METAL SLEEVE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)
Field fabricated – GE Appliances recommends the use of one of the deeper RAB71† wall sleeves offered as special order items.
CAULK*
SPLITTER BETWEEN
AIR INTAKE AND
DISCHARGE
GE Zoneline
®
units can be installed in walls of greater
depth than the wall sleeve. Where the sleeve recession
is less than 3" and where it is possible to waterproof
the exposed sides and top of the opening, the
suggested procedure is to apply a flashing to the
bottom of the wall sleeve as shown on page 33. Where
waterproofing is questionable or not possible, or for
installations in walls of greater depth, the following
is a suggested application procedure. It involves the
field fabrication of a sleeve extension. Since the wall
sleeve is a water - bearing container, the extension
likewise must also be water-bearing and the
connection between the two must be watertight. The
sleeve extension must contain splitters to prevent
recirculation of the outdoor air circuit.
1. The sleeve extension is field fabricated. The
extension depth “D” should allow for a minimum
outdoor projection of 1/4". This allows for room
cabinet clearance to the finished wall and ample
surfaces to apply sealant or caulking for a tight
weather seal between the completed wall sleeve/
extension assembly and the wall opening. It is
recommended that the extension be painted and
corner and lap joints be additionally sealed with
a quality-grade sealant.
2. The wall sleeve and extension should be connected prior
to installation in the wall opening. A quality-grade sealant
should be applied to all four (4)butting flanges. Use bolts
and nuts or oversized self-tapping screws (driven from the
wall sleeve to the extension) to attach the two assemblies.
Clean all drain holes of excess sealant. The assembly must
be free draining.
3. Install flashing, using a quality-grade sealant between the
flashing and wall as shown in section A-A below.
4. Install the wall sleeve/extension assembly following
procedures described for a standard installation. See
diagrams below. The assembly should be sealed or
caulked to the wall around all four sides both outdoors and
indoors.
NOTE: The wall sleeve/extension assembly should be level.
5. Suggested materials for sleeve extension and
flashing should be non-ferrous metals. Minimal
acceptable material: Galvanized G-90 painted.
SEALANT - ALL
FOUR (4) FLANGES
6-1/4" ± 1/4"
AS REQ'D.
CUT DRAIN SLOTS
IN BOTH FLANGES
(FOUR REQUIRED)
TO MATCH DRAIN
HOLES IN RAB71B/77B
FLANGES AND
DRAIN HOLE
LOCATIONS
SAME AS ON
WALL Sleeve
1" WIDE
45° DRIP LIP
FLASHING (FIELD SUPPLIED)
13-3/4" + D"
2" MIN.
D
10-5/8" ± 1/4"
CAULK*
CAULK*
CAULK*
WALL -
ANY
CONSTRUCTION
RAB71B/77BROOM
CABINET
Sleeve
EXT.
SEE DETAIL
SECTION A-A
*Caulk around perimeter of wall sleeve all four sides
where it joins the building - Interior and Exterior.
EXTENSION
ALL 4 FLANGES
WALL Sleeve
ALL 4
SIDES
WALL
FLASHING
ALL 4
SIDES
SECTION A-A
BASEPAN/FLANGE DESIGN
SHOWING SEALANT LOCATIONS.
1/4" MIN.
RAB71B/77B
WALL Sleeve
1-1/2"
(4 SIDES)
EXTENSION
(FIELD
SUPPLIED)
WORKS FOR ALL RAB71 OR RAB77 SERIES WALL SLEEVE
WALL SLEEVE INSTALLATION DATA (CONTINUED)