Gallagher T12 Reader Installation Note T12 Mifare Reader Black: C300420 T12 Mifare Reader White: C300421 T12 Multi Tech Reader Black: C300440 T12 Multi Tech Reader White: C300441 3E4290 Gallagher T12 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited Page 1
Disclaimer This document gives certain information about products and/or services provided by Gallagher Group Limited or its related companies (referred to as "Gallagher Group"). The information is indicative only and is subject to change without notice meaning it may be out of date at any given time.
Contents 1 Introduction...................................................................................................................................... 4 2 Before you begin............................................................................................................................... 4 3 Distance between readers................................................................................................................ 7 4 Installation..........................................
1 Introduction The Gallagher T12 Reader is a mobile credential and smart card proximity reader. It can be installed as either an entry reader or exit reader. It can be mounted on a BS 4662 British Standard square flush box. The reader sends information to the Gallagher Controller and acts upon information sent from the Gallagher Controller. The reader itself does not make any access decisions. The reader is available in four variants. The card technologies for each variant are shown below.
2.2 Power supply The Gallagher T12 Reader is designed to operate over a supply voltage range of 9 - 16 Vdc measured at the reader terminals. The operating current draw is dependant on the supply voltage at the reader. For the Mifare reader, at 13.6 Vdc the current draw is 84 mA (idle). During card read, beeper and LED activity, the current will momentarily reach 113 mA (maximum). For the Multi Tech reader, at 13.6 Vdc the current draw is 100 mA (idle) and will momentarily reach 124 mA (maximum).
HBUS Device HBUS Device "T" or "Star" circuits are not permitted between HBUS devices RS485 1 HBUS Device HBUS Device Controller 6000 Terminate Remove the on-board termination jumper Terminate HBUS Device HBUS Device "T" or "Star" circuits are not permitted between HBUS devices Controller 6000 HBUS Device H1 H5 HBUS Device H4 H8 HBUS Device HBUS Module Terminate HBUS Device Terminate HBUS Device HBUS Device Terminate Terminate Cable distance Cable type Cable format* CAT 5e or bet
** Recommended cable types for optimal HBUS RS485 performance. *** Not applicable for Gallagher mobile credential reader installations. Notes: 3 • Shielded cable may reduce the obtainable cable length. Shielded cable should be grounded at the Controller end only. • If other cable types are used, operating distances and performance may be reduced depending on the cable quality. • HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at least 9 Vdc to function correctly.
2. Run the building cabling out through the centre hole and through the reader bezel. 3. Secure the bezel to the flush box using the two M3.5 screws provided. It is important the bezel of the reader is flush with and tight against the mounting surface. If you are not mounting to a flush box, secure the bezel to the mounting surface using the four fixing screws provided. Note: It is strongly recommended that you use the screws provided.
Cardax IV Reader Cardax IV Reader connection: Positive Negative HBUS Termination HBUS A HBUS B CDXIV TX CDXIV RX Red Black Orange Green Brown White Blue 5. Fit the facia assembly into the bezel by clipping the small lip, into the top of the bezel and holding the top, press the bottom of the facia assembly down into the bezel. 6. Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) through the hole at the bottom of the bezel to secure the facia assembly.
5 6 LED indications LED (squiggle) HBUS indication 3 Flash (Amber) No communications with the Controller. 2 Flash (Amber) Communications with the Controller, but reader is not configured. 1 Flash (Amber) Configured to a Controller, but reader is not assigned to a door or elevator car. On (Green or Red) Fully configured and functioning normally. Green = Access mode is Free Red = Access mode is Secure Flashes Green Access has been granted. Flashes Red Access has been denied.
7 Technical specifications Routine maintenance: Not applicable for this reader Cleaning: This reader should only be cleaned with a clean, lint free, damp cloth Voltage: 9 Vdc - 16 Vdc Current: Mifare Reader Idle 1 2 3 1 Maximum Multi Tech Reader 2 Idle 1 Maximum 2 at 9 Vdc 124 mA 175 mA 115 mA 164 mA at 13.
8 Approvals and standards This symbol on the product or its packaging indicates that this product must not be disposed of with other waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.
9 Mounting dimensions 30 mm (1.18") 10 mm (0.39") 26 mm (1") 86 mm (3.39") 22.3 mm (0.88") 29 mm (1.14") 13 mm (1/2") diameter hole for cable 40 mm (1.57") 35 mm (1.38") 25 mm (1") 86 mm (3.39") IMPORTANT This picture is not to scale, therefore use the measurements provided.