Disclaimer This document gives certain information about products and/or services provided by Gallagher Group Limited or its related companies (referred to as "Gallagher Group"). The information is indicative only and is subject to change without notice meaning it may be out of date at any given time.
Contents 1 Introduction...................................................................................................................................... 4 2 Before you begin............................................................................................................................... 4 3 Distance between readers................................................................................................................ 7 4 Installation..........................................
1 Introduction The Gallagher T10 Reader is a smart card proximity reader. It can be installed as either an entry reader or exit reader. The reader sends information to the Gallagher Controller and acts upon information sent from the Gallagher Controller. The reader itself does not make any access decisions. The reader is available in four variants. The card technologies for each variant are shown below.
2.3 Cabling The Gallagher T10 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm2) stranded security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When using a single cable to carry both power supply and data, both the power supply voltage drop and data requirements must be considered. Although the reader is specified to operate at 9 Vdc, for good engineering design it is recommended that the voltage at the reader should be approximately 12 Vdc.
HBUS Device "T" or "Star" circuits are not permitted between HBUS devices Controller 6000 HBUS Device H1 H5 HBUS Device H4 H8 HBUS Device HBUS Module Terminate HBUS Device Terminate HBUS Device HBUS Device Terminate Terminate Cable distance Cable type Cable format* CAT 5e or better** HBUS single reader connected using data only in a single cable Cardax IV single reader connected using data only in a single cable HBUS/Cardax IV single reader connected using power and data in a single cabl
3 Distance between readers The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions. When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of the wall is not less than 200 mm (8 in) away. 200 mm 200 4 mm Installation ATTENTION: This equipment contains components that can be damaged by electrostatic discharge. Ensure both you and the equipment are earthed before beginning any servicing.
No. 6 pan head screw Bezel Building cable No. 6 pan head screw 4. Connect the reader tail extending from the facia assembly to the building cable. Connect the wires for the appropriate reader you wish to interface, either an HBUS Reader or a Cardax IV Reader, as shown. Note: Gallagher PIV readers must be connected as HBUS Readers. Gallagher PIV readers connect to the Gallagher Controller 6000 High Spec PIV (C305101) only.
5. Fit the facia assembly into the bezel by clipping the small lip, into the top of the bezel and holding the top, press the bottom of the facia assembly down into the bezel. 6. Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) through the hole at the bottom of the bezel to secure the facia assembly. Note: The Torx Post Security screw needs only to be lightly tightened. Reader tail Building cable Facia Connection Fit screw to secure facia to bezel 5 7.
6 7 LED (squiggle) Cardax IV indication 3 Flash (Amber) No communications with the Controller. On (Green or Red) Fully configured and functioning normally. Green = Access mode is Free Red = Access mode is Secure Flashes Green Access has been granted. Flashes Red Access has been denied.
8 Approvals and standards This symbol on the product or its packaging indicates that this product must not be disposed of with other waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.
Mounting dimensions 13 mm (1/2") diameter hole for cable 44 mm (1.73") 40 mm (1.57") 115 mm (4.53") 40 mm (1.57") 9 22.5 mm (0.89") 35 mm (1.38") IMPORTANT This picture is not to scale, therefore use the measurements provided.