Data Manual

15
Mode 4Constant ON fan
The default setting for Mode 4 is OFF.
NOTE: Constant fan “on” runs the indoor fan continuously
at high speed—even if the unit is turned off.
Mode 5Temperature limiting
The default setting for Mode 5 is as follows:
Cool: 2 (66ºF to 85ºF) Heat: 5 (60ºF to 78ºF)
Temperature limits—Cool Temperature limits—Heat
0 = 60°F to 85°F 0 = 60°F to 65°F
1 = 64°F to 85°F 1 = 60°F to 70°F
2 = 66°F to 85°F 2 = 60°F to 72°F
3 = 68°F to 85°F 3 = 60°F to 74°F
4 = 70°F to 85°F 4 = 60°F to 76°F
5 = 72°F to 85°F 5 = 60°F to 78°F
6 = 74°F to 85°F 6 = 60°F to 80°F
7 = 76°F to 85°F 7 = 60°F to 85°F
Mode 6Remote thermostat – Class 2
The default setting for Mode 6 is OFF. Setting this mode
to ON will allow the unit to operate with a Class 2 Remote
Control Wall Thermostat. Hitting the + button a second time
will turn on Mode 6A, which is required for auto-changeover
thermostats.
Mode 7—Duct mode
The default setting for Mode 7 is OFF. This setting is used
when the unit is installed using a duct adapter kit. If the
unit is ducted, the Duct Mode needs to be set to ON.
This increases the fan speed to ensure proper circulation.
NOTE: Heater wattages are reduced in duct mode
(see page 39).
NOTE: This function is disabled on Dry Air 25 models.
Mode 8—All-electric heat (AZ65 only)
The default setting for Mode 8 is OFF. This electric heat
option functions only on the AZ65 model. When this option
is ON, heat pump operation is locked out, causing the unit
to provide only electric resistance heat.
Mode 9—Heat boost (AZ65 only)
The default setting for Mode 9 is OFF. The Heat Boost option
works with remote thermostat operation and unit control
operation. This setting is used to provide 1000 watts of
supplementary electric heat to the heat pump operation.
“Mode”
Press
+ / –
+ / –
+ / –
+ / –
+ / –
+ / –
+ / –
+ / –
+ / –
HEAT
COOL
Freeze Sentinel Off
Freeze Sentinel On
“Mode”
Press
HEAT
COOL
Heat Sentinel Off
Heat Sentinel On
“Mode”
Press
Constant Fan – Off
Constant Fan – On
“Mode”
Press
Duct Mode – Off
Duct Mode – On
“Mode”
Press
ALL Electric Mode – Off
ALL Electric Mode – On
“Mode”
Press
Boost Heat – Off
Boost Heat – On
“Mode”
Press
HEAT
COOL
Temperature Limit Cool
“Mode”
Press
Class 2 Mode – Off
Auto Change
Over
Class 2 Mode – On
0: 60F-85F
1: 64F-85F
2: 66F-85F
3: 68F-85F
4: 70F-85F
5: 72F-85F
6: 74F-85F
7: 76F-85F
“Mode”
Press
HEAT
COOL
Temperature Limit Heat
0: 60F-65F
1: 60F-70F
2: 60F-72F
3: 60F-74F
4: 60F-76F
5: 60F-78F
6: 60F-80F
7: 60F-85F
NOTE: Boost heat will not operate below 25°F outdoor
ambient conditions or above 85°F ambient conditions.
In those conditions, boost heat will be replaced by all
electric heat.
Mode 0—Digital Makeup Air Module Fan Speed
Press MODE until a 0 appears in the first digit of the display for the Digital Makeup Air mode. To turn o the module
or change the fan speeds, press the + or - pad. 00 indicates the module is o. 01=module on with fans set at 25cfm,
02= module on with fans set at 30cfm, etc. The default setting for Mode 0 is ON with a fan speed of 35cfm
“ ”
.
Mode E—Digital Makeup Air Module in Occupancy
To enable occupancy detection, press MODE until an E appears in the first digit of the display. Press the + or -pad
to set occupancy detection to OFF “ ” or ON “ ”. The default setting for Mode E is OFF “ ”.
Mode P—Engineering Revision Setup
This setting is used to configure the unit when the main control board is
replaced. The first time the unit is powered after a service board is installed,
the unit will automatically enter this mode. The UI will read “P1. Press
the + pad until the number matches the PTAC engineering revision as
shown. The engineering revision is the last number in the model number.
Press “Aux” to save and exit.
AZ45E09DABW2
Nomenclature Example
Engineering
Revision
MODE P
AUXILIARY CONTROL SETTINGS (CONTINUED)
ARCHITECTS & ENGINEERS DATA MANUAL AZ45/AZ65 SERIES