DUCTED APPLICATION AZ45/AZ65 SERIES)
44"
DUCT ADAPTER EXTENSION HAS 1/2" INSULATION
Notes:
1. RAK6053 kit includes duct adapter, transition and mounting hardware.
2. RAK601B duct extension may be installed at either end of the RAK6053
duct adapter. Maximum duct extension length is 15'. Duct extension must
be field fabricated for installations where length of duct exceeds length
of RAK601B (44"). Field-fabricated duct extension must be insulated to
prevent condensation from forming on exterior. Duct extension may not
contain bends or turns.
3. Ducted units may need to be permanently connected. Check local code
for specific electrical installation requirements.
4. Duct extension kit RAK601B contains 44" duct extension, discharge
grille mounting collar, and discharge grille. Duct extension must be cut
to required length. Two ducted installations may be made from one kit
if the combined ducted length is less than 44". RAK602B kit contains
mounting collar, discharge grille and mounting hardware necessary
for second installation.
5. Filler strip (field supplied) actual width depends upon wall sleeve projection
into room. A flush installation to finished wall (i.e., no filler strip) can
be made.
6. Unit must be installed to provide at least a 2" clearance between side
of unit and wall.
7. Provisions for return air must be made in order to allow air circulation
from secondary room. Doors in both secondary and primary rooms may
be undercut or a return grille may be installed through common wall.
8. For replacement of previous-design units, see pages 39, 42 and 55–56.
RAK601
44" LENGTH
RAK6053
ADAPTER
TRANSITION
RECOMMENDED
MINIMUM
CLEARANCE
2" TO SIDE WALL
7-3/8"
wide
8" high
DUCTED INSTALLATIONS (CONTINUED)