ACCESSORIES SSX16 SSX16 024* SSX16 030* SSX16 036* SSX16 042* SSX16 048* SSX16 060* Anchor Bracket Kit X X X X X X ASC01 Anti-Short Cycle Kit X X X X X X CSR-U-1 Hard-start Kit X X X CSR-U-2 Hard-start Kit CSR-U-3 Hard-start Kit X X Model ABK-20 1 2 Description X X FSK01A Freeze Protection Kit X X X X X X LSK02* Liquid Line Solenoid Kit X X X X X X TXV Kit X X X X X X 3 TX2N4A TX3N4 3 TXV Kit TX5N4 3 TXV Kit ASX16/DSX16 Model 1 Description
ACCESSORIES GSX16S/GSX16A Model 1 ABK-20 ASC01 CSR-U-1 CSR-U-2 CSR-U-3 2 FSK01A LSK02* TXV-303 TXV-423 TXV-483 TXV-603 GSX16 GSX16 GSX16 GSX16 GSX16 GSX16 GSX16 S/A181A* S/A241A* S/A301A* S/A361A* S/A421A* S/A481A* A601A* Description Anchor Bracket Kit Anti-Short Cycle Kit Hard-start Kit Hard-start Kit Hard-start Kit Freeze Protection Kit Liquid Line Solenoid Kit Fixed TXV Kit Fixed TXV Kit Fixed TXV Kit X X X X X X X X X X X X X X X X X X X X X X X X GSX16 A611A* X X X X X X X X X X X X
ACCESSORIES ASZ13 Model Description ASZ13 018 ASZ13 024 ASZ13 030 ASZ13 036 ASZ13 042 ASZ13 048 ASZ13 060 AFE18-60A All-Fuel Kit X X X X X X X ASC01 X X X X X Anti-Short Cycle Kit X X X X CSR-U-1 4 Hard-start Kit X X X X CSR-U-2 4 Hard-start Kit CSR-U-3 4 Hard-start Kit 2 X X FSK01A Freeze Protection Kit X X X X X X X LSK02* Liquid Line Solenoid Kit X X X X X X X X X X X X X X Outdoor Thermostat w/Lockout Stat X X X X X X X TXV K
ACCESSORIES GSZ13 Model Description G/VSZ13 G/VSZ13 G/VSZ13 G/VSZ13 G/VSZ13 G/VSZ13 G/VSZ13 024 030 036 042 048 060 018 AFE18-60A All-Fuel Kit X X X X X X X ASC01 Anti-Short Cycle Kit X X X X X X X CSB-15 Sound Blanket X X X CSB-16 Sound Blanket X X X X X X X X X X CSR-U-1 4 Hard-start Kit CSR-U-2 4 Hard-start Kit CSR-U-3 4 Hard-start Kit 2 X X FSK01A Freeze Protection Kit X X X X X X X LSK02* Liquid Line Solenoid Kit X X X X X X X X X X
ACCESSORIES SSZ14 Model Description AFE18-60A All-Fuel Kit CSR-U-1 Hard-start Kit CSR-U-2 Hard-start Kit CSR-U-3 Hard-start Kit 1 SSZ14 SSZ14 SSZ14 SSZ14 SSZ14 SSZ14 SSZ14 018* 024* 030* 036* 042* 048* 060* X X X X X X X X X X X X X X X Freeze Protection Kit X X X X X X X Liquid Line Solenoid Kit X X X X X X X Outdoor Thermostat X X X X X X X OT/EHR18-60 Emergency Heat Relat Kit X X X X X X X TX2N4A³ TXV Kit X X TX3N4³ TXV Kit X
ACCESSORIES ASZ16/DSZ16 Model AFE18-60A CSR-U-1 CSR-U-2 CSR-U-3 1 FSK01A LSK02* OT/EHR18-60 OT18-60A² TX2N4A TX3N4 TX5N4 1 2 Description All-Fuel Kit Hard-start Kit Hard-start Kit Hard-start Kit Freeze Protection Kit Liquid Line Solenoid Kit Emergency Heat Relay Kit Outdoor Thermostat w/ Lockout Stat TXV Kit TXV Kit TXV Kit A/DSZ16 024* A/DSZ16 030* A/DSZ16 036* A/DSZ16 042* A/DSZ16 048* A/DSZ16 060* X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
ACCESSORIES ASZ/DSZ18 Model AFE18-60A CSR-U-1 CSR-U-2 CSR-U-3 1 FSK01A LSK02* OT/EHR18-60 OT18-60A² TX2N4A³ TX3N4³ TX5N4³ 1 Installed 2 Description All-Fuel Kit Hard-start Kit Hard-start Kit Hard-start Kit Freeze Protection Kit Liquid Line Solenoid Kit Emergency Heat Relay Kit Outdoor Thermostat w/ Lockout Stat TXV Kit TXV Kit TXV Kit A/DSZ18 036* X X X X X X X A/DSZ18 048* X A/DSZ18 060* X X X X X X X X X X X X X X on indoor coil Require for heat pump applications where ambient temperatures fa
ACCESSORIES ASSOCIATED KITS EXPANSION VALVE KITS For Applications requiring a field installed access fitting 1/4 FLARE CONNECTION BULB TO BE LOCATED AT 10 OR 2 O'CLOCK BULB SUCTION LINE EVAPORATOR COIL PISTON SEAL SUPPLIED W/ KIT SEAL SUPPLIED W/ KIT EXPANSION VALVE DISTRIBUTOR BODY TAILPIECE SEAL 3/8"SWEAT REMOVE BEFORE INSTALLING EXPANSION VALVE 7/8" NUT For Applications not requiring a field installed access fitting 1/4' FLARE CONNECTION BULB TO BE LOCATED AT 10 OR 2 O'CLOCK BULB SUCTIO
ACCESSORIES FSK01A Freeze Thermostat Kit Wire Nut Y Bl ac k Y k ac l B Wire Nut Install Line Thermostat Here Install Line Thermostat Here Wire Nut Bla ck Bla c Y Wire Nut 66 k Y
ACCESSORIES COIL ACCESSORIES COIL MODEL TX2N4A TXV KIT CA*F18246* X TX3N4 TXV KIT TX5N4 TXV KIT FSK01A FREEZE PROTECTION KIT X CA*F30306* X X CA*F31316* CA*F36366* CA*F36426* X X X CA*F37436* CA*F48606* CA*F49616* CHPF18246* X X CHPF24306* X CHPF36366* X CHPF36426* X X CHPF37436* CHPF48606* CSCF1824N6* X X CSCF3036N6* X CSCF3642N6* X X X X CSCF4860N6* HK* SERIES ELECTRIC HEAT KITS ELECTRIC HEAT KIT APPLICATIONS - MBR, MBE BLOWER NO HEAT HKR-03* HKR05-(C)' HKR-06* HKR-
ACCESSORIES ELECTRIC HEAT KIT APPLICATIONS - ARPF ARPF1824 1/16 ARPF1931 1/16 ARPF3030 1/16 ARPF3642 1/16 ARPF3743 1/16 ARPF4860 1/16 HKR-03* X X X X X X HKR-05*, HKR-05C* X X X X X X HKR-06* X X X X X X 1 1 X X X X 1 1 X X X 2 3 3 X 3 X 3 X 3 X HKR-08*, HKR-08C* X X 1 HKR-10*, HKR-10C* X X 2 HKA-15C* X 2 X X X X 2 HKA-20C* X X 2 ^ HKR3-15* X 3 X X 2 ^ HKR3-20* X 3 X 3 X X X * Revision level that may or may not be designated C
ACCESSORIES ELECTRIC HEAT KIT APPLICATIONS - ADPF ADPF182416 ADPF304216 ADPF486016 ADPF4486016 HKR-03* X X X X HKR-05*, HKR-05C* X X X X HKR-06* X X X X HRK-08*, HKR-08C* X 1 X 1 X 1 X HKR-10*, HKR-10C* X 1 X 1 X 1 X HKA-15C* X X 2 X X HKA-20C* - X X 2 X ^HKR3-15* - X X X ^HKR3-20* - X X X * 1 Revision level that may or may not be designated 1 Air handler must be on speed tap 2, 3, 4 or 5 2 C Circuit Breaker option 3 ^ Heat kit requires 3-phase
ACCESSORIES ELECTRIC HEAT KIT APPLICATIONS - ASPF ASPF183016 ASPF303616 ASPF313716 ASPF426016 HKR-03* X X X X HKR-05*, HKR-05C* X X X X HKR-06* X X X X HRK-08*, HKR-08C* X1 X1 X1 X HKR-10*, HKR-10C* X1 X1 X 1 X +HKR3-15* X2 X2 X2 X1 X2 X2 X1 X2 X2 X1 X2 X2 X1 +HKR3-20* HKA-15C* X2 HKA-20C* Revision level that may or may not be designated C Circuit Breaker option + Heat kit requires 3-phase power supply 1 Air handler must be on speed tap 2, 3, 4 or 5 2 Air handl
ACCESSORIES ARPT**14** ARPT Heat Kit Applications Type / model 18B14-A* 24B14-A* 30B14-A* 36C14-A* 36D14-A* 42D14-A* 48D14-A* 60D14-A* HKSX03XC* X X X X X X X X HKSX05XC* X X X X X X X X HKSX06XC* X X X X X X X X HKSX08XC* X X X X X X X X HKSX10XC* X X X X X X X X HKSX15XF* X X X X X HKSX20XF* X X X X X HKSC05XC* X X X X X X X X HKSC08XC* X X X X X X X X HKSC10XC* X X X X X X X X HKSC15XA* X X X X X X HKSC15
ACCESSORIES ARUF**14** ARUF Heat Kit Applications TYPE/MODEL 18B14-A* 24B14-B* 24B14-C* 30B14-A* 30C14-B* 36C14-B* 42C14-A* 48D14-A* 60D14-A* HKSX03XC* X X X X X X X X X HKSX05XC* X X X X X X X X X HKSX06XC* X X X X X X X X X HKSX08XC* X X X X X X X X X HKSX10XC* X X X X X X X X X HKSX15XF* X X X X X HKSX20XF* X X X X X HKSC05XC* X X X X X X X X X HKSC08XC* X X X X X X X X X HKSC10XC* X X X X X X X X X HKS
ACCESSORIES ASUF**14** Heat Kit Applications TYPE/MODEL ASUF 29B14-A* 39C14-A* 49C14-A* 59D14-A* HKSX03XC* X X X X HKSX05XC* X X X X HKSX06XC* X X X X HKSX08XC* X X X X HKSX10XC* X X X X HKSX15XF* X X X HKSX20XF* X X X HKSC05XC* X X X X HKSC08XC* X X X X HKSC10XC* X X X X HKSC15XA* X X X HKSC15XB* X X X HKSC15XF* X X X HKSC19CA* X X HKSC19CB* X X HKSC20DA* X HKSC20DB* X HKSC20XF* X X HKSC25DC* X X * Revision level that may or ma
ACCESSORIES ASPT**14** Heat Kit Applications ASPT TYPE/MODEL 24B14-A* 30C14-A* 36C14-A* 42C14-A* 48C14-A* 42D14-A* 48D14-A* 60D14-A* HKSX03XC* X X X X X X X X HKSX05XC* X X X X X X X X HKSX06XC* X X X X X X X X HKSX08XC* X X X X X X X X HKSX10XC* X X X X X X X X HKSX15XF* X X X X X X HKSX20XF* X X X X X X HKSC05XC* X X X X X X X X HKSC08XC* X X X X X X X X HKSC10XC* X X X X X X X X HKSC15XA* X X X X X X H
ACCESSORIES ASPT**14** ASPT ASPT24B14* ASPT30C14* ASPT36C14* ASPT42C14* ASPT48C14* ASPT42D14* ASPT48D14* ASPT60D14* 3 715 730 NR NR NR NR NR NR 5 715 715 1170 1170 1170 1590 1590 1590 6 715 715 1170 1170 1170 1590 1590 1590 8 715 715 1170 1170 1170 1590 1590 1590 HEATER (kW) Minimum CFM required for Heater Kits 75 10 875 950 1170 1170 1170 1590 1590 1590 15 NR NR 1345 1345 1345 1715 1715 1715 19 NR NR 1345 1345 1345 NR NR NR 20 NR NR 1345 1345 1345 1715 1715 1715 25 NR NR NR NR NR NR 1715 1715
ACCESSORIES ARUF & ASPT MODEL LIST FOR DOWNFLOW KIT DFK-B DFK-C DFK-D DOWNFLOW KIT DOWNFLOW KIT DOWNFLOW KIT ARUF25B14** ARUF37C14** ARUF37D14** ARUF29B14** ARUF43C14** ARUF43D14** ARUF31B14** ARUF49C14** ARUF47D14** ASPT24B14** ASPT33C14** ARUF49D14** ASPT29B14** ASPT37C14** ARUF61D14** ASPT35B14** ASPT39C14** ASPT61D14** ASPT37B14** ASPT47C14** ASPT47D14** ASPT49C14** ASPT49D14** ASPT59C14** MODEL HEATER KIT (kW) 3 5 6 8 10 ARUF25B14 715 715 715 715 950 ARUF29B14 715 715 715 715 950 ARU
Product Design Product Design This section gives a basic description of cooling unit operation, its various components and their basic operation. Ensure your system is properly sized for heat gain and loss according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent. MBE blower cabinests are approved for applications with cooling coils of up to 0.8 inches W.C. external static pressure. The MBE models includes a feature that allows airflow to be changed by +10% or -15%.
Product Design The ASX [16 & 18], ASZ [16 & 18], DSX[16 & 18] and DSZ [16 & 18] series split system units use a two-stage scroll compressor. The two-step modulator has an internal unloading mechanism that opens a bypass port in the first compression pocket, effectively reducing the displacement of the scroll. The opening and closing of the bypass port is controlled by an internal electrically operated solenoid.
Product Design The refrigerant used in the system is R-410A. It is a clear, colorless, non-toxic and non-irritating liquid. R-410A is a 50:50 blend of R-32 and R-125. The boiling point at atmospheric pressure is -62.9°F. During the compression process, there are several pockets within the scroll that are compressing gas. Modulation is achieved by venting a portion of the gas in the first suction pocket back to the low side of the compressor thereby reducing the effective displacement of the compressor.
SYSTEM OPERATION cooling cycle. By energizing the reversing valve solenoid coil, the flow of the refrigerant is reversed. The indoor coil now becomes the condenser coil, and the outdoor coil becomes the evaporator coil. by a temperature sensor, which is clamped to a return bend (3/8” coils) or a feeder tube (5 mm coils) entering the outdoor coil. Defrost timing periods of 30, 60, or 90 minutes may be selected by connecting the circuit board jumper to 30, 60, or 90 respectively.
SYSTEM OPERATION COOLING CYCLE Reversing Valve (Energized) Outdoor Coil Indoor Coil Accumulator Thermostatic Expansion Valve Bi-Flow Filter Dryer Check Valve HEATING CYCLE Reversing Valve (De-Energized) Indoor Coil Outdoor Coil Accumulator Thermostatic Expansion Valve Bi-Flow Filter Dryer 81 Check Valve
SYSTEM OPERATION EXPANSION VALVE/CHECK VALVE ASSEMBLY IN COOLING OPERATION EXPANSION VALVE/CHECK VALVE ASSEMBLY IN HEATING OPERATION Most expansion valves used in current Amana Heat Pump products use an internally checked expansion valve. This type of expansion valve does not require an external check valve as shown above.
SYSTEM OPERATION AFE18-60A Control Board Description On some controls, if the outdoor thermostat fails closed in this position during the heating season, it will turn on the furnace during the cooling season on a “Y” cooling demand. In this situation, the furnace produces heat and increases the indoor temperature thereby never satisfying the cooling demand.
TROUBLESHOOTING CHART TROUBLESHOOTING CHART COOLING/HP ANALYSIS CHART Pow er Failure Blow n Fuse Unbalanced Pow er, 3PH Loose Connection Shorted or Broken Wires Open Fan Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Internal Compressor Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor Faulty Fan Relay Open Control Circuit Low Voltage Faulty Evap.
SERVICING SERVICING TABLE OF CONTENTS S-1 S-2 S-3 S-3A S-4 S-7 S-8 S-9 S-10 S-11 S-12 S-13 S-10 S-10B S-15 S-15A S-15B S-16A S-16B S-16C S-16D S-16E S-16F S-16G S-17 S-17A S-17B S-17C S-17D S-17E CHECKING VOLTAGE......................................................84 CHECKING WIRING........................................................84 CHECKING THERMOSTAT and WIRING .........................84 Thermostat Wiring........................................................
SERVICING S-1 S-2 CHECKING VOLTAGE CHECKING WIRING 1. Remove outer case, control panel cover, etc., from unit being tested. WARNING With power ON: HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. WARNING Line Voltage now present. 2.
SERVICING 3. No voltage indicates the trouble is in the thermostat or wiring. WARNING 4. Check the continuity of the thermostat and wiring. Repair or replace as necessary. HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. NOTE: Consideration must be given to how the heaters are wired (O.D.T. and etc.). Also safety devices must be checked for continuity.
SERVICING T2 WARNING Line Voltage now present. T1 CC VOLT/OHM METER L2 4 L1 OHMMETER 2 Ohmmeter for testing holding coil Voltmeter for testing contacts TESTING COMPRESSOR CONTACTOR (Single Phase) 1 4. Using an ohmmeter, test between 2 and 4 - should read continuous . Test between 5 and 6 - should read open. Using a voltmeter, test across terminals: 5. If not as above, replace the relay. Checking Relay Contacts - PSC Fan Motor A. L1-L2, L1-L3, and L2-L3 - If voltage is present, proceed to B.
SERVICING S-10 MBR/AR*F ELECTRONIC BLOWER TIME DELAY RELAY WARNING The MBR/AR*F contains an Electronic Blower Time Delay Relay board, B1370735. This board provides on/off time delays for the blower motor in cooling and heat pump heating demands when “G” is energized. HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
SERVICING It will automatically cut-in (close) at approximately 50 PSIG for heat pumps and 95 PSIG for air conditioners. Test for continuity using a VOM and if not as above, replace the control. S-10 Copeland Comfort Alert™ Diagnostics - 3-Wire module Applies to ASX /ASZ and DSX/DSZ units WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
SERVICING Status LED Green “POWER” Red “TRIP” DIAGNOSTICS TABLE: 2-WIRE COMFORT ALERT™ MODULE Status LED Description Module has power Status LED Troubleshooting Information Supply voltage is present at module terminals Thermostat demand signal 1. Compressor protector is open Y1 is present, but the 2. Outdoor unit power disconnect is open compressor is not 3. Compressor circuit breaker or fuse(s) is open running 4. Broken wire or connector is not making contact 5.
SERVICING Once attached, CoreSense™ provides around-the-clock monitoring for common electrical problems, compressor defects and broad system faults. If a glitch is detected, an LED indicator flashes the proper alert codes to help you quickly pinpoint the problem. See Diagnostic Table: 2-Wire Comfort Alert™ Module on following pages.
SERVICING DIAGNOSTICS TABLE: CORESENSE™ MODULE Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation.
SERVICING DIAGNOSTICS TABLE: CORESENSE™ MODULE (cont.) Flash code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at the same time mean control circuit voltage is too low for operation.
SERVICING Table 1 - Quick Reference Table 95
SERVICING S-15 CHECKING CAPACITOR CAPACITOR, RUN 2. Connect the Meter leads to the Capacitor terminals. 3. Digital meter will show a reading momentarily (Figure 1). Note the reading. A run capacitor is wired across the auxiliary and main windings of a single phase permanent split capacitor motor. The capacitors primary function is to reduce the line current while greatly improving the torque characteristics of a motor.
SERVICING value of the capacitor). 5. If line voltage is present, reinsert the 5-pin connector and remove the 16-pin connector. 5. If you read a significantly lower capacitance or none at all, then capacitor is dead and must be replaced. S-16A 6. Check for signal (24 volts) at the transformer. CHECKING FAN AND BLOWER MOTOR WINDINGS (PSC MOTORS) 7. Check for signal (24 volts) from the thermostat to the “G” terminal at the 16-pin connector. 8.
SERVICING S-16C CHECKING ECM MOTOR WINDINGS • Improved Humidity Control MOTOR SPEED ADJUSTMENT Each ECM™ blower motor has been preprogrammed for operation at 4 distinct airflow levels when operating in Cooling/ Heat Pump mode or Electric Heat mode. These 4 distinct levels may also be adjusted slightly lower or higher if desired. The adjustment between levels and the trim adjustments are made by changing the dipswitch(s) either to an “OFF” or “ON” position.
SERVICING Cooling/Heat Pump Operation Model MBE1200 MBE1600 MBE2000 Switch 5 OFF Switch 6 CFM OFF ON OFF OFF ON ON ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF OFF ON ON 1,200 1,000 800 600 1,600 1,400 1,200 1,000 2,000 1,800 1,600 1,200 Model Emergecny Heat Pump (Electric) w/Backup Heat Heat 2 7 8 OFF OFF OFF OFF 1100 1210 ON OFF OFF OFF 890 935 OFF ON OFF OFF 700 770 OFF OFF OFF OFF 2050 2150 AEPF3036 ON OFF OFF OFF 1750 1835 AEPF3137 OFF ON OFF
- Check line voltage for variation or "sag". - Check low voltage connections (G, Y, W, R, C) at motor, unseated pins in motor harness connectors. - Check-out system controls - Thermostat. - Perform Moisture Check.* - Does removing panel or filter reduce "puffing"? - Check/replace filter. - Check/correct duct restrictions. - Adjust to correct blow er speed setting. - Incorrect or dirty filter(s). - Incorrect supply or return ductw ork. - Incorrect blow er speed setting.
- Check/replace filter. - Check/correct duct restrictions. - Adjust to correct blow er speed setting. - Current leakage from controls into G, Y, or W. - - Blow er w on't shut off. - Air noise. - Motor failure or malfunction has occurred and moisture is present. - Replace motor and perform Moisture Check.* - Moisture in motor/control module. - "Hunts" or "puffs" at high CFM (speed). - Turn pow er OFF prior to repair. Wait 5 minutes after disconnecting pow er before opening motor.
SERVICING S-16E BLOWER PERFORMANCE DATA SPEED HIGH MEDIUM LOW STATIC MBR800**-* SCFM MBR1200**-* SCFM MBR1600**-* SCFM MBR2000**-* SCFM 0.1 1,240 1,500 1,800 2,160 0.2 1,170 1,460 1,740 2,080 0.3 1,120 1,360 1,680 1,990 0.4 1,060 1,280 1,610 1,890 0.5 980 1,200 1,520 1,790 0.6 900 1,110 1,430 1,690 0.1 900 1,380 1,540 1,730 0.2 850 1,320 1,490 1,670 0.3 790 1,270 1,450 1,590 1,520 0.4 740 1,200 1,400 0.5 680 1,140 13,560 1,420 0.
SERVICING S-16G EEM BLOWER REPLACEMENT For AWUF19-25, AWUF31-32, and AWUF37 Air Handlers. 1. Disconnect power at main electrical panel. 2. Remove front access panel. 3. Remove the two screws on each side holding the lower control box and move out of the way to give access to the blower assembly 6. Install cardboard or rug over coil to protect fins from damage. 7. Remove the three 3/8” screws holding the blower in place. 5.
SERVICING WARNING Hermetic compressor electrical terminal venting can be dangerous. When insulating material which supports a hermetic compressor or electrical terminal suddenly disintegrates due to physical abuse or as a result of an electrical short between the terminal and the compressor housing, the terminal may be expelled, venting the vapor and liquid contents of the compressor housing and system. 10.Remove the bolts holding the motor bracket to the blower and slide out of blower shell.
SERVICING Each compressor is equipped with an internal overload. The line break internal overload senses both motor amperage and winding temperature. High motor temperature or amperage heats the disc causing it to open, breaking the common circuit within the compressor on single phase units. Heat generated within the compressor shell, usually due to recycling of the motor, high amperage or insufficient gas to cool the motor, is slow to dissipate.
SERVICING unloader coil. WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. 1. Remove unit wiring from disconnect switch and wire a test cord to the disconnect switch. NOTE: The wire size of the test cord must equal the line wire size and the fuse must be of the proper size and type. 2.
SERVICING 3. Reverse rotation will result in substantially reduced amp draw from tabulated values. follows: With power ON; unit not running. To correct improper rotation, switch any two power supply leads at the outdoor unit contactor. 1. Jumper defrost thermostat by placing a jumper wire across the terminals “DFT” and “R”/”R-DFT” at defrost control board. The 3-phase scroll compressors are direction of rotation sensitive. They will rotate in either direction depending on the phasing of the power.
SERVICING “G” and “Y” and 24Vac is supplied to “Y” at the condensing unit and the “G” terminal on the EBTDR board. motor is turned off. 1.2 The compressor and condenser fan are turned on and after a 7 second on delay, the relay on the EBTDR board is energized and the blower motor starts. 4.0 Heating Operation On heat pump units, when the room thermostat set to the heating mode, the reversing valve is not energized.
SERVICING heat pump is turned off and the blower motor turns off after a 65 second off delay. 5.0 Defrost Operation On heat pump units, when the room thermostat is set to the heating mode, the reversing valve is not energized. As long as the thermostat is set for heating, the reversing valve will be in the de-energized position for heating except during a defrost cycle. 5.1 The heat pump will be on and operating in the heating mode as described the Heating Operation in section 4. 5.
SERVICING mostat will remove the 24Vac from “E/W1” and the VSTB rebetween 30 to 70 seconds and turn off the heater element(s) and the blower motor ramps down to a complete stop. second stage heat and 24Vac will be supplied to “E/W1” of the MBE/ AEPF. The VSTB will supply 24Vac to heat sequencer, HR1, on the electric heater assembly. MBE/AEPF WITH SINGLE STAGE 4.3 HR1 contacts M1 and M2 will close within 10 to 20 seconds and turn on heater element #1.
SERVICING relay on the defrost board open and turns off the outdoor fan. The contacts of the LVDR relay on the defrost board closes and supplies 24Vac to “O” and “W2”. The reversing valve is energized and the contacts on HR1 close and turns on the electric heater(s). The unit will continue to run in this mode until the defrost cycle is completed. a. For models with defrost control PCBDM133 or PCBDM160, a 30 second compressor delay at defrost initiation/termination is optional.
SERVICING will open between 30 to 70 seconds and turn off the heater element(s) and the blower motor ramps down to a complete stop. MBE/AEPF WITH TWO STAGE ASZ & DSZ HEAT PUMP UNITS 3.0 Cooling Operation When used with the ASZ & DSZ two stage heat pumps, dip switch #4 must be set to the OFF position on the VSTB inside the MBE/AEPF.
SERVICING heater elements #3 and #4 will be turned off. On most digital/ electronic thermostats, “W3/W4” will remain energized until the first stage demand “Y1” is satisfied and then the “G”, “Y1”, “Y2” “W2/W3” and “W3/W4” demands will be removed. 4.5 As the temperature indoors increase, it will reach a point where the “W2/W3” demand is satisfied. When this happens, the room thermostat will remove the 24Vac from “E/ W1” of the MBE/AEPF.
SERVICING Other components such as a Heating/Cooling Thermostat and Outdoor Thermostats are available to complete the installation. CFM The system CFM can be determined by measuring the static pressure external to the unit. The installation manual supplied with the blower coil, or the blower performance table in the service manual, shows the CFM for the static measured.
SERVICING DANGER WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Always remove the refrigerant charge in a proper manner before applying heat to the system. When repairing the refrigeration system: WARNING 1. Remove the wiring from the control terminals. HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present.
SERVICING WARNING To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system. WARNING To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig. producing a vacuum equivalent to 250 microns or less and a vacuum gauge to give a true reading of the vacuum in the system.
SERVICING cause future problems. LOW SIDE GAUGE AND VALVE NOTE: R410A should be drawn out of the storage container or drum in liquid form due to its fractionation properties, but should be “Flashed” to its gas state before entering the system. There is commercially available restriction devices that fit into the system charging hose set to accomplish this. DO NOT charge liquid R410A into the compressor.
SERVICING necessary. 1. Attach gauges to the high and low side of the system. 2. Start the system and run a “Cooling Performance Test. 1. Purge gauge lines. Connect service gauge manifold to basevalve service ports. Run the system in low stage at least 10 minutes to allow pressure to stabilize. 2. Temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6” from the compressor on the suction line.
5. Compare the hi-pressure reading to the "Required Liquid Line Temperature" chart (page 108). Find the hi-pressure value on the left column. Follow that line right to the column under the design subcooling value. Where the two intersect is the required liquid line temperature. CAUTION To prevent personal injury, carefully connect and disconnect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
SERVICING Pressure vs. Temperature Chart R-410A PSIG 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 °F -37.7 -34.7 -32.0 -29.4 -36.9 -24.5 -22.2 -20.0 -17.9 -15.8 -13.8 -11.9 -10.1 -8.3 -6.5 -4.5 -3.2 -1.6 0.0 1.5 3.0 4.5 5.9 7.3 8.6 10.0 11.3 12.6 13.8 15.1 16.3 17.5 18.7 19.8 21.0 22.1 23.2 24.3 25.4 26.4 27.4 28.5 29.5 30.5 31.2 32.2 33.2 34.1 35.1 35.5 36.9 PSIG 114.0 116.0 118.0 120.
SERVICING REQUIRED LIQUID LINE TEMPERATURE LIQUID PRESSURE AT SERVICE VALVE (PSIG) 189 195 202 208 215 222 229 236 243 251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474 486 499 511 8 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 REQUIRED SUBCOOLING TEMPERATURE (°F) 10 12 14 16 56 54 52 50 52 54 56 58 60 58 56 54 62 60 58 56 64 62 60 58 66 64 62 60 68 66 64 62 70 68 66 64 72 70 68 66
SERVICING S-113 OVERCHARGE OF REFRIGERANT An overcharge of refrigerant is normally indicated by an excessively high head pressure. An evaporator coil, using an expansion valve metering device, will basically modulate and control a flooded evaporator and prevent liquid return to the compressor. An evaporator coil, using a capillary tube metering device, could allow refrigerant to return to the compressor under extreme overcharge conditions.
SERVICING S-202 DUCT STATIC PRESSURES AND/OR STATIC PRESSURE DROP ACROSS COILS This minimum and maximum allowable duct static pressure for the indoor sections are found in the specifications section. 1. Remove compressor discharge line strainer. 2. Remove the liquid line drier and expansion valve. 3 Purge all remaining components with dry nitrogen or carbon dioxide until clean. Tables are also provided for each coil, listing quantity of air (CFM) versus static pressure drop across the coil. 4.
SERVICING 4. Consult proper air handler airflow chart for quantity of air (CFM) at the measured external static pressure. Supply Static + .20” wc Return Static - .30” wc S-204 COIL STATIC PRESSURE DROP 1. Using a draft gauge (inclined manometer), connect the positive probe underneath the coil and the negative probe above the coil. 2. A direct reading can be taken of the static pressure drop across the coil. 3. Consult proper table for quantity of air.
ACCESSORIES WIRING DIAGRAMS ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. 3-Phase Heat Kit 25kW Heat Kit Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS S R LE D N HA R I A 129
WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF Effective 12/24/14 SEE N OTE S 2 & 6 BL RD GR L1 L2 BK RD PLM 1 2 3 4 5 6 7 8 9 PLF 1 2 3 4 5 6 7 8 9 TERMINA L BLOC K SHOW N FOR 50HZ MODELS ONLY WH BR HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS AEPF FL FL FL FL HTR2 TL FL HTR1 TL FL HTR1 TL BK BK 4 M1 W M2 BK 8 R PU R BL 4 BR 5 M2 R2 BK BK BL 3 M1 M4 BK 1 R BK R M1 Y R BL M3 M2 2 PU M4 M5 M7 M6 M8 R1 W 6 3 R R2 BK R BK 6 R BL 4 BR 5 W 6 7 7 BK R 7 Y 8 9 R 8 Y BK 9 R 9 L1 BL 2 R1 5 M4 M3 M2 Y HTR4 TL 1 Y BL M1 4 M3 W 7 R 3 BK BL M1 R 6 BK BL BK 8 9 L2 L1 ONE (1) ELEMENT ROWS L2 L1 TWO (2) ELEMENT ROWS L2 L1 L2 THREE (3) ELE
WIRING DIAGRAMS AEPF******CA FL FL HTR1 TL PL1 BK BK FL HTR2 TL BK RD 2 BK PU RD M1 R 3 HTR3 TL M2 BK RD BK 8 RD RD FL BK 6 1 PL1 BL BK 1 R2 BL 4 BR 5 BK RD M1 YL RD 2 PU BL RD 6 3 BL M3 M2 M4 M5 M7 M6 M8 R1 WH RD R2 BK BK BL 4 BR 5 WH RD 6 7 7 RD 9 7 YL 8 YL BK 8 RD 9 BL BK 8 RD 9 L1 YL HTR4 TL 3 BL M2 BK RD BK RD HTR3 TL FL PU M1 M4 BK HTR2 TL 2 R1 5 M4 FL YL M3 M2 HTR1 TL BK PL1 BK M1 4 M3 WH 7
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS AR[090-120]4 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON TERMINAL "2" FOR 208 VOLTS. 2) SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE WIRING CONNECTIONS. 3) CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAP NEEDS TO BE CHANGED, CONNECT APPROPRIATE MOTOR WIRE (RED FOR LOW, BLUE FOR MEDIUM, AND BLACK FOR HIGH SPEED) ON "COM" CONNECTION OF THE EBTDR. INACTIVE MOTOR WIRES MUST BE CONNECTED TO "M1 OR M2" ON EBTDR.
USE MIN. 75°C FIELD WIRE (SEE RATING PLATE) COPPER POWER SUPPLY L2 BK R BK M2 M1 BK PU WH BL ONE (1) ELEMENT ROWS RD TL RD BK PL L1 RD BK L2 FL BK R BK RD M2 M1 HTR1 HTR2 M4 M3 BL WH BK PU RD TWO (2) ELEMENT ROWS RD TL TL BL WH GR W1 W2 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 BK R RD TL PU WH BL BK RD BK ONE (1) ELEMENT ROWS BK M2 M1 HTR 1 9 8 7 6 5 4 3 2 1 RD L1 BK FL L2 FL M2 M1 RD M4 M3 TL TL BK WH PU BL RD RD BK TW O (2) ELEMENT ROW S BK RD BK R HTR2 HTR1 9 8 7 6 5 4 3 2 1 L1 L2 BK RD BK RD YL R1 M4 M3 BK M2 R2 BL TL YL M1 BK RD TL TL WH PU BR RD BL BK THREE (3) ELEMENT ROW S L2 RD M2 RD HTR3 HTR2 HTR1 M1 BK L1 YL FL FL FL 9 8 7 6 5 4 3 2 1 L1 BK RD L2 FL L1 YL
WH RD or BK B A BL 1 4 7 WH COPPER POWER SUPPLY (USE RATING PLATE) USE MIN. 75° C FIELD WIRE GR CR PU IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE WIRE THAT CONFORMS TO THE NATIONAL ELECTRIC CODE. RD WH BR PLM PLF 1. RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON TERMINAL "2" FOR 208 VOLTS. 2. SEE COMPLETE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE WIRING CONNECTIONS. 3.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS 3-PHASE HEAT KIT ASPT**14**/ASUF**14** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
6. COMPONENT CODE: C - CONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR F - FUSE HTR - HEATER ELEMENT R - RELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER 5. WIRING CODE: FACTORY WIRING: HIGH VOLTAGE LOW VOLTAGE FIELD WIRING: HIGH VOLTAGE 4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW 3.
GR BR WH DISC BL RD BK BK RD RD PU RD C BL BL RD L1 L2 BR BL WH BL K1 K1 M1 T1 T2 RD EBTDR SPEED UP G EBTDR R XFMR-R XFMR-C C GR RD EVAPORATOR MOTOR LEADS PU COMMON BK HIGH RD LOW BK DISC L1 BK BK RD RD BK NC M2 COM NO BK RD RD BR RD RD FC EM BR PU BK SEE NOTE 5 CONTROLS SHOWN WITH UTILITIES IN "ON" POSITION AND THERMOSTAT IN "OFF" POSITION. IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE 105˚C.
7. FOR UNITS USING 3KW AND 5KW HEATERS, WHITE WIRE WILL BE CONNECTED TO TERMINAL 4. 6. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER 5. WIRING CODE: FACTORY WIRING: HIGH VOLTAGE LOW VOLTAGE FIELD WIRING: HIGH VOLTAGE 4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW PK - PINK 3.
6. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER 5. WIRING CODE: FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE SEE NOTE 2 4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW 3.
6. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FFUSE HTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORMER 5. WIRING CODE: FACTORY WIRING: HIGH VOLTAGE LOW VOLTAGE FIELD WIRING: HIGH VOLTAGE 4. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW 3.
GR BR WH RD BL RD DISC RD BL GR L2 L1 EBTDR K1 K1 BR RD WH BL RD C T2 T1 SPEED M1 UP EBTDR R XFMR-R XFMR-C C G EVAPORATOR MOTOR LEADS PU COMMON BK HIGH RD LOW BK BK RD BL RD RD RD BK BK BK NC M2 COM NO RD RD BR FC EM BR RD PU BK RD SEE NOTE 5 CONTROLS SHOWN WITH UTILITIESIN "ON" POSITION AND THERMOSTAT IN "OFF" POSITIO N. IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE 105˚C.
7. COMPONENT CODE: CCONTACTOR DISC - DISCONNECT SWITCH EM - EVAPORATER MOTOR FUSE FHTR - HEATER ELEMENT RRELAY SEQ - SEQUENCER TL - THERMAL LIMIT TR - TRANSFORM ER 6. WIRING CODE: FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE SEE NOTE 3 5. COLOR CODES: BK - BLACK BL - BLUE BR - BROWN GR - GREEN PU - PURPLE RD - RED WH - WHITE YL - YELLOW 4.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
q l MBE l HKR Heat Kit q HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS l q lr oa l ` j l l Nq mQ g l Oq mO g mS g Blower Section Typical Wiring Schematic MBE Blower with Electric Heat. This wiring diagram is for reference only. Not all wiring is as shown above. Wiring is subject to change.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS - REMOTE SPLITS A/C WIRING DIAGRAMS S T I PL S E T O M E C / R A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 1 SR IO CM AUX M AIN ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL 2 5 BK BK BR PU BL RD CONTROL BOX YL BK IO BK C R YL AUX M AIN C OM P RD S BL Y L/PK BK PU C L2 T2 BK LPS YL L1 T1 BK RD YL H SA (IF USED) NOTE 2 RD RD RD C F RC CF BL YL/PK EQUIPMENT GROUND SEE NOTE 3 RD RD BR YL RD SC YL C LVJB LV JB SEE N OTE 1 L1 C T1 CO MPO NE NT CODE C --------------- CONTACTOR CSM -------- CORESENSE MODULE CM ------------ OUTDOOR FAN MOTOR COMP ---
YL T2 L2 T1 L1 1 SR BL IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR 2 5 BK BK BR PU RD CONTROL BOX YL BK C R AUX MAIN COMP YL BL S BK L1 T1 BK C L2 T2 BK RD RD YL RCCF SA (IF USED) NOTE 2 RD SC YL C BL RD BR F RD EQUIPMENT GROUND SEE NOTE 3 H PU RD RD C SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
BK L2 L1 ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 1 SR Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK L2 L1 1 SR IO CM AUX MA IN ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL 2 5 BK BR PU BL RD CONTROL BOX YL BK CSM C P PU Y IO BK C BK YL C R YL AUX M AIN C OM P RD S YL/PK PU L1 C L2 T2 BK LPS BK T1 BK BR C RD RC CF F HERM SA (IF USED) N OTE 2 RD RD RD YL YL YL BL YL/PK EQUIPMENT GROUND NOTE 3 RD PU RD RD SC YL C LVJB LVJB SEE NO TE 1 L1 C CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
L2 L1 1 SR IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL 2 5 BK Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 1 SR IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL 2 5 BK BK BR PU BL CONTROL BOX RD YL BK C BL Y YL CSM P PU YL BK C BK IO C R BL/PK YL RD BL/PK AUX MAIN S HPS YL/PK COMP BL/PK YL PU L1 YL/PK BL/PK YL/PK LPS C L2 T2 BK YL BK T1 BK BR C RD RD RCCF HERM F SA (IF USED) NOTE 2 RD RD YL/PK YL YL BL EQUIPMENT GROUND NOTE 3 RD PU RD RD SC YL C LVJB LVJB SEE NOTE 1 L1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITIO
YL T2 L2 T1 L1 1 SR BL IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR 2 5 BK BK BR PU RD CONTROL BOX YL BK C R AUX MAIN COMP YL BL S BK L1 T1 BK C L2 T2 BK RD YL RCCF SA (IF USED) NOTE 2 RD RD SC YL C BL RD BR F RD EQUIPMENT GROUND SEE NOTE 3 H PU RD RD C SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
T2 L2 T1 L1 PU YL BK RD DFT IO AUX MAIN BK PS2 CSM YL ALTERNATE DOUBLE POLE CONTACTOR YL BL YL Y 1 BK CM W 2 C-RV SR RD BR PU YL BK 0 BK RVC YL YL/PK OR YL/PK YL/PK BK BL/PK 0 5 BK Y YL 0-RV WH BK BK CNT PU RD HVDR PU LVDR YL/PK R-PS1 R-DFT DFT DF2 DF1 CCR CRP Y C RD BK RD BK DC CONTROL BOX LPS HPS PU C C C R R BL BK C RD CHS BK L2 T2 R AUX COMP MAIN BR PU YL C L1 T1 BK PU BK BK SEE NOTE 4 BL/PK BL RD S H C
YL 2 T2 L2 T1 L1 1 YL BK DFT IO AUX MAIN BK YL CM BK Y RD CSM YL PS2 CR P Y C PU BL W SR C-RV 5 BK Y YL RD BR PU YL BK 0 BK RVC YL PU YL/PK OR YL/PK YL/PK BK BL/PK 0 PU HVDR RD 0-RV WH BK BK LVDR YL/PK R-PS1 R-DFT DFT DF2 DF1 CNT ALTERNATE DOUBLE POLE CONTACTOR BK RD BK DC CONTROL BOX CCR RD RD LPS HPS PU C C C R R BL PU BL BK C RD CHS BK L2 T2 BK BK Wiring is subject to change.
YL 2 T2 L2 T1 L1 1 BK YL DFT IO AUX MAIN BK YL CM BK Y RD CSM C YL PS2 CR P Y PU BL W SR C-RV RD BR PU YL BK BK RVC YL PU YL/PK OR 0 5 BK Y YL 0-RV WH BK BK YL/PK YL/PK BK BL/PK 0 PU HVDR RD LVDR YL/PK R-PS1 R-DFT DFT DF2 DC CONTROL BOX CNT ALTERNATE DOUBLE POLE CONTACTOR BK RD BK DF1 CCR RD RD LPS HPS PU C C C R R PU BL BK C RD CHS BK L2 T2 BK BK R AUX COMP MAIN BR PU YL C L1 T1 PU BK SEE NOTE 4 BL/PK B
Y C SEE NOTE 7 CSM RVC DFT CM BK IO RD HPS BK PU RD (LOW) BK (HIGH) BR PU YL/PK BK BL/PK BL/PK OR C C C R R YL/PK BK BK BL/PK YL/PK 0 AUX MAIN BL/PK Y BK RD L2 L1 ALTERNATE DOUBLE POLE CONTACTOR T2 T1 BL PS2 1 Y 2 W R P PU SR C-RV YL WH BK 0 5 BK HVDR YL/PK 0-RV YL/PK RD LVDR RD BK R-PS1 R-DFT DFT DF2 DF1 CNT C BL RD RD RD BK DC CCR BL RD RD LPS DT BL BL RD YL RD BK BL BK BL BK BK CH C 2 MAIN R AUX YL S RD
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS *SX160[24-60]1** Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
1 SR T2 L2 T1 L1 BL PU Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
1 SR T2 L2 T1 L1 GR/YL BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
YL/PK BL/PK LPS HPS BL/PK 165 PU YL/PK CM BR BK YL SEE NOTE 3 BL YL L1 BK RD L2 COMP L3 T3 L2 L3 PU T2 YL L1 L2 L3 BK BK L1 T1 BK CONTROL BOX BK BK C BK PU CH PU BR SEE NOTE 3 BK SEE NOTE 2 EQUIPMENT GROUND FC RD C LVJB SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
IO CM AUX MAIN BK BR PU YL YL T1 BK BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 166 C T3 RD L3 T3 L2 YL T2 RD BK COMP T2 L1 T1 BK CONTROL BOX PU RD RD BR EQUIPMENT GROUND SEE NOTE 2 FC C SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
YL T2 L2 T1 L1 1 SR BL IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR 2 5 BK BK BR PU RD CONTROL BOX YL BK C R AUX MAIN COMP YL BL S BK L1 T1 BK C L2 T2 BK RD RD YL RCCF SA (IF USED) NOTE 2 RD SC YL C BL RD BR F RD EQUIPMENT GROUND SEE NOTE 3 H PU RD RD C SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
WH YL BL 2 5 1 SR T2 L2 T1 L1 BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. WIRING DIAGRAMS GSX160611F* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
RD LPS BL/PK Y HPS PS2 BL/PK Y YL/PK W BK PU CM BR BK BK OR 0 RD C-RV WH BK 0-RV BK DFT HVDR BL/PK LVDR YL/PK R-PS1 R-DFT DFT DF2 DF1 DC RD PU CNT RVC RD RD CCR YL/PK RD 0 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 T1 L1 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK BK 173 L2 L1 ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 RVC Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 T1 L1 1 SR BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 T1 L1 1 SR BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 T1 L1 1 SR BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK L2 L1 ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 T1 L1 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
L2 L1 BK RVC DFT CM BK RD BL IO HPS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
YL T2 L2 T1 L1 1 SR BL IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR 2 5 BK BK BR PU RD CONTROL BOX YL BK C R AUX MAIN COMP YL BL S BK L1 T1 BK C L2 T2 BK RD RD YL RCCF SA (IF USED) NOTE 2 RD SC YL C BL RD BR F RD EQUIPMENT GROUND SEE NOTE 3 H PU RD RD C BL SEE NOTE 1 CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
L2 L1 1 SR IO CM AUX MAIN ALTERNATE DOUBLE POLE CONTACTOR T2 T1 YL 2 5 BK BL BK BR PU RD YL BK C CONTROL BOX IO R AUX MAIN COMP S RD BK YL BL BK BK RD L1 T1 BK BR RD C RD RD RCCF HERM F RD CH NOTE 3 BK GR RD EQUIPMENT GROUND NOTE 4 RD PU C RD RD CHS L2 T2 BK SC YL YL SA (IF USED) NOTE 2 YL YL BL C NOTE 1 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
YL T2 L2 T1 L1 1 SR BL Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
T2 L2 L1 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.