Service Instructions Split System Air Conditioners, Split System Heat Pumps with R-22 Refrigerant Blowers, Coils, & Accessories This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person. Copyright © 2005 - 2014 Goodman Manufacturing Company, L.P.
TABLE OF CONTENTS IMPORTANT INFORMATION ........................... 2 - 3 SYSTEM OPERATION ................................ 28 - 33 MODEL IDENTIFICATION .............................. 4 - 14 TROUBLESHOOTING CHART .......................... 34 AIR HANDLER/COIL IDENTIFICATION ....... 15 - 18 SERVICING TABLE OF CONTENTS ................. 35 ACCESSORIES ........................................... 20 - 25 SERVICING .................................................. 36 - 65 PRODUCT DESIGN ................
IMPORTANT INFORMATION SAFE REFRIGERANT HANDLING While these items will not cover every conceivable situation, they should serve as a useful guide. WARNING Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space.To avoid possible difficulty in breathing or death: • Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed. • If an indoor leak is suspected, thoroughly ventilate the area before beginning work.
PRODUCT IDENTIFICATION Split System Air Conditioners R-22 Model # Description GSC13018-241AA Goodman® Brand Split Condenser 13 Seer condensing units. Initial release. 26" chassis GSC13036-481AA Goodman® Brand Split Condenser 13 Seer condensing units. Initial release. 29" chassis GSC13036,48*AA Goodman® Brand Split Condenser 13 Seer condensing units.
PRODUCT IDENTIFICATION Split System Air Conditioners R-22 Model # GSC130181BB GSC130241DB GSC130301DB GSC130361FB GSC130421BB GSC130481BB GSC130601CB GSC130421CA GSC130481CA GSC130361GB GSC130421CB GSC130481CB GSC130601DB Description Goodman® Brand Split Condenser 13 Seer condensing units. Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and charged with R-22 per the installation instructions. Goodman® Brand Split Condenser 13 Seer condensing units.
PRODUCT IDENTIFICATION Split System Air Conditioners R-22 6 Model # Description GSC130483CB GSC130603CB Goodman® Brand Split Condenser 13 Seer condensing units. Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and charged with R-22 per the installation instructions. The current four piece louver assembly has changed to a two piece louver plus a corner post on Goodman and value series 26" and 29" chassis.
PRODUCT IDENTIFICATION Split System Air Conditioners R-22 Model # Description GSC140**1AA Goodman® Brand Split Condenser 14 Seer condensing units. Introduces Goodman® Brand 14 Seer AC R-22 models. GSC140**1AB Goodman® Brand Split Condenser 14 Seer condensing units. New revisions have screw locations moved in the top panel, base pans, louvers, and control box covers. GSC140**1AC Goodman® Brand Split Condenser 14 Seer condensing units.
PRODUCT IDENTIFICATION Split System Heat Pumps R-22 Model # 8 Description GSH10***AA Goodman® Brand Split Heat Pump 10 Seer heat pump units. Initial release. GSH10***AB Goodman® Brand Split Heat Pump 10 Seer heat pump units. Screw locations moved in the top panel, base pans, louvers, and control box covers. . GSH13***AA Goodman® Brand Split Heat Pump 13 Seer heat pump units. Initial release. GSH13**1AB Goodman® Brand Split Heat Pump 13 Seer heat pump units.
PRODUCT IDENTIFICATION Split System Heat Pumps R-22 Model # Description GSH100903AC GSH101203AC Goodman® Brand Split Heat Pump 10 Seer heat pump units. Initial release of light commercial models without R-22 refrigerant. MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and charged with R-22 per the installation instructions. GSH101203AD Goodman® Brand S plit Heat Pump 10 Seer heat pump units without R-22 refrigerant with new ball valve/brackets, suction tube/assembly and panel w/offset.
PRODUCT IDENTIFICATION Split System Heat Pumps R-22 Model # Description GSH130363AE GSH130483AE GSH130603AC Goodman® Brand Split Pump 13 Seer condensing units. Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and charged with R-22 per the installation instructions. Goodman® Brand Split Pump 13 Seer condensing units. Release of Goodman 13 SEER Condensers with updated serial plates (MCA and compressor RLA/LRA ratings).
PRODUCT IDENTIFICATION Single Piece Air Handlers Model # Description ARUF****16AA A Single Piece R Multi-Position PSC Motor Unpainted Flowrater Introduction of new 13 SEER Air Handler Models. All Models will be suitable for use with R-22 and R-410A ARUF364216AB A Single Piece R Multi-Position PSC Motor Unpainted Flowrater.Revision replaces the current spot welded blower housing with the same cinched or crimped design used on the 80% furnace line.
PRODUCT IDENTIFICATION Single Piece Air Handlers Model # Description AEPF****16AA A Single Piece E Multi-Position Variable-Speed Painted Flowrator. Introducation of new 13 SEER Air Handler Models. All Models will be suitable for use with R22 and R-410A AEPF****16BA A Single Piece E Multi-Position Variable-Speed Painted Flowrator. Revision introduces new models adding lower kw hit kits on the S&R plate AEPF****16BB A Single Piece E Multi-Position Variable-Speed Painted Flowrator.
PRODUCT IDENTIFICATION MBR/MBE Air Handlers Model # Description MBR****AA-1AA Modular Blower R Multi-Position PSC Motor. Introduces module blower with PSC blower motor. MBE****AA-1AA Modular Blower E Multi-Position Variable-Speed. Introduces module blower with variable speed blower motor. MBE****AA-1BA Modular Blower E Multi-Position Variable-Speed.
PRODUCT IDENTIFICATION Evaporator Coils Model # CHPF1824A6CA CHPF2430B6CA CHPF3636B6CA CHPF3642C6CA CHPF3642D6CA CHPF3743C6BA CHPF3743D6BA CHPF4860D6DA CHPF1824A6CB CHPF2430B6CB CHPF3636B6CB CHPF3642C6CB CHPF3642D6CB CHPF3743C6BB CHPF3743D6BB CHPF4860D6DB C Indoor Coil Horizontal A Coil Painted Flowrator. 13 SEER CHPF horizontal A coil, revision has louver fins & replaces copper tube hairpins with aluminum hairpins. C Indoor Coil Horizontal A Coil Painted F lowrator. 13 SEER CHPF horizontal A coil.
PRODUCT IDENTIFICATION G S C BRAND: G: Goodman ® Brand / Amana® Brand Distinctions A: Amana® Brand V: Value 14 036 1 A A MINOR REVISION: A: Initial Release SEER: 10: 10 SEER 13: 13 SEER 14: 14 SEER MAJOR REVISION: A: Initial Release NOMINAL CAPACITY: 018: 1.5 Tons 024: 2 Tons 030: 2.5 Tons 036: 3 Tons 042: 3.
PRODUCT IDENTIFICATION C KL 036 2 REVISION: A: Revision PRODUCT CATEGORY: C: Split System UNIT TYPE: E: Commercial Air Conditioner K: Air Conditioner P: Heat Pump 018: 024: 030: 036: 042: C 1: 2: 3: 4: ELECTRICAL: 208-230V/1ph/60Hz 220-240V/1ph/50 Hz 208-230v/3ph/60Hz 308/415V/3ph/50Hz NOMINAL CAPACITY: 1.5 Tons 048: 4 Tons 2 Tons 060: 5 Tons 2.5 Tons 070: 5 Tons 3 Tons 090: 7.5 Tons 3.
PRODUCT IDENTIFICATION C E 120 5 A REVISION: A: Revision PRODUCT CATEGORY: C: Split System 1: 2: 3: 4: UNIT TYPE: E: Commercial Air Conditioner K: Air Cojditioner P: Heat Pump ELECTRICAL: 208-230V/1ph/60Hz 220-240V/1ph/50 Hz 208-230v/3ph/60Hz 308/415V/3ph/50Hz NOMINAL CAPACITY: 018: 1.5 Tons 048: 4 Tons 024: 2 Tons 060: 5 Tons 030: 2.5 Tons 070: 5 Tons 036: 3 Tons 090: 7.5 Tons 042: 3.
PRODUCT IDENTIFICATION THIS NOMENCLATURE IS TO BE USED AFTER JULY 2006 A W PRODUCT TYPE: A: Air Handler U F 3642 1 6 EXPANSION DEVICE: F: Flowrater T: TXV (Expansion Device) A MINOR REVISION* MAJOR REVISION* CABINET FINISH: U: Unpainted P: Painted N: Uncased APPLICATION C: Ceiling Mount PSC Motor D: Downflow PSC Motor E: Multi-Position Varible Speed Motor S: Energy- Efficient Motor R: Multi-Position PSC Motor T: Coated Coils W: Wall Mount PSC Motor A REFRIGERANT CHARGE: No Digit: R-22 Only 6:
PRODUCT IDENTIFICATION C A P F 1824 A 6 A EXPANSION DEVICE: F: Flowrater PRODUCT TYPE: C: Indoor Coil REVISION A: Revision REFRIGERANT CHARGE: 6: R-410A or R-22 2: R-22 4: R-410a CABINET FINISH: U: Unpainted P: Painted N: Unpainted Case NOMINAL WIDTH FOR GAS FURNACE A: Fits 14" Furnace Cabinet B: Fits 17 1/2" Furnace Cabinet C: Fits 21" Furnace Cabinet D: Fits 24 1/2" Furnace Cabinet N: Does Not Apply (Horizontal Slab Coils) APPLICATION A: Upflow/Downflow Coil H: Horizontal A Coil S: Horizonta
ACCESSORIES Model Description ASC13018 ASC13024 ASC13030 ASC13036 ASC13042 ASC13048 ASC13060 OT18-60A FSK01A* Outdoor Thermostat --- --- --- --- --- --- --- Freeze Protection Kit Anti Short Cycle Kit TXV Kit X X X X X X X X X X X X X X X TXV Kit TXV Kit x --- --x --- --x --- --x --- ----- ----- ----- X X X Hard Start Kit Hard Start Kit X X X X --- --- --- ----- ----- ----- X X --- --- X X X X X X X X X X X ASC01 TX2N2* TX3N2* TX5N2* CSR-U-1 C
ACCESSORIES Model AFE18-60A OT18-60A FSK01A* ASC01 TX2N2* TX3N2* TX5N2* OT18-60A OT/EHR18-60 CSR-U-1 CSR-U-2 CSR-U-3 LSK02A Model AFE18-60A OT18-60A FSK01A* ASC01 TX2N2* TX3N2* TX5N2* OT18-60A OT/EHR18-60 CSR-U-1 CSR-U-2 CSR-U-3 LSK02A Model FSK01A* ASC01 OT/EHR18-60 LSK03* Description All Fuel Kit Outdoor Thermostat Freeze Protection Kit Anti Short Cycle Kit G/VSH13018 X X X X G/VSH13024 X X X X G/VSH13030 X X X X G/VSH13036 X X X X G/VSH13042 X X X X G/VSH13048 X X X X G/VSH13060 X X X X TXV Ki
ACCESSORIES Model AFE18-60A Description All Fuel Kit OT18-60A Outdoor Thermostat FSK01A* Freeze Protection Kit ASC01 Anti Short Cycle Kit TX2N2* TXV Kit TXV Kit TX3N2* TX5N2* TXV Kit OT18-60A Outdoor Lockout Stat OT/EHR18-60 Emergency Heat relay kit CSR-U-1 Hard Start Kit CSR-U-2 Hard Start Kit CSR-U-3 Hard Start Kit Model AFE18-60A Description All Fuel Kit OT18-60A Outdoor Thermostat FSK01A* Freeze Protection Kit Anti Short Cycle Kit ASC01 TX2N2* TXV Kit TX3N2* TXV Kit TX5N2
ACCESSORIES EXPANSION VALVE KITS For Applications requiring 1/4 FLARE CONNECTION BULB TO BE LOCATED AT 10 OR 2 O'CLOCK a field installed access fitting BULB SUCTION LINE EVAPORATOR COIL PISTON SEAL SUPPLIED W/ KIT SEAL SUPPLIED W/ KIT SEAL DISTRIBUTOR BODY EXPANSION VALVE TAILPIECE REMOVE BEFORE INSTALLING EXPANSION VALVE 3/8"SWEAT 7/8" NUT For Applications not requiring 1/4' FLARE CONNECTION a field installed access fitting BULB TO BE LOCATED AT 10 OR 2 O'CLOCK BULB SUCTION LINE PISTON EX
ACCESSORIES FSK01A FREEZE THERMOSTAT KIT Wire Nut Y Bla ck Y a Bl ck Wire Nut Install Line Thermostat Here Install Line Thermostat Here Wire Nut Bla ck Y Bla ck Wire Nut Y ASC01A ANTI-SHORT -CYCLE CONTROL KIT SHORT CYCLE PROTECTOR Y1 R1 Y2 R2 YELLOW 1 CONTACTOR T2 T1 Y BLACK 1 THERMOSTAT WIRE L2 L1 C BLACK 1 24 UNIT TERMINAL BOARD
ACCESSORIES COIL ACCESSORIES COIL MODEL TX2N2 TXV KIT TX3N2 TXV KIT TX5N2 TXV KIT FSK01A FREEZE PROTECTION KIT CA*F030B4* --- X --- X CA*F036B4* --- X --- X CA*F042C4* --- --- X X CA*F048C4* --- --- X X CA*F057D4* --- --- X X CA*F060D4* --- --- X X CHPF030A4* --- X --- X CHPF036B4* --- X --- X CHPF042A4* --- --- X X CHPF048D4* --- --- X X CHPF060D4* --- --- X X CH36FCB --- X --- X CH48FCB --- --- X X CH60FCB --- --- X X CA*F18246* X
PRODUCT DESIGN This section gives a basic description of cooling unit operation, its various components and their basic operation. Ensure your system is properly sized for heat gain and loss according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent. CONDENSING UNIT These units are designed for free air discharge. Condensed air is pulled through the condenser coil by a direct drive propeller fan and then discharged from the cabinet top.
PRODUCT DESIGN The MBR/MBE blower cabinets with proper coil matches can be positioned for upflow, counterflow, horizontal right or horizontal left operation. All units are constructed with R-4.2 insulation. In areas of extreme humidity (greater than 80% consistently), insulate the exterior of the blower with insulation having a vapor barrier equivalent to ductwork insulation, providing local codes permit.
SYSTEM OPERATION COOLING HEATING The refrigerant used in the system is R-22. It is a clear, colorless, non-toxic, non-irritating, and non-explosive liquid. The chemical formula is CHCLF2. The boiling point, at atmospheric pressure is -41.4°F. The heating portion of the refrigeration cycle is similar to the cooling cycle. By energizing the reversing valve solenoid coil, the flow of the refrigerant is reversed.
SYSTEM OPERATION DEFROST CYCLE HEATING CYCLE The defrosting of the outdoor coil is jointly controlled by the defrost timing board, defrost (30/60) control, and compressor run time. The reversing valve on the heat pump models is energized in the cooling cycle through the "O" terminal on the room thermostat. Solid State Defrost Control These models have a 24 volt reversing valve coil.
SYSTEM OPERATION COOLING CYCLE Reversing Valve (Energized) Outdoor Coil Indoor Coil Accumulator Thermostatic Expansion Valve Bi-Flow Filter Dryer Check Valve HEATING CYCLE Reversing Valve (De-Energized) Indoor Coil Outdoor Coil Accumulator Thermostatic Expansion Valve Bi-Flow Filter Dryer Check Valve 30
SYSTEM OPERATION EXPANSION VALVE/CHECK VALVE ASSEMBLY IN COOLING OPERATION EXPANSION VALVE/CHECK VALVE ASSEMBLY IN HEATING OPERATION Most expansion valves used in current Amana® Brand Heat Pump products use an internally checked expansion valve. This type of expansion valve does not require an external check valve as shown above. However, the principle of operation is the same.
SYSTEM OPERATION COOLING CYCLE - CONDENSING UNIT Indoor Coil Outdoor Coil Thermostatic Expansion Valve In the cooling mode, the orifice is pushed into its seat, forcing refrigerant to flow through the metered hole in the center of the orifice.
SYSTEM OPERATION AFE18-60A CONTROL BOARD DESCRIPTION The AFE18 control is designed for use in heat pump applications where the indoor coil is located above/downstream of a gas or fossil fuel furnace. It will operate with single and two stage heat pumps and single and two stage furnaces. The AFE18 control will turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature is also incorporated which initiates a 3 minute timed off delay when the compressor goes off.
TROUBLESHOOTING CHART COOLING/HP ANALYSIS CHART Pow er Failure Blow n Fuse Unbalanced Pow er, 3PH Loose Connection Shorted or Broken Wires Open Fan Overload Faulty Thermostat Faulty Transf ormer Shorted or Open Capacitor Internal Compressor Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor Faulty Fan Relay Open Control Circuit Low V oltage Faulty Evap.
SERVICING Table of Contents S-1 CHECKING VOLTAGE ............................................ 36 S-2 CHECKING WIRING ................................................ 36 S-3 CHECKING THERMOSTAT, WIRING, S-41 CONDENSERS ...................................................... 51 S-41A A AEP* & MBE WITH SINGLE STAGE AND ANTICIPATOR ................................................. 36 S-3A THERMOSTAT AND WIRING ................................... 36 S-3B COOLING ANTICIPATOR ............................
SERVICING S-2 CHECKING WIRING S-1 CHECKING VOLTAGE 1. Remove outer case, control panel cover, etc., from unit being tested. With power ON: WARNING Line Voltage now present. 2. Using a voltmeter, measure the voltage across terminals L1 and L2 of the contactor for the condensing unit or at the field connections for the air handler or heaters. 3. No reading - indicates open wiring, open fuse(s) no power or etc., from unit to fused disconnect service. Repair as needed. 4.
SERVICING 4. Check the continuity of the thermostat and wiring. Repair or replace as necessary. Resistance Heaters 1. Set room thermostat setpoint to a higher temperature than room temperature to assure both stages call for heat. 2. With voltmeter, check for 24 volts at each heater relay. 3. No voltage indicates the trouble is in the thermostat or wiring. 4. Check the continuity of the thermostat and wiring. Repair or replace as necessary. NOTE: Consideration must be given to how the heaters are wired (O.D.
SERVICING S-6 CHECKING TIME DELAY RELAY 1. Remove the leads from the holding coil. Time delay relays are used in some of the blower cabinets to improve efficiency by delaying the blower off time. Time delays are also used in electric heaters to sequence in multiple electric heaters. 2. Using an ohmmeter, test across the coil terminals. WARNING If the coil does not test continuous, replace the relay or contactor. S-8 CHECKING CONTACTOR CONTACTS Disconnect ALL power before servicing. 1.
SERVICING WARNING Line Voltage now present. 4 3 OHMMETER 2 5 1 TESTING FAN RELAY 4. Using an ohmmeter, test between 2 and 4 - should read continuous . Test between 5 and 4 - should read open. 5. If not as above, replace the relay.
SERVICING DIAGNOSTICS TABLE Status LED Green “POWER” Red “TRIP” Status LED Description Module has power Status LED Troubleshooting Information Supply voltage is present at module terminals Thermostat demand signal 1. Compressor protector is open Y1 is present, but the 2. Outdoor unit power disconnect is open compressor is not 3. Compressor circuit breaker or fuse(s) is open running 4. Broken wire or connector is not making contact 5. Low pressure switch open if present in system 6.
SERVICING S-11 CHECKING LOSS OF CHARGE PROTECTOR (Heat Pump Models) The loss of charge protector senses the pressure in the liquid line and will open its contacts on a drop in pressure. The low pressure control will automatically reset itself with a rise in pressure. The low pressure control is designed to cut-out (open) at approximately 7 PSIG. It will automatically cut-in (close) at approximately 25 PSIG.
SERVICING B. Shorted - indicator swings to zero and stops there replace. 1. Remove the motor leads from its respective connection points and capacitor (if applicable). C. Open - no reading - replace. (Start capacitor would read resistor resistance.) 2. Check the continuity between each of the motor leads. S-15B CAPACITANCE CHECK Using a hookup as shown below, take the amperage and voltage readings and use them in the formula: 3.
SERVICING } 1 2 Lines 1 and 2 will be connected for 12OVAC Power Connector applications only 3 Gnd 4 AC Line Connection 5 AC Line Connection OUT - 8 16 OUT + ADJUST +/- 7 15 G (FAN) Y1 6 14 Y/Y2 COOL 5 13 EM Ht/W2 DELAY 4 12 24 Vac (R) COMMON2 3 11 HEAT W/W1 2 10 BK/PWM (SPEED) COMMON1 1 9 O (REV VALVE) 4. Using an ohmmeter, check the motor windings for continuity to ground (pins to motor shell).
- Does removing panel or filter reduce "puffing"? - Check/replace filter. - Check/correct duct restrictions. - Adjust to correct blower speed setting. - Incorrect or dirty filter(s). - Incorrect supply or return ductwork. - Incorrect blower speed setting. - Varies up and down or intermittent. - "Hunts" or "puffs" at high CFM (speed). ---- - Check line voltage for variation or "sag". - Check low voltage connections (G, Y, W, R, C) at motor, unseated pins in motor harness connectors.
- Turn power OFF prior to repair. - Turn power OFF prior to repair. - Check for loose blower housing, panels, etc. - Check for air whistling thru seams in ducts, cabinets or panels. - Check for cabinet/duct deformation. - Does removing panel or filter reduce "puffing"? - Check/replace filter. - Check/correct duct restrictions. - Adjust to correct blower speed setting. - Loose blower housing, panels, etc. - High static creating high blower speed. - Air leaks in ductwork, cabinets, or panels.
SERVICING DIPSWITCH FUNCTIONS The MBE air handler motor has an electronic control that contains an eight (8) position dip switch. The function of these dipswitches are shown in Table 1.
SERVICING HUMIDITY CONTROL When using a Humidstat (normally closed), cut jumper PJ6 on the control board. The Humidstat will only affect cooling airflow by adjusting the Airflow to 85%. TWO STAGE HEATING When using staged electric heat, cut jumper PJ4 on the control board. S-16E CHECKING GE X13TM MOTORS The GE X13TM Motor is a one piece, fully encapsulated, 3 phase brushless DC (single phase AC input) motor with ball bearing construction. Unlike the ECM 2.3/2.
SERVICING HI-POT 1. Remove the leads from the compressor terminals. See warnings S-17 before removing compressor terminal cover. 2. Using an ohmmeter, test continuity between terminals SR, C-R, and C-S, on single phase units or terminals T2, T2 and T3, on 3 phase units. COMPRESSOR GROUND TEST 3. If a ground is indicated, then carefully remove the compressor terminal protective cover and inspect for loose leads or insulation breaks in the lead wires. 4.
SERVICING A. If the compressor starts and continues to run, the cause for failure is somewhere else in the system. B. If the compressor fails to start - replace. COPELAND COMPRESSOR 03 A 12345 L If voltage is registered at the coil, tap the valve body lightly while switching the system from HEATING to COOLING, etc. If this fails to cause the valve to switch positions, remove the coil connector cap and test the continuity of the reversing valve solenoid coil.
SERVICING S-40 AR*F & MBR ELECTRONIC BLOWERS TIME DELAY RELAY The MBR contains an Electronic Blower Time Delay Relay board, PCBFM103. This board provides on/off time delays for the blower motor in cooling and heat pump heating demands when “G” is energized. During a cooling or heat pump heating demand, 24Vac is supplied to terminal “G” of the EBTDR to turn on the blower motor. The EBTDR initiates a 7 second delay on and then energizes it’s onboard relay.
SERVICING 4.4 In order to make sure the blower is running when heat is on, the normally closed contacts on the EBTDR will power the blower motor if no G signal is received. 4.5 There may be delay on activation or deactivating heater elements. 5.0 Defrost Operation On heat pump units, when the room thermostat is set to the heating mode, the reversing valve is not energized.
SERVICING 24Vac from “W2” and the VSTB will remove the 24Vac from HR2. The contacts on HR2 will open between 30 to 70 seconds and heater elements #3 and #4 will be turned off and the blower motor will change to low speed. On most digital/electronic thermostats, “W2” will remain energized until the first stage demand “W1” is satisfied and then the “W1” and “W2” demands will be removed. 2.
SERVICING 5.0 Defrost Operation On heat pump units, when the room thermostat is set to the heating mode, the reversing valve is not energized. As long as the thermostat is set for heating, the reversing valve will be in the de-energized position for heating except during a defrost cycle. 5.1 The heat pump will be on and operating in the heating mode as described the Heating Operation in section 4. 5.
SERVICING S-61A CHECKING HEATER LIMIT CONTROL(S) CFM 600 700 TEMPERATURE RISE (F°) @ 240V 3 4.8 7.2 9.6 14.4 19.2 KW KW KW KW KW KW 16 25 38 51 ----14 22 33 43 ----- 24 KW ----- 28.
SERVICING S-100 REFRIGERATION REPAIR PRACTICE DANGER Always remove the refrigerant charge in a proper manner before applying heat to the system. When repairing the refrigeration system: WARNING To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig. 1. Never open a system that is under vacuum. Air and moisture will be drawn in.
SERVICING CAUTION R-22 MANIFOLD Use refrigerant certified to AHRI standards. Used refrigerant may cause compressor damage and will void the warranty. Most portable machines cannot clean used refrigerant to meet AHRI standards. HIGH SIDE GAUGE AND VALVE LOW SIDE GA UGE AND VALVE CAUTION 800 PSI RATED HOSES CHARGING CYLINDER AND SCALE Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage.
SERVICING Verification of proper rotation of Scroll Compressors is made as follows. SYSTEM SUPERHEAT NOTE: The compressor may run backwards (noisy operation) for 1 or 2 seconds at shutdown. This is normal and does not harm the compressor. Return Air Temperature (°F Drybulb) Ambient Condenser Inlet Temp.
SERVICING S-105A PISTON KIT CHART FOR ASC13, GSC13, VSC13, GSC14, ASH13, GSH13, VSH14, GSH14 UNITS Air Conditioners Orifice Size Heat Pumps S-105B THERMOSTATIC EXPANSION VALVE Orifice Size .052 GSC130181A* / B* / C* .055 G/VSH130181A* VSC130181A* / B* G/VSC130241A* .055 GSH130181B* .059 G/VSH130191A* .052 G/VSH130241A* .061 GSC130241C* .055 AC30, ACNF24 .059 GSH130241B* .061 AWB24/AWUF24 .059 G/VSH130251A* .061 # All other ARI Matches .061 G/VSH130301A* .
SERVICING S-107 UNDERFEEDING Underfeeding by the expansion valve results in low system capacity and low suction pressures. If these symptoms are observed: 1. Check for a restricted liquid line or drier. A restriction will be indicated by a temperature drop across the drier. 2. Check the operation of the power element of the valve as described in S-110 Checking Expansion Valve Operation. S-108 SUPERHEAT The expansion valves are factory adjusted to maintain 12 to 18 degrees superheat of the suction gas.
SERVICING Temp. °F. Gauge Pressure (PSIG) Freon-22 Temp. °F. Gauge Pressure (PSIG) Freon-22 -40 -38 -36 -34 -32 -30 -28 -26 -24 -22 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 0.61 1.42 2.27 3.15 4.07 5.02 6.01 7.03 8.09 9.18 10.31 11.48 12.61 13.94 15.24 16.59 17.99 19.44 20.94 22.49 24.09 25.73 27.44 29.21 31.04 32.93 34.88 36.89 38.96 41.09 43.28 45.53 47.85 50.24 52.70 55.23 57.83 60.51 63.27 66.11 69.02 71.99 75.04 78.18 81.
SERVICING S-111 FIXED ORIFICE RESTRICTOR DEVICES The fixed orifice restrictor device (flowrator) used in conjunction with the indoor coil is a predetermined bore (I.D.). It is designed to control the rate of liquid refrigerant flow into an evaporator coil. The amount of refrigerant that flows through the fixed orifice restrictor device is regulated by the pressure difference between the high and low sides of the system.
SERVICING Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a Sporlan Acid Test Kit, AK3 or its equivalent. Remove the compressor and obtain an oil sample from the suction stub. If the oil is not acidic, either a burnout has not occurred or the burnout is so mild that a complete clean-up is not necessary. If acid level is unacceptable, the system must be cleaned by using the clean-up drier method. CAUTION Do not allow the sludge or oil to contact the skin.
SERVICING • The distance between the condenser and evaporator in a completely horizontal installation in which the indoor and outdoor unit do not differ more than 10 feet in vertical distance from each other can approach 150 feet, as long as the equivalent length does not exceed 150 feet. 4. Two-Stage Condensing Unit: The maximum length of tubing must not exceed 75 feet here indoor coil is located above the outdoor unit.
SERVICING 3. An oil trap is required at the evaporator only if the condenser is above the evaporator. Preformed oil traps are available at most HVAC supply houses, or oil traps may be created by brazing tubing elbows together (see diagram below). Remember to add the equivalent length from oil traps to the equivalent length calculation of the suction line.
SERVICING 3. Add the two readings together. 3. Consult proper table for quantity of air. TOTAL EXTERNAL STATIC NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. 4. Consult proper table for quantity of air. If external static pressure is being measured on a furnace to determine airflow, supply static must be taken between the "A" coil and the furnace.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS BL 5 208 2 3 COM TR 240 1 9 8 9 8 R G 24V BL L2 4 L1 R HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. EQUIPMENT GROUND USE COPPER WIRE COPPER POWER SUPPLY (SEE RATING PLATE) USE MIN. 75°C FIELD WIRE Typical Wiring Schematic ASPF****16B* with Electric Heat. This wiring diagram is for reference only. Not all wiring is as shown above.
ACCESSORIES WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.