Design Technical Manual

Table Of Contents
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Remarks
3 7
Outdoor
temperature
zone boundary
temperature
B
0 0 42.8°F (6°C)
l
Setting required if changing of the outdoor
temperature setting for heat pump only zone is
required when heater selection control using
outdoor temperature 1 is performed on the
indoor unit.
For details, refer to Chapter 8. 1-2-2.
EXTERNAL OUTPUT.
0 1 14.0°F (-10°C)
0 2 17.6°F (-8°C)
0 3 21.2°F (-6°C)
0 4 24.8°F (-4°C)
0 5 28.4°F (-2°C)
0 6 32.0°F (0°C)
0 7 35.6°F (2°C)
0 8 39.2°F (4°C)
0 9 42.8°F (6°C)
1 0 46.4°F (8°C)
1 1 50.0°F (10°C)
1 2 53.6°F (12°C)
1 3 57.2°F (14°C)
1 4 60.8°F (16°C)
1 5 64.4°F (18°C)
4 0
Capacity
priority setting
(in low noise
mode)
0 0 O󰀨 (quiet priority)
l
If the cooling/heating performance becomes
insu󰀩cient when the low noise mode is set,
it is possible to set “capacity priority” that
automatically cancels the low noise mode
(once performance is restored, the mode will
automatically return to the low noise mode).
0 1 On (capacity priority)
4 1
Low noise
mode setting
0 0 O󰀨 (Normal)
l
0 1 On (Low noise mode)
4 2 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
6 0 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
6 1 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
- (07 - 85) -
FUNCTION
SETTING
FUNCTION
SETTING