TECHNICAL MANU AL MANUAL *PC 14 SEER R-410A Package Air Conditioners with R-410A • Refer to Service Manual RS6300014 (Horizontal) for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. This manual is to be used by qualified, professionally trained HVAC technicians only.
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
PRODUCT DESIGN *PC14 Package Cooling Units are designed for outdoor installations only in either residential or light commercial applications. The connecting ductwork (Supply and Return) can be connected for either horizontal or vertical airflow. In the vertical application a matching Roof Curb is recommended. A return air filter must be installed behind the return air grille(s) or provision must be made for a filter in an accessible location within the return air duct.
PRODUCT DESIGN In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top installations), the installer must provide service platform for service person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edition of the Uniform Mechanical Code Section 305. NOTE: Unit can also use roof curb.
PRODUCT DIMENSIONS *PC14[24-60]H41** A BACK VIEW (DUCT OPENINGS) B *PC14[24-60]H41A*/B*/C*/D* Chassis Small Medium Large Dimensions in inches 6 *PC14[24-60]H41E* Model A B *PC1424 22 30 *PC1430 22 30 *PC1436 24 35 *PC1442 24 35 *PC1448 24 38¾ *PC1460 24 38¾ Chassis Small Medium Model A B *PC1424 22 30 *PC1430 22 30 *PC1436 22 30 *PC1442 22 30 *PC1448 24 35 *PC1460 24 35 Dimensions in inches
PRODUCT DESIGN *PC14[24-60]H41** HKR ELECTRICAL DATA Circuit #1 Model and Heat Kit Usage *PC1424H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* *PC1430H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* HKR/P15*,C* *PC1436H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* HKR/P15*,C* *PC1442H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* HKR/P15*,C* HKR/P20*,C* *PC1448H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* HKR/P15*,C* HKR/P20*,C* *PC1460H41* HKR/P05*,C* HKR08*,C* HKR/P10*,C* HKR/P15*,C* HKR/P20*,C* Minimum Circuit Ampacity at 208 / 240V 24 / 27
*PC14[24-60]H41** ACCESSORIES ACCESSORIES - *PC/*PH****H UNITS Part Number 8 Description OT18-60A Outdoor Thermostat Kit w/Lockout Stat OT/EHR18-60 Emergency Heat Relay Kit HKR/P Electric Heat Kit PCCP101-103 Roof Curb PCP101-103 Downflow Plenum Kit PCP101-103R8 Downflow Plenum Kit w/ R-8 Insulation PCEC101-103 Downflow Economizer for GPC-(H) A/C - To Be Used With PCP101-103 PCEH101-103 Downflow Economizer for GPH-(H) Heat Pump - To Be Used With PCP101-103 PCMD101-103 Manual Damper - To
GPC14[24-60]H41A*/B* BLOWER PERFORMANCE DATA Dry Coil Data GPC1460H41A*/ B* GPC1448H41A*/B* GPC1442H41A*/ B* GPC1436H41A*/ B* GPC1430H41A*/B* GPC1424H41A*/B* M o d el Sp ee d V ol ts T1 23 0 T 2 ,T 3 23 0 T4 , T5 23 0 T1 23 0 T 2 ,T 3 23 0 T4 , T5 23 0 T1 23 0 T 2 ,T 3 23 0 T4 , T5 23 0 T1 23 0 T 2 ,T 3 23 0 T4 , T5 23 0 T1 23 0 T 2 ,T 3 23 0 T4 , T5 23 0 T 1 , T 2, T 3 T4 , T5 E. S.P (In . o f H 2 O) 0 .1 0. 2 0.3 0 .4 0 .5 0. 6 0.7 0 .
GPC14[24-60]H41CA BLOWER PERFORMANCE DATA Dry Coil Data GPC1424H41CA T1 230 T2,T3 230 T4, T5 230 T1 230 T2,T3 230 T4, T5 230 T1 230 T2,T3 230 T4, T5 230 T1 230 T2,T3 230 T4, T5 230 T1 230 T2,T3 230 T4, T5 230 T1 230 GPC1448H41CA GPC1442H41CA GPC1436H41CA GPC1430H41CA Speed GPC1460H41CA 10 E.S.P (In. of H2O) Volts Model T2,T3 230 T4,T5 230 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
*PC14[24-60]H41D*/E* BLOWER PERFORMANCE DATA *PC1448H41E* *PC1442H41E* *PC1460H41D*/E* *PC1448H41D* *PC1442H41D* *PC1436H41D* *PC1430HD*/E* *PC1424HD*/E* Model T1 230 T2 / T3 230 T4 / T5 230 T1 T2 / T3 230 230 T4 / T5 230 T1 230 T2 / T3 230 T4 / T5 230 T1 T2 / T3 230 230 T4 / T5 230 T1 230 T2 / T3 230 T4 / T5 230 T1 T2 / T3 230 230 T4 / T5 230 T1 230 T2 / T3 230 T4 / T5 T1 E.S.P. (In. of H2 O) Volts Speed 230 230 T2 / T3 230 T4 / T5 230 CFM 0.1 922 0.
10 20 30 40 50 60 70 30 80 90 100 40 50 60 700 600 CFM 90 100 2000 2200 2400 CFM 1800 1600 1400 OUTPUT BTU/HR x 1000 80 1200 1100 1000 900 70 800 FORMULAS 110 120 130 140 BTU OUTPUT = CFM x 1.08 x RISE BTU OUTPUT RISE = ÷ CFM 1.
PACKAGE COOLING SPECIFICATIONS GPC14[24-36]H41AB GPC1424H41AB GPC1430H41AB GPC1436H41AB COOLING COOLING CAPACITY, BTUH CAPACITY SEER / EER UNIT VOLTAGE (NAMEPLATE) ELECTRICAL AMPS (TOTAL) 24,600 28,400 35,600 14.5 / 12.1 14.0 / 12.1 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 16.1 15.76 20.06 19.5 19 24.2 30 30 40 SCROLL SCROLL SCROLL RATED LOAD AMPS 13.5 12.8 16.7 LOCKED ROTOR AMPS 58.
PACKAGE COOLING SPECIFICATIONS GPC14[42-48]H41AB GPC1442H41AB GPC1448H41AB COOLING CAPACITY, BTUH 40,000 46,500 14.2 / 12.0 14.5 / 12.0 208-230/1/60 208-230/1/60 AMPS (TOTAL) 22.2 24.2 MINIMUM CIRCUIT AMPACITY 26.6 29.1 40 45 SCROLL SCROLL RATED LOAD AMPS 17.9 19.9 LOCKED ROTOR AMPS 112 109 HORSEPOWER 1/4 1/4 1075 1075 FULL LOAD AMPS 1.4 1.4 LOCKED ROTOR AMPS 2.9 2.9 22 / 4 22 / 4 16.0 19.
PACKAGE COOLING SPECIFICATIONS GPC14[24-36]H41B*/C* GPC1424H41 B* GPC1424H41 C* GPC1430H41 B*/C* GPC1436H41 B*/C* 24,600 24,600 28,400 35,600 14.5 / 12.1 14.5 / 12.1 14.0 / 12.1 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 16.1 10.3 15.76 20.06 19.5 12.2 19 24.2 30 15 30 40 SCROLL ROTARY SCROLL SCROLL RATED LOAD AMPS 13.5 7.7 12.8 16.7 LOCKED ROTOR AMPS 58.
PACKAGE COOLING SPECIFICATIONS GPC14[42-60]H41B*/C* GPC1442H41 B*/C* 40,000 GPC1448H41 B*/C* 46,500 GPC1460H41 B*/C* 57,500 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 22.2 24.2 30.7 26.6 29.1 37.3 40 45 60 SCROLL SCROLL SCROLL RATED LOAD AMPS 17.9 19.9 26.4 LOCKED ROTOR AMPS 112 109 134 CONDENSER HORSEPOWER 1/4 1/4 1/4 FAN MOTOR RPM 1075 1075 1075 FULL LOAD AMPS 1.4 1.4 1.4 LOCKED ROTOR AMPS 2.9 2.9 2.
PACKAGE COOLING SPECIFICATIONS *PC14[24-36]H41D* GPC1424H41D* APC1424H41D* *PC1430H41D* *PC1436H41D* 24,600 24,600 28,400 35,600 14.5 / 12.1 14.5 / 12.1 14.0 / 12.1 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 12.6 18.4 17.7 22 15 22 21 26 20 35 30 40 ROTARY SCROLL SCROLL SCROLL RATED LOAD AMPS 7.7 13.5 12.8 16.7 LOCKED ROTOR AMPS 37 58.3 64 79 CONDENSER HORSEPOWER 1/6 1/6 1/6 1/4 FAN MOTOR RPM 815 815 815 830 FULL LOAD AMPS 1.1 1.
PACKAGE COOLING SPECIFICATIONS COOLING COOLING CAPACITY, BTUH CAPACITY SEER / EER UNIT VOLTAGE (NAMEPLATE) ELECTRICAL AMPS (TOTAL) SPECIFICATION MINIMUM CIRCUIT AMPACITY MAXIMUM OVERCURRENT PROTECTION COMPRESSOR (1) TYPE *PC14[42-60]H41D* *PC1442H41D* *PC1448H41D* *PC1460H41D* 40,000 46,500 57,500 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 23.1 26.7 33.2 28 32 40.0 45 50 60 SCROLL SCROLL SCROLL RATED LOAD AMPS 17.9 19.9 26.
PACKAGE COOLING SPECIFICATIONS *PC14[24-36]H41E* GPC1424H41E* APC1424H41E* *PC1430H41E* *PC1436H41E* COOLING COOLING CAPACITY, BTUH CAPACITY SEER / EER UNIT VOLTAGE (NAMEPLATE) ELECTRICAL AMPS (TOTAL) SPECIFICATION MINIMUM CIRCUIT AMPACITY MAXIMUM OVERCURRENT PROTECTION COMPRESSOR (1) 24,600 24,600 28,400 35,600 14.5 / 12.1 14.5 / 12.1 14.0 / 12.1 14.0 / 12.0 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 12.6 18.
PACKAGE COOLING SPECIFICATIONS *PC14[42-60]H41E* *PC1442H41E* *PC1448H41E* *PC1460H41E* COOLING COOLING CAPACITY, BTUH CAPACITY SEER / EER UNIT VOLTAGE (NAMEPLATE) ELECTRICAL AMPS (TOTAL) SPECIFICATION MINIMUM CIRCUIT AMPACITY (1) 46,500 57,500 14.0 / 12.0 14.0 / 12.0 14.0 / 11.5 208-230/1/60 208-230/1/60 208-230/1/60 23.1 26.7 33.2 28 32 40.0 45 50 60 SCROLL SCROLL SCROLL RATED LOAD AMPS 17.9 19.9 26.
23.4 0.71 18 1.56 6.6 231 110 21.6 0.68 18 1.52 6.4 224 107 24.5 0.84 20 1.58 6.7 236 112 23.8 0.81 21 1.57 6.6 233 111 22.0 0.78 21 1.53 6.5 226 108 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 850 745 955 850 745 955 24.1 0.74 17 1.57 6.6 233 111 MBh S/T Delta T KW A MPS HI PR LO PR 22.6 0.69 19 1.56 6.6 244 115 24.5 0.72 19 1.60 6.8 251 118 25.
85 80 IDB* EXPANDED PERFORMANCE DATA COOLING OPERATION 24.2 0.88 23 1.58 6.7 236 112 22.4 0.85 24 1.54 6.5 229 109 25.4 0.97 24 1.61 6.8 241 115 24.6 0.93 25 1.60 6.8 238 114 22.7 0.89 25 1.56 6.6 231 110 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 850 745 955 850 745 23.2 0.86 25 1.59 6.7 249 117 25.1 0.89 24 1.63 6.9 256 121 25.9 0.94 23 1.
27.0 0.73 17 1.84 7.6 237 110 24.9 0.70 17 1.80 7.4 230 107 28.3 0.86 19 1.88 7.8 242 113 27.5 0.82 20 1.86 7.7 240 111 25.4 0.79 20 1.81 7.5 232 108 MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR 1050 920 1180 1050 920 1180 27.8 0.76 16 1.86 7.7 240 111 MBh S/T Delta T KW AMPS HI PR LO PR 26.1 0.71 19 1.85 7.7 250 115 28.3 0.74 18 1.90 7.9 258 119 29.1 0.
85 80 IDB* EXPANDED PERFORMANCE DATA COOLING OPERATION 28.0 0.90 22 1.88 7.8 242 113 25.8 0.87 22 1.83 7.6 235 109 29.3 0.99 23 1.91 7.9 247 115 28.5 0.95 24 1.89 7.8 244 114 26.3 0.91 24 1.84 7.6 237 110 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 1050 920 1180 1050 920 26.8 0.88 24 1.89 7.8 255 117 29.0 0.91 23 1.93 8.0 263 121 29.9 0.
33.9 0.73 19 2.31 10.5 236 106 31.3 0.70 19 2.25 10.2 229 103 35.5 0.87 21 2.35 10.6 241 109 34.4 0.83 22 2.33 10.5 238 107 31.8 0.80 22 2.27 10.3 231 104 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 1200 1052 1349 1200 1052 1349 34.9 0.76 18 2.33 10.5 238 107 MBh S/T Delta T KW A MPS HI PR LO PR 32.7 0.71 20 2.32 10.5 249 111 35.5 0.74 20 2.38 10.
85 80 IDB* EXPANDED PERFORM ANCE DATA COOLING OPERATION 35.1 0.91 24 2.35 10.6 241 109 32.4 0.87 25 2.29 10.4 233 105 36.7 1.00 25 2.39 10.8 245 111 35.7 0.95 26 2.37 10.7 243 110 32.9 0.92 26 2.31 10.5 236 106 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 1200 1052 1349 1200 1052 33.6 0.88 26 2.36 10.7 254 113 36.4 0.92 26 2.42 10.9 261 117 37.
38.5 0.72 20 2.52 11.5 234 108 35.6 0.69 20 2.46 11.2 227 105 40.4 0.85 22 2.56 11.7 238 111 39.2 0.81 23 2.54 11.6 236 110 36.2 0.79 23 2.48 11.3 229 106 MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR 1300 1139 1461 1300 1139 1461 39.7 0.75 19 2.54 11.6 236 110 MBh S/T Delta T KW AMPS HI PR LO PR 37.2 0.70 21 2.53 11.5 246 113 40.3 0.73 21 2.60 11.
85 80 IDB* EXPANDED PERFORM ANCE DATA COOLING OPERATION 39.9 0.89 25 2.56 11.7 238 111 36.8 0.86 26 2.50 11.4 231 107 41.8 0.98 26 2.61 11.8 243 113 40.6 0.94 27 2.58 11.8 241 112 37.5 0.90 27 2.52 11.5 234 108 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 1300 1139 1461 1300 1139 38.2 0.87 27 2.58 11.7 251 115 41.4 0.90 26 2.64 12.0 259 119 42.
44.2 0.73 18 2.92 12.6 233 109 40.8 0.70 19 2.85 12.3 226 106 46.3 0.87 21 2.97 12.8 238 112 45.0 0.83 21 2.94 12.7 236 110 41.5 0.80 22 2.87 12.4 229 107 MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR 1600 1400 1800 1600 1400 1800 45.6 0.76 18 2.94 12.7 236 110 MBh S/T Delta T KW AMPS HI PR LO PR 42.8 0.71 20 2.93 12.7 246 114 46.3 0.74 20 3.01 13.
85 80 IDB* EXPANDED PERFORM ANCE DATA COOLIN G OPERATION 45.8 0.91 24 2.97 12.9 238 112 42.3 0.87 24 2.90 12.5 231 108 48.0 1.00 24 3.01 13.1 243 114 46.6 0.95 25 2.99 13.0 240 113 43.0 0.92 26 2.92 12.6 233 109 MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR 1600 1400 1800 1600 1400 43.8 0.88 25 2.98 12.9 251 116 47.5 0.92 25 3.05 13.2 259 120 48.9 0.
54.7 0.68 21 3.67 15.6 236 107 50.5 0.66 22 3.58 15.2 229 103 57.3 0.81 24 3.73 15.8 241 109 55.6 0.77 25 3.70 15.7 238 108 51.3 0.75 25 3.61 15.3 231 105 MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR MBh S/T Delta T KW A MPS HI PR LO PR 1600 1400 1800 1600 1400 1800 56.3 0.71 21 3.70 15.7 238 108 MBh S/T Delta T KW A MPS HI PR LO PR 52.9 0.67 23 3.69 15.6 249 111 57.3 0.69 23 3.79 16.
85 80 IDB* EXPANDED PERFORMANCE DATA COOLING OPERATION 56.6 0.85 28 3.73 15.8 241 109 52.3 0.82 28 3.64 15.4 233 106 59.3 0.93 28 3.80 16.1 245 111 57.6 0.89 29 3.77 16.0 243 110 53.2 0.86 30 3.67 15.6 236 107 MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR MBh S/T Delta T KW AMPS HI PR LO PR 1600 1400 1800 1600 1400 54.2 0.83 30 3.75 15.9 254 113 58.7 0.86 29 3.85 16.3 262 117 60.5 0.
COOLING PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change. 2.
WIRING DIAGRAMS *PC14[24-48]H41** PU NOTE #3 BK BK PU PU BL C BK BL RD T2 RD WARNING HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS *PC1460H41** PU NOTE #3 BK BK 1 2 3 C 208 240 PU BK BL 24V RD BL WARNING HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.